Page 2 - Legal Information
Legal Information The Schneider Electric brand and any registered trademarks of Schneider ElectricIndustries SAS referred to in this guide are the sole property of Schneider Electric SAand its subsidiaries. They may not be used for any purpose without the owner'spermission, given in writing. This gu...
Page 3 - Table of Contents; Important Safety Instructions — SAVE THESE; Drawings
250/500 kW 400/480 V Table of Contents Important Safety Instructions — SAVE THESE INSTRUCTIONS .........................................................................................5 Safety Precautions .....................................................................................6 Technica...
Page 5 - NOTICE; Please Note
Important Safety Instructions — SAVE THESEINSTRUCTIONS 250/500 kW 400/480 V Important Safety Instructions — SAVE THESEINSTRUCTIONS Read these instructions carefully and look at the equipment to become familiarwith it before trying to install, operate, service or maintain it. The following safetymess...
Page 6 - Safety Precautions; DANGER; DANGER
250/500 kW 400/480 V Important Safety Instructions — SAVE THESE INSTRUCTIONS Safety Precautions DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • The product must be installed according to the specifications andrequirements as defined by Schneider Electric. It concerns in particular theexte...
Page 8 - Technical Data; Model List; Systems with Maintenance Bypass and Distribution
250/500 kW 400/480 V Technical Data Technical Data Model List Systems with Maintenance Bypass and Distribution Part Number Description SY100K250DR-PD 100 kW scalable to 250 kW with right mounted maintenance bypass and distribution SY125K250DL-PD 125 kW scalable to 250 kW with left mounted maintenanc...
Page 9 - Efficiency Curves
Technical Data 250/500 kW 400/480 V Efficiency (TÜV Certified) 480 V Systems System 25% load 50% load 75% load 100% load 250 kW 95.2 96.2 96.3 96.3 500 kW 95.5 96.3 96.4 96.3 400/415 V Systems System 25% load 50% load 75% load 100% load 250 kW 95.5 96.1 96.0 95.7 500 kW 95.5 96.1 96.0 95.6 Efficienc...
Page 10 - Derating due to Load Power Factor
250/500 kW 400/480 V Technical Data 500 kW 480 V Curve fit to measured efficiency data. All measurements taken in normal operatingmode, at typical environmental conditions, with 480 V 60 Hz input and 480 V 60Hz balanced resistive load (PF = 1.0) output. Derating due to Load Power Factor The Symmetra...
Page 11 - Electrolyte Values; Material Safety Data Sheets
Technical Data 250/500 kW 400/480 V Electrolyte Values Single Cartridge Single Shelf (6 cartridges) 16 Shelves (96 cartridges) Electrolyte Volume 2.19 L (0.58 gal) 13.14 L (3.48 gal) 210.24 L (55.68 gal) Electrolyte Weight 2.88 kg (6.35 lbs) 17.28 kg (38.1 lbs) 276.48 kg (609.6 lbs) Sulfuric Acid We...
Page 12 - Battery Runtimes
250/500 kW 400/480 V Technical Data Battery Runtimes Symmetra PX 100 kW Scalable to 250 kW 400/480 V Battery Run-Times(Minutes) Load (kW) Part numbers 20 40 60 80 100 A SY100K250DSY100K250DL-PDSY100K250DR-PD 63 27 15 10 7 B + (1)SYBT9-B6 or SYBT9-B6LL 75 32 19 12 9 C + (1)SYBFXR8-8 176 76 47 32 24 D...
Page 19 - Battery Discharge Current
Technical Data 250/500 kW 400/480 V Symmetra PX 500 kW 400/480 V Battery Run-Times (Minutes) Load (kW) Part numbers 20 40 60 80 100 125 150 175 200 300 400 500 A SY500K500DSY500K500DR-PDSY500K500DL-PD 357 168 105 74 57 43 35 28 24 14 9 6 B +(1)SYBFXR8-8 468 220 138 98 75 58 46 38 32 19 12 9 C + (2)S...
Page 20 - End of Discharge Voltage at 100% Load; Communication and Management; Network Management Card
250/500 kW 400/480 V Technical Data End of Discharge Voltage at 100% Load NOTE: The voltage is 1.6 to 1.75 per cell depending on load. NOTE: C equals I discharge divided by the battery Ah capacity. Communication and Management Network Management Card The system is equipped with one network managemen...
