Page 3 - Align the captive screws on the cFP-PG-522 with the holes on
© National Instruments Corp. 3 FP-PG-522 and cFP-PG-522 To install the cFP-PG-522, refer to Figure 2 and complete the following steps: 1. Align the captive screws on the cFP-PG-522 with the holes on the backplane. The alignment keys on the cFP-PG-522 prevent backward insertion. 2. Press firmly to se...
Page 4 - Caution
FP-PG-522 and cFP-PG-522 4 ni.com Wiring the [c]FP-PG-522 The FP-TB- x terminal base has connections for each of the eight output channels and for an external power supply to power the output channels and field devices. The cFP-CB- x connector block provides the same connections. Each channel has on...
Page 5 - Pulse Output Circuit; Channel; COM
© National Instruments Corp. 5 FP-PG-522 and cFP-PG-522 Table 1 lists the terminal assignments for the signals of each channel. Terminal assignments are also listed on the side panel of the cFP-PG-522 and under the slide-in card on the front of the FP-PG-522. Pulse Output Circuit The [c]FP-PG-522 ou...
Page 6 - In the ON state, the effective resistance between V; and COM; Configuring the Count-Input Channels; Attributes; Pulse Mode; Channel Commands; Channel Subset
FP-PG-522 and cFP-PG-522 6 ni.com Table 2 shows some common combinations of output current levels on several channels. In the ON state, the effective resistance between V OUT and COM is 0.12 Ω , which causes a voltage drop. For example, if the output current is 1 A, the voltage drop is 0.12 V: (1 A ...
Page 7 - On Time; Resolution
© National Instruments Corp. 7 FP-PG-522 and cFP-PG-522 A channel set to Continuous mode must be switched to Finite mode in order to stop pulse generation. When switched to Finite mode from Continuous mode, a channel finishes generating the current pulse and then stops. On Time The On Time attribute...
Page 9 - POWER; and; READY; indicator lights; Physical Channel
© National Instruments Corp. 9 FP-PG-522 and cFP-PG-522 values, which reflect the number of pulses each channel has left to generate after the current pulse. When you send the Generate Pulses command to one of these channels, the data immediately changes to reflect the number of pulses that remain. ...
Page 10 - Upgrading the FieldPoint Firmware; Isolation and Safety Guidelines; not
FP-PG-522 and cFP-PG-522 10 ni.com When the network module recognizes the [c]FP-PG-522, it sends initial configuration information to the [c]FP-PG-522. After the [c]FP-PG-522 receives this initial information, the green READY indicator lights and the [c]FP-PG-522 is in normal operating mode. In addi...
Page 11 - following symbol stamped beside it:; Specifications; Output; Maximum output current
© National Instruments Corp. 11 FP-PG-522 and cFP-PG-522 following symbol stamped beside it: . Connect the backplane PE ground terminal to the system safety ground using 14 AWG (1.6 mm) wire with a ring lug. Use the 5/16 in. panhead screw shipped with the backplane to secure the ring lug to the back...
Page 12 - Physical Characteristics; green output state indicators; Power Requirements; channels; Environmental; noncondensing; Shock and Vibration
FP-PG-522 and cFP-PG-522 12 ni.com Physical Characteristics Indicators .......................................... Green POWER and READY indicators, eight green output state indicators Weight FP-PG-522.................................. 130 g (4.6 oz)cFP-PG-522 ................................ 100 g (...
Page 13 - Safety; must; CE Compliance; Note; Declarations of Conformity Information
© National Instruments Corp. 13 FP-PG-522 and cFP-PG-522 Operating shock (IEC 60068-2-27).............................. 50 g, 3 ms half sine, 18 shocks at 6 orientations;30 g, 11 ms half sine, 18 shocks at 6 orientations Safety This product is designed to meet the requirements of the following stand...
Page 14 - Mechanical Dimensions; Where to Go for Support
FP-PG-522 and cFP-PG-522 14 ni.com Mechanical Dimensions Figure 5 shows the mechanical dimensions of the FP-PG-522 installed on a terminal base. If you are using the cFP-PG-522, refer to your Compact FieldPoint controller user manual for the dimensions and cabling clearance requirements of the Compa...