Page 3 - Contents; About This Guide
HP Uninterruptible Power System T2200 XR Models User Guide iii Contents About This Guide Audience Assumptions ............................................................................................................................... vii Important Safety Information ................................
Page 4 - China Taiwan
Contents iv HP Uninterruptible Power System T2200 XR Models User Guide Chapter 3 Configuration Placing the UPS in Configure Mode ......................................................................................................... 3-1 Configuration Parameters........................................
Page 5 - Appendix C
Contents HP Uninterruptible Power System T2200 XR Models User Guide v Appendix C Specifications Physical Specifications ............................................................................................................................. C-1 Input Specifications ................................
Page 6 - Audience Assumptions; Before installing this product, read the; Symbols on Equipment
HP Uninterruptible Power System T2200 XR Models User Guide vii About This Guide This guide provides step-by-step instructions for configuration, and reference information for operation, battery maintenance, and troubleshooting for the Uninterruptible Power System (UPS). Audience Assumptions This gui...
Page 7 - Symbols in Text; Related Documents; HP UPS XR Products Power Cord and Options Reference Guide; Getting Help
About This Guide viii HP Uninterruptible Power System T2200 XR Models User Guide Symbols in Text These symbols may be found in the text of this guide. They have the following meanings. WARNING: Text set off in this manner indicates that failure to follow directions in the warning could result in bod...
Page 8 - Technical Support; Reader’s Comments
About This Guide HP Uninterruptible Power System T2200 XR Models User Guide ix Technical Support In North America, call the HP Technical Support Phone Center at 1-800-652-6672. This service is available 24 hours a day, 7 days a week. For continuous quality improvement, calls may be recorded or monit...
Page 9 - Overview; UPS Features; Communications Port
HP Uninterruptible Power System T2200 XR Models User Guide 1-1 1 Overview This chapter contains a general overview of the HP UPS, including an introduction to the model configurations, power management software, available hardware options, and warranties. Read this chapter to become familiar with th...
Page 10 - Network Transient Protector
Overview 1-2 HP Uninterruptible Power System T2200 XR Models User Guide Network Transient Protector The UPS includes a Network Transient Protector (NTP) that provides surge protection for connected communication devices. CAUTION: To avoid damaging the equipment, do not connect the Network Transient ...
Page 11 - Front Panel; The front panel of the UPS is shown in Figure 1-1.
Overview HP Uninterruptible Power System T2200 XR Models User Guide 1-3 Front Panel The front panel of the UPS is shown in Figure 1-1. 3 1 2 Figure 1-1: Front panel configuration 1 LED display 2 Control buttons 3 Battery compartment For detailed information on using the control buttons and LED indic...
Page 12 - Rear Panels
Overview 1-4 HP Uninterruptible Power System T2200 XR Models User Guide Rear Panels The rear panel configurations of the UPS are shown in Figures 1-2, 1-3, 1-4, and 1-5. 1 3 2 4 5 6 8 7 Figure 1-2: Rear panel of T2200 XR NA 1 Communications port/option slot 2 Network Transient Protector IN jack 3 Ne...
Page 16 - Power Management Software; Monitors the status of the UPS and performs UPS diagnostics; UPS Hardware Options; HP UPS XR Products
Overview 1-8 HP Uninterruptible Power System T2200 XR Models User Guide Power Management Software Power management software ensures maximum power reliability of HP computer systems through comprehensive control of HP UPSs. Specifically, power management software performs the following: IMPORTANT: No...
Page 17 - Warranties; $25,000 Computer Load Protection Guarantee; The $25,000 Computer Load Protection Guarantee applies only if:; Pre-Failure Battery Warranty
Overview HP Uninterruptible Power System T2200 XR Models User Guide 1-9 Warranties To back up the wide range of features offered with the UPS, HP provides a three-year limited warranty. $25,000 Computer Load Protection Guarantee In addition to the limited warranty, HP offers a $25,000 Computer Load ...
Page 18 - Operation; Front Panel Controls and LED Indicators
HP Uninterruptible Power System T2200 XR Models User Guide 2-1 2 Operation This chapter contains information on operating the UPS. Topics include the front panel controls, LED indicators, and modes of operation. Knowledge of these features is helpful when configuring and troubleshooting the unit. NO...
Page 19 - Modes of Operation; Standby Mode
Operation 2-2 HP Uninterruptible Power System T2200 XR Models User Guide continued Item Description Meaning/Function 6 Site Wiring Fault Indicator ( ) Red—No ground connection exists between utility power and the UPS, the line and neutral connections between utility power and the UPS are reversed, o...
Page 20 - Charging the Batteries; Placing the UPS in Operate Mode; The UPS is powered down and no utility power is available.
Operation HP Uninterruptible Power System T2200 XR Models User Guide 2-3 Charging the Batteries When the UPS is in Standby mode, allow the batteries to charge before putting the UPS into service. IMPORTANT: The batteries charge to: • 90 percent of their capacity within 3 hours • 100 percent of their...
