HIGH TEMPERATURE VENT LIMIT SWITCH

Models: LS-140A, LS-550A

Items Included:

1) High temperature vent limit switch

1) TCA-1 thermocouple junction block (LS-550A)

2) 2-1/2 to 5-1/2 inch hose clamps

1) 6 foot length of 12/2 wire (LS-550A)

1) Tube of high temperature sealant

2) Wire hold down clips (LS-550A)

4) Wiring quick connect terminals (LS-140A)

1) ROMEX connector

Installation of a High temperature vent limit switch is recommended for LP and Natural gas fired power
vented and natural draft water heaters. This device is installed to limit the vent temperature in either
plastic pipe (140

0

F temperature limit) or B vent installations (550

0

F temperature limit) caused by scaled

up tanks and/or inadequate venting. Wiring MUST be in accordance with the National Electrical Code and
applicable local codes.

The Field Controls High temperature vent limit switch

MUST be installed by a qualified agency in

accordance with the manufacturer’s installation instructions.

The definition of a qualified agency is:

any individual, firm, corporation or company which either in person

or through a representative is engaged in, and is responsible for, the installation and operation of gas
appliances, who is experienced in such work, familiar with all the precautions required, and has complied
with the requirements of the authority having jurisdiction.

Before and after adding this safety control on existing appliances, an installation inspection in accordance
with the National Fuel Gas Code 54, Z223.1 Appendix H should be performed and a combustion analysis
is recommended to determine the operating condition of the appliance.

CAUTION:

Disconnect Electrical Power When Wiring High temperature vent limit switch

MODEL

P/N

CONTACT

MATERIAL

LOAD RATING

LIMIT

SETPOINT °F

RESET

SWITCH

TYPE

APPLICATION

AMPS VOLTS

LS-140A

46564100

SILVER

15 A

120 AC

140

AUTOMATIC

SPDT

PLASTIC VENT APPLICATIONS

LS-550A

46564200

SILVER

15 A

120 AC

550

AUTOMATIC

SPDT

B-VENT APPLICATIONS