Page 2 - Mount the Compact FieldPoint Backplane; backplane on a 35mm DIN rail, on a panel, or in a; Keep in mind these requirements for space and cabling
cFP-21xx Quick Start Guide 2 ni.com 1. Mount the Compact FieldPoint Backplane You can mount the cFP-BP- x backplane on a 35mm DIN rail, on a panel, or in a standard 19 in. rack. Before using any of these mounting methods, record the serial number from the back of the backplane. Each set of mounting ...
Page 3 - If you are using UL Recognized I\O modules with the Compact
© National Instruments Corporation 3 cFP-21xx Quick Start Guide Caution If you are using UL Recognized I\O modules with the Compact FieldPoint system, you must install the entire system in a suitably rated, UL Listed NEMA or IP enclosure. Cabling Clearance Cooling Outline 51 mm (2 in.) All Around 4 ...
Page 4 - NI recommends that you use one of the mounting systems
cFP-21xx Quick Start Guide 4 ni.com Caution NI recommends that you use one of the mounting systems described in this document. If you decide to use a custom mounting solution, make sure that the screws you use are short enough to fit in the holes in the backplane. The screw holes are 5 mm (0.2 in.) ...
Page 5 - Mounting the Backplane on a Panel; using a; Do not use screws longer than 5/16 in. to fasten the
© National Instruments Corporation 5 cFP-21xx Quick Start Guide Mounting the Backplane on a Panel 1. Fasten the panel-mount plates to the back of the cFP-BP- x using a number 2 Phillips screwdriver and the 8-32 × 5/16 in. countersink screws shipped with the kit. Caution Do not use screws longer than...
Page 7 - Disconnect power before removing the backplane from the; Mounting the Backplane on a DIN Rail
© National Instruments Corporation 7 cFP-21xx Quick Start Guide 2. Bolt or screw the panel-mount accessory to a panel. 3. Connect the PE ground terminal on the cFP-BP- x to safety ground. Caution Disconnect power before removing the backplane from the panel. Mounting the Backplane on a DIN Rail NI r...
Page 8 - Do not use screws longer than 5/16 in. to fasten the DIN rail
cFP-21xx Quick Start Guide 8 ni.com Caution Do not use screws longer than 5/16 in. to fasten the DIN rail clip to the backplane. 2. Insert one edge of the DIN rail into the deeper opening of the DIN rail clip. 3. Press down firmly on the backplane to compress the spring until the clip locks in place...
Page 9 - Mounting the Backplane in a Standard 19 in. Rack; using the captive
© National Instruments Corporation 9 cFP-21xx Quick Start Guide Mounting the Backplane in a Standard 19 in. Rack 1. Fasten the rack-mount bracket to the back of the cFP-BP- x using the captive screws on the bracket. 2. Bolt the rack-mount accessory to a standard 19 in. rack. NA TIO NA L INS TR UM EN...
Page 11 - xx; Controller on the Backplane; Make sure that no power is connected to the controller.
© National Instruments Corporation 11 cFP-21xx Quick Start Guide 2. Install the cFP-21 xx Controller on the Backplane 1. Make sure that no power is connected to the controller. 2. Make sure that the cFP-21 xx controller is right side up with the NI logo at the top, and align the captive screws on th...
Page 13 - Install Connector Blocks on the Backplane
© National Instruments Corporation 13 cFP-21xx Quick Start Guide 4. Install Connector Blocks on the Backplane In order to connect I/O modules to input signals or to external loads, you need to install a cFP-CB- x connector block or other connectivity accessory for each I/O module on the backplane. U...
Page 14 - to Your Network
cFP-21xx Quick Start Guide 14 ni.com 5. Connect the cFP-21 xx to Your Network Connect the cFP-21 xx controller to an Ethernet network using the RJ-45 Ethernet port on the controller. Use a standard Category 5 Ethernet cable to connect the cFP-21 xx to an Ethernet hub, or use an Ethernet crossover ca...