Page 23 - Compliance
Technical Data 250/500 kW 400/480 V Compliance • UL 1778 4.th Edition (cUL) • FCC47 CFR 15 subpart B • EN/IEC 62040-1 • EN/IEC 62040-2 990-3880G-001 23
Page 24 - Facility Planning; Input Specifications
250/500 kW 400/480 V Facility Planning Facility Planning Input Specifications 250 kW 500 kW Input voltage (V) 380 1 400 415 480 380 1 400 415 480 Voltage range (v) +/-15% at 100% load (340 - 460 V at 400 V, 408 - 552 V at 480 V)-50% for reduced load (200 V at 400 V, 240 V at 480 V) Input frequency (...
Page 25 - Battery Specifications; Single Configurations
Facility Planning 250/500 kW 400/480 V 250 kW 500 kW 380 V 400 V 415 V 480 V 380 V 400 V 415 V 480 V Nominal outputcurrent (A) 380 361 348 301 760 722 696 601 Output frequency(sync to mains) (Hz) 50/60 Slew rate (Hz/Sec) 0.25 - 6 THDU < 2% linear load< 3% non-linear load Output power factor 1 ...
Page 26 - Overview of Systems without Maintenance Bypass
250/500 kW 400/480 V Facility Planning Single Utility/Mains with Maintenance Bypass Dual Utility/Mains with Maintenance Bypass Overview of Systems without Maintenance Bypass Single Configurations NOTICE HAZARD OF EQUIPMENT DAMAGE The neutral connection to utility/mains must not be disconnected even ...
Page 27 - Parallel Configurations
Facility Planning 250/500 kW 400/480 V Parallel Configurations Single Utility/Mains Dual Utility/Mains 990-3880G-001 27
Page 28 - Parallel Systems
250/500 kW 400/480 V Facility Planning Fuses, Breakers, and Cables in the US In single utility/mains systems, supply the UPS from a grounded 4–wire WYEservice. Schneider Electric also supports 3–wire installations if the utility/mains transformeris a grounded WYE transformer located in the same buil...
Page 30 - Recommended Fuses, Breakers, and Cable Sizes in the US
250/500 kW 400/480 V Facility Planning NOTE: Schneider Electric recommends that each UPS in the parallel system has a neutral connection installed. Contact Schneider Electric for informationon other configurations. Recommended Fuses, Breakers, and Cable Sizes in the US DANGER HAZARD OF ELECTRIC SHOC...
Page 35 - Torque Specifications; Physical; Weights and Dimensions; Shipping Weights and Dimensions
Facility Planning 250/500 kW 400/480 V Torque Specifications Bolt size M8 Bolt size M10 13.5 Nm 30 Nm Physical Weights and Dimensions Modules Weight kg (lbs) Power module (SYPM25KD) 42 (92) Battery unit (SYBTU2-PLP, SYBTU2-PLPLL) 25.5 (56) Static bypass switch 250kVA (SYSW250KD) 79 (174) Static bypa...
Page 36 - Clearance
250/500 kW 400/480 V Facility Planning Clearance DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH The required free space to other equipment containing live parts is 1219 mm(48 in). Failure to follow these instructions will result in death or serious injury. NOTE: Clearance dimensions are pub...
Page 38 - Environmental; Heat Dissipation
250/500 kW 400/480 V Facility Planning Environmental Operating Temperature 0 to 40° C Storage Temperature -15 to 40° C for systems with batteries-30 to 70° C for systems without batteries Operating Relative Humidity 0 - 95% Storage Relative Humidity 0 - 95% Operating Elevation 0-1000 m: 100% load100...
Page 56 - Options; Hardware Options; Breakers
250/500 kW 400/480 V Options Options Hardware Options Breakers NOTE: 4–pole breakers are not available as an option in North America. • T1 breaker kit for unsupported breaker amperages with current transformerwithout adaptors • T3 breaker kit for unsupported breaker amperages with current transforme...
Page 57 - Other Options; Configuration Options
Options 250/500 kW 400/480 V • Pair of value battery cabinets with 7 minute battery @ 250 kW • Pair of value battery cabinets with 7 minute battery @ 250 kW and includingbattery management Other Options • Air filters • Optional terminal blocks • 3.rd party switch gear kit • Paralleling cable • Seism...
Page 58 - Limited Factory Warranty; One-Year Factory Warranty
250/500 kW 400/480 V Limited Factory Warranty Limited Factory Warranty One-Year Factory Warranty The limited warranty provided by Schneider Electric in this Statement of LimitedFactory Warranty applies only to products you purchase for your commercial orindustrial use in the ordinary course of your ...
Page 59 - Exclusions
Limited Factory Warranty 250/500 kW 400/480 V Exclusions Schneider Electric shall not be liable under the warranty if its testing andexamination disclose that the alleged defect in the product does not exist or wascaused by end user or any third person misuse, negligence, improper installationor tes...