Field Controls UV-12HP - Manual
Field Controls UV-12HP – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 8 – ALARM CIRCUIT WIRING; Loosen the cover screw and open the unit cover.
- Page 9 – BULB MOUNTING BRACKET SELECTION; Installation; UV-AireTM Configurations; Good Best
- Page 10 – VIII. REPLACEMENT PROCEDURE; Turn switch on unit to “OFF” position and unplug unit from outlet.; When replacing the lamp, always wipe off lamp before installing.
- Page 11 – GUIDE; replaced immediately.; REPLACEMENT PARTS LIST; MODEL; DUCT
- Page 12 – WARRANTY INFORMATION; Limited
UV-AIRE™ AIR PURIFYING SYSTEM
Model: UV-12C,18C,28C,28,12HP,18HP,28HP,12HPC,18HPC,28HPC
READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION
LEAVE
THE
INSTALLATION
INSTRUCTIONS
WITH
THE
OWNER/OPERATOR
OF
THE
DEVICE
AFTER
OPENING
THE
CARTON,
UNPACK
AND
INSPECT
THE
UNIT
AND
LAMP
FOR
DAMAGE.
DO
NOT
INSTALL
THIS
UNIT
IF
ANY
DAMAGE
IS
NOTICEABLE.
SAFETY CONSIDERATIONS
WARNING:
Never expose eyes or skin to UVC light from any source.
•
Looking directly at the UVC light may cause permanent eye damage or blindness.
•
Never operate the UV-Aire™ Air Purifying System out of the plenum
.
•
Designed for a closed duct system. Do not mount near a supply or a return air opening
•
All duct openings in direct line of site of the UV light must be sealed with aluminum tape or equivalent
sealing methods.
WARNING: UV light will break down plastic materials not rated for UV exposure:
(Examples: wire insulation, flex duct, drain pans and humidifiers)
•
The unit must be mounted at least 30” from the above stated type of materials.
•
If it is necessary to mount the unit in direct line of site of these types of materials, they must be shielded
with aluminum foil, aluminum foil tape, or sheet metal.
WARNING: DO NOT mount this unit outdoors.
•
This product is designed for indoor installation only (i.e. attics, crawl spaces, basements, etc.).
ITEMS
INCLUDED
IN
KIT:
1-UV-Aire
™
power unit
4-Sheet metal mounting screws
1-Angled mounting bracket
1-Flat mounting bracket
1-Duct board mounting bracket
1-Ultra Violet lamp
1-Instruction Sheet
1-Wing nut
Caution Labels
Gasket
UV-C light inhibits the growth and reproduction of germs and bacteria that circulate through a
homes’ heating and air conditioning system. The treatment is a safe, silent, and proven way
to make your home a healthier place to live.
*Exclusive 5 position lamp mounting feature!
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
Page 8 V. ALARM CIRCUIT WIRING The UV Aire units supplied with a circuit board allows for the wiring of the UV Aire unit into an alarm or security system to monitor the operation of the UV lamp. This circuit is a set of normal open contacts that close if the operational time exceeds 9000 hrs or if t...
Page 9 Chart A VI. BULB MOUNTING BRACKET SELECTION The UV-AIRE TM units come with an angled mounting bracket and flat mounting bracket to position the bulb either straight or at an angle. Choose one or the other bracket method best suited for your needs. Refer to the configurations chart below when ...
Page 10 VII. MAINTENANCE 1. Inspect and clean lamp at least every 6 months. 2. Replace your UV-Aire™ Air Purifying System lamp once a year to maintain the lamps maximum output intensity. The lamp should operate continuously for maximum lamp life and light effectiveness. VIII. REPLACEMENT PROCEDURE V...