Page 15 - Wire Power to the Compact FieldPoint System; Cascading power defeats isolation between the cascaded
© National Instruments Corporation 15 cFP-21xx Quick Start Guide 6. Wire Power to the Compact FieldPoint System Each cFP-21 xx on your network requires an 11–30 VDC power supply. 1. Connect the positive lead of the primary power supply to one of the V1 terminals and the negative lead to one of the C...
Page 16 - DIP Switches
cFP-21xx Quick Start Guide 16 ni.com 7. Power Up the cFP-21 xx Check the DIP switches on the controller, making sure that the RESET IP switch is in the OFF position. Plug in each power supply to the Compact FieldPoint system. The cFP-21 xx runs a power-on self test (POST) that takes several seconds....
Page 17 - Install Software on the Host PC; Start»Run; Start»Programs»
© National Instruments Corporation 17 cFP-21xx Quick Start Guide 8. Install Software on the Host PC 1. Install the software packages you plan to use, such as LabVIEW, the LabVIEW Real-Time Module, Measurement Studio, VI Logger, or LabWindows ™ /CVI ™ , before you install the FieldPoint software. The...
Page 18 - Compact FieldPoint Safety Information
cFP-21xx Quick Start Guide 18 ni.com Compact FieldPoint Safety Information The following section contains important safety information that you must follow when installing and using Compact FieldPoint products. Do not operate Compact FieldPoint products in a manner not specified in the user manual o...
Page 21 - Using This Product Safely in Hazardous Locations; Explosion hazard—Substitution of components may impair; Specifications; Network
© National Instruments Corporation 21 cFP-21xx Quick Start Guide Using This Product Safely in Hazardous Locations This product is suitable for use in U.S. and Canada: Class I, Division 2, Groups A, B, C, D, T4 hazardous locations; and nonhazardous locations. Caution Explosion hazard—Substitution of ...
Page 22 - Memory; and enter; Serial Ports; one RS-485 serial port
cFP-21xx Quick Start Guide 22 ni.com Memory cFP-2100 ........................................... 64 MB nonvolatile; 64 MB DRAM cFP-2110 ........................................... 64 MB nonvolatile; 128 MB DRAM cFP-2120 ........................................... 128 MB nonvolatile; 128 MB DRAM Memo...
Page 23 - , verified by 5 s test; Power Requirement; Recommended power supply; Physical Characteristics
© National Instruments Corporation 23 cFP-21xx Quick Start Guide RS-485 (DTE) serial port Baud rate .................................... 110 to 115,200 bpsData bits...................................... 5, 6, 7, 8Stop bits ...................................... 1, 1.5, 2Parity .........................
Page 24 - Environmental; voltage ratings must be lowered; Shock and Vibration; Operating vibration; Safety
cFP-21xx Quick Start Guide 24 ni.com Environmental FieldPoint modules are intended for indoor use only. For outdoor use, they must be installed in a suitable sealed enclosure. Operating temperature ...................... – 40 to 70 °C Storage temperature .......................... – 40 to 85 °C Humi...
Page 25 - For UL, hazardous location, and other safety certifications, refer; Electromagnetic Compatibility; FCC 47 CFR Part 15B: Class A emissions; For EMC compliance, operate this device with shielded cabling.; CE Compliance
© National Instruments Corporation 25 cFP-21xx Quick Start Guide Note For UL, hazardous location, and other safety certifications, refer to the product label or visit ni.com/certification , search by model number or product line, and click the appropriate link in the Certification column. Electromag...
Page 26 - Refer to the Declaration of Conformity (DoC) for this product for; Cabling
cFP-21xx Quick Start Guide 26 ni.com Note Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory compliance information. To obtain the DoC for this product, visit ni.com/certification , search by model number or product line, and click the appropriate link in the...
Page 27 - Where to Go for Support; you have access to everything from
Where to Go for Support The National Instruments Web site is your complete resource for technical support. At ni.com/support you have access to everything from troubleshooting and application development self-help resources to email and phone assistance from NI Application Engineers. National Instru...