Page 21 - Returning to Standby Mode
Operation 2-4 HP Uninterruptible Power System T2200 XR Models User Guide Returning to Standby Mode When the UPS is in Operate mode (the Utility LED is solid green), press and hold the Standby button (2) until the audible alarm sounds. The Utility LED (1) flashes, and power to the loads ceases. 1 2 F...
Page 22 - Initiating a Self-Test
Operation HP Uninterruptible Power System T2200 XR Models User Guide 2-5 Initiating a Self-Test To initiate a self-test, press and hold the Test/Alarm Reset button (1) for three seconds. 1 Figure 2-4: Test/Alarm Reset button Because a portion of the self-test requires battery power, the self-test ca...
Page 23 - Audible Alarms; Silencing an Audible Alarm; Shutting Down the System; To shut down the system:
Operation 2-6 HP Uninterruptible Power System T2200 XR Models User Guide Audible Alarms The UPS may sound an audible alarm to warn of a problem. For information on what to do if the UPS detects an alarm condition, refer to Chapter 5, “Troubleshooting.” Silencing an Audible Alarm To silence an audibl...
Page 24 - Configuration; Placing the UPS in Configure Mode; The UPS can enter Configure mode while in Operate or Standby mode.
HP Uninterruptible Power System T2200 XR Models User Guide 3-1 3 Configuration This chapter contains information on configuring the UPS. Proper configuration of the UPS is important in performing other functions on the unit, such as maintaining the battery and troubleshooting alarms. Placing the UPS...
Page 25 - Configuration Parameters
Configuration 3-2 HP Uninterruptible Power System T2200 XR Models User Guide 2. Press and hold the Configure button (2) for three seconds. When the Configure button is released, the front panel configuration parameters flash in unison and the Configure Mode On LED (1) illuminates solid green. 1 2 Fi...
Page 26 - Changing Configuration Parameters; Refer to Figure 3-3 when changing configuration parameters.; To change configuration parameters:
Configuration HP Uninterruptible Power System T2200 XR Models User Guide 3-3 Table 3-2: Available Voltage Settings UPS Model Available Settings Utility Voltage (VAC) Parameter (LED) T2200 XR NA 110 On Battery ( ) 120 (default) Bad Battery/Low Battery ( ) 127 Site Wiring Fault Indicator ( ) T2200 XR ...
Page 28 - Battery Maintenance; Precautions; Charging Batteries
HP Uninterruptible Power System T2200 XR Models User Guide 4-1 4 Battery Maintenance This chapter contains information for properly maintaining batteries for the UPS, including battery charging, replacement, disposal procedures, and warranties. Precautions WARNING: There is a risk of personal injury...
Page 29 - Determining When to Replace Batteries
Battery Maintenance 4-2 HP Uninterruptible Power System T2200 XR Models User Guide Determining When to Replace Batteries When the Bad Battery/Low Battery LED (1) illuminates red, batteries may need to be replaced within 30 to 60 days. 1 Figure 4-1: Bad Battery/Low Battery LED To check a battery alar...
Page 30 - Replacing Batteries; There are two options for replacing UPS batteries:; Preparing the UPS; To replace batteries with the UPS powered down:
Battery Maintenance HP Uninterruptible Power System T2200 XR Models User Guide 4-3 Replacing Batteries There are two options for replacing UPS batteries: • Powering down the UPS before removing the batteries • In certain circumstances, replacing the batteries without powering down the UPS CAUTION: W...
Page 31 - Removing the Battery Pack; To remove the battery pack:
Battery Maintenance 4-4 HP Uninterruptible Power System T2200 XR Models User Guide Removing the Battery Pack To remove the battery pack: 1. Remove the front bezel by depressing the tab located under the front bezel and pulling from the bottom (1). The LED/control button pedestal remains attached to ...
Page 32 - “Disposing of Used Batteries,” in this chapter.; Installing a New Battery Pack
Battery Maintenance HP Uninterruptible Power System T2200 XR Models User Guide 4-5 4. Unfasten the plastic handle (1) and partially remove the battery pack (2). 5. Disconnect the battery cable by pressing the black tab on the connector (3) and pulling apart (4). 2 1 3 4 Figure 4-4: Disconnecting the...
Page 33 - Testing the New Battery Pack; Care and Storage of Batteries; To maximize the life of batteries:
Battery Maintenance 4-6 HP Uninterruptible Power System T2200 XR Models User Guide Testing the New Battery Pack After installing the new battery pack, press the Test/Alarm Reset button. For information on initiating a self-test, refer to the section, “Initiating a Self-Test,” in Chapter 2. IMPORTANT...
Page 34 - warning
Battery Maintenance HP Uninterruptible Power System T2200 XR Models User Guide 4-7 Pre-Failure Battery Warranty The Pre-Failure Battery Warranty, standard on all HP UPS units, extends the advantage of an HP three-year limited warranty by applying it to the battery before it actually fails. Specifica...
