Page 3 - GENERAL; Trademark Information
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 3 31-00475-01 GENERAL Trademark Information • Spyder™ is a trademark of Honeywell International Inc. • BACnet® is a registered trademark of ASHRAE Inc. • Sylk™ is a trademark of Honeywell International Inc. Product Description Honeywell’s Spyde...
Page 4 - Dimensions; Fig. 2 Spyder Model 7 VAV Dimensions; NETWORK SECURITY; WARNING; GENERAL SAFETY; CAUTION
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 4 Dimensions Fig. 2 Spyder Model 7 VAV Dimensions NETWORK SECURITY WARNING Honeywell hereby expressly states that the Spyder™ Model 7 VAV controllers are not inherently protected against all cyber security risks from the Internet an...
Page 5 - SPECIFICATIONS; Electrical
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 5 31-00475-01 SPECIFICATIONS Electrical Operational Environment Hardware Integrated Actuator Table 3 Electrical Specification Parameter Specification Rated input voltage 20 - 30 VAC; Class 2 transformer Nominal Power Consumption IP model: 8 VA;...
Page 6 - Communications; Range
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 6 Communications Modbus Client Sylk™ Supported Devices Differential Pressure Sensor Weight And Dimensions Table 7 Communication Specification Parameter Specification Protocol supported BACnet IP, BACnet MSTP, Sylk™, Modbus RTU (Modb...
Page 7 - Universal IO
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 7 31-00475-01 Universal IO Solid State Relay (SSR) Wireless Connectivity Table 12 Universal IO Specification Parameter Specification AO (Analog output) Voltage: 0(2) to 10 VDC direct or reverse with -3 mA to 20 mA Current: 0 (4) to 2 0 mA UI (U...
Page 8 - HARDWARE OVERVIEW; IP Model; Fig. 3 IP Model Hardware Overview; MSTP Model; Fig. 4 MSTP Model Hardware Overview
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 8 HARDWARE OVERVIEW IP Model Fig. 3 IP Model Hardware Overview MSTP Model Fig. 4 MSTP Model Hardware Overview 6(59ආ&(%87721 6\ඇN:$// 02'8/(6 9$& 32:(5 62/ආ'67$7( 5(/$<6665 )ආ(/'5(3/$&($%/( $ආ5)/2:6(1625 '(&/87&am...
Page 9 - Service Button; Fig. 5 Service Button Location; Pressing Service Button during normal operation; MOUNTING; Before Mounting Actuator; Fig. 6 Determining the Rotation Direction (CW or
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 9 31-00475-01 Service Button Fig. 5 Service Button Location The service button is used to trigger dedicated events. It is important to distinguish different controller behaviors which are elicited depending upon whether the service button is pr...
Page 10 - Mounting Actuator onto Damper
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 10 NOTE: Mount the actuator flush with damper housing or add a spacer between the actuator mounting sur - face and damper box housing. Fig. 8 Mounting Controller to VAV Box Damper Housing when Actuator is not Parallel to VAV Box Dam...
Page 11 - and the angle of the damper open-to-closed is
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 11 31-00475-01 cator on the bracket represents approximately 6.5 ° of rotation per side. The declutch button, when pressed, allows you to rotate the universal shaft adapter. The unit is shipped with the actuator set to rotate open in the clockw...
Page 12 - Airflow Sensor Connection; Fig. 11 Airflow Pickup Connections; Differential Pressure Installation
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 12 Airflow Sensor Connection Connect the airflow pickup to the two restrictor ports on the controller. NOTE: Use 1/4 in. (6 mm outside diameter and 5 mm inner diameter), with a 3/64 in. (1 mm) wall thick - ness, plenum-rated 1219 FR...
Page 13 - Airflow Sensor Replacement; Fig. 12 Removing the Airflow Sensor Cover
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 13 31-00475-01 Airflow Sensor Replacement Procedure to replace the airflow sensor is as follows: 1. Gently pull the sensor cover outward and rotate it by 75 ° . Fig. 12 Removing the Airflow Sensor Cover 2. Disconnect the electrical connector by...
Page 14 - POWER SUPPLY; General Information
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 14 POWER SUPPLY General Information To prevent a risk of injury due to electrical shock and/or damage to the device due to short-circuiting, low- voltage and high-voltage lines must be kept physically separate. To prevent a risk of ...
Page 15 - Power Wiring Examples; Fig. 14 Power Wiring Examples
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 15 31-00475-01 Power Wiring Examples Fig. 14 Power Wiring Examples UL Listed Class 2 Transformer 100 VA 120 / 240 VAC 3 2 1 ~ V0 Spyder Model 7 COM 24 VAC Earth Ground 1 1 WHEN CONNECTING POWER TO THE SPYDER MODEL 7 CONTROLLERS, CONNECT THE COM...
Page 16 - INPUT / OUTPUT WIRING; Wiring Requirements; Single wire; Fig. 15 Attaching Two or More Wires at Terminal Block
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 16 INPUT / OUTPUT WIRING Wiring Requirements NOTE: When attaching two or more wires to the same terminal, other than 14 AWG (2.0 mm 2 ), be sure to twist them together. Deviation from this rule can result in improper electrical cont...
Page 17 - Internal Wiring Examples; IP Model Internal Wiring
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 17 31-00475-01 Internal Wiring Examples IP Model Internal Wiring Fig. 16 IP Model Internal Wiring MSTP Model Internal Wiring Fig. 17 MSTP Model Internal Wiring
Page 18 - Terminal Connections
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 18 Terminal Connections All the terminals for this controller are removable. Table 15 Terminal Connections Terminal Label Description Power 24 VAC 1 Earth ground (connected to building earth ground) 2 V0 Power supply voltage (connec...
Page 19 - UIO Wiring Examples; Fig. 18 Universal IO Wiring Examples
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 19 31-00475-01 UIO Wiring Examples Fig. 18 Universal IO Wiring Examples NOTE: A protective diode is recommended, such as 1N4001, to protect the controller from the relay’s voltage EMF. The rating of the diode must be 11 V and 22 mA maximum. 19 ...
Page 20 - 0 VDC Auxiliary Wiring Examples; Fig. 20 20 VDC Auxiliary Wiring
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 20 SSR (DO) Wiring Examples Fig. 19 SSR (DO) Wiring Examples NOTE: • SR IN (terminal 5, SSR power input) is connected to AC OUT