Page 35 - Troubleshooting; Troubleshooting During Startup
HP Uninterruptible Power System T2200 XR Models User Guide 5-1 5 Troubleshooting This chapter serves as a troubleshooting guide when problems occur with the UPS. Solutions for UPS problems that occur both during and after startup are covered. Troubleshooting During Startup If problems occur when sta...
Page 36 - Troubleshooting After Startup
Troubleshooting 5-2 HP Uninterruptible Power System T2200 XR Models User Guide Troubleshooting After Startup If problems occur after starting the UPS, refer to Table 5-2 for possible causes and suggested actions. Table 5-2: Troubleshooting After Startup Symptom Possible Cause Suggested Action An aud...
Page 37 - Repairing the UPS
Troubleshooting HP Uninterruptible Power System T2200 XR Models User Guide 5-3 Table 5-2: Troubleshooting After Startup continued Symptom Possible Cause Suggested Action The Overload LED is red. Protected devices are exceeding the UPS power rating. Remove one or more devices to reduce the power requ...
Page 38 - Regulatory Compliance Notices; Regulatory Compliance Identification Numbers; Class A Equipment
HP Uninterruptible Power System T2200 XR Models User Guide A-1 A Regulatory Compliance Notices Regulatory Compliance Identification Numbers For the purpose of regulatory compliance certifications and identification, your product has been assigned a unique series number. The series number can be foun...
Page 39 - Class B Equipment; Reorient or relocate the receiving antenna.; Modifications
Regulatory Compliance Notices A-2 HP Uninterruptible Power System T2200 XR Models User Guide Class B Equipment This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protec...
Page 40 - Cables; European Union Notice; EN50091-1 – UPS Product Safety Requirements
Regulatory Compliance Notices HP Uninterruptible Power System T2200 XR Models User Guide A-3 Cables Connections to this device must be made with shielded cables with metallic RFI/EMI connector hoods in order to maintain compliance with FCC Rules and Regulations. Canadian Notice (Avis Canadien) Class...
Page 41 - Japanese Notice
Regulatory Compliance Notices A-4 HP Uninterruptible Power System T2200 XR Models User Guide Japanese Notice China Taiwan Notice
Page 42 - Battery Replacement Notice
Regulatory Compliance Notices HP Uninterruptible Power System T2200 XR Models User Guide A-5 Battery Replacement Notice The UPS is equipped with a sealed lead-acid battery pack. There is a danger of explosion and risk of personal injury if the battery is incorrectly replaced or mistreated. Replaceme...
Page 43 - Electrostatic Discharge; Grounding Methods; Use conductive field service tools.
HP Uninterruptible Power System T2200 XR Models User Guide B-1 B Electrostatic Discharge To prevent damaging the system, be aware of the precautions you need to follow when setting up the system or handling parts. A discharge of static electricity from a finger or other conductor may damage system b...
Page 44 - Specifications; Physical Specifications
HP Uninterruptible Power System T2200 XR Models User Guide C-1 C Specifications This appendix provides the physical, input, and output specifications for the UPS. Topics also include battery descriptions, battery runtime estimates, and environmental requirements when operating the UPS. Physical Spec...
Page 45 - Input Specifications
Specifications C-2 HP Uninterruptible Power System T2200 XR Models User Guide Input Specifications Table C-2: Input Specifications UPS Model Utility Voltage Frequency (Hz) Default Settings Nominal Voltage (VAC) Available Settings Utility Voltage (VAC) Power Cord Supplied T2200 XR NA 50/60 120 110, 1...
Page 46 - Output Specifications
Specifications HP Uninterruptible Power System T2200 XR Models User Guide C-3 Output Specifications Table C-3: Output Specifications UPS Model Effective VA Nominal Power Rating (W) Load Segment # Output Receptacles T2200 XR NA 1920 1600 1 3 x 5-15R 2 3 x 5-15R 3 2 x 5-20R T2200 XR JPN 2200 1600 1 3 ...
Page 47 - Battery Specifications
Specifications C-4 HP Uninterruptible Power System T2200 XR Models User Guide Table C-4: Output Specifications Characteristics Configuration Setting (VAC) Available Nominal Output Voltage (VAC) Available Nominal Output Voltage (VAC) on Battery Voltage 100 100 110* 110 110 110 120 120 120 127 127 120...
Page 48 - Environmental Specifications
Specifications HP Uninterruptible Power System T2200 XR Models User Guide C-5 Environmental Specifications Table C-6: Environmental Specifications Feature Specification Operating temperature 10 o C to 40 o C (50 o F to 104 o F) UL-tested at 25 o C (77 o F) Non-operating temperature -15 o C to 55 o C...
Page 49 - Index
HP Uninterruptible Power System T2200 XR Models User Guide Index-1 Index A alarms See audible alarms altitude specifications C-5 audible alarms enabling and disabling for Site Wiring Fault detection 3-2 silencing 2-6 troubleshooting 5-1 authorized reseller ix B Bad Battery/Low Battery LED 2-2 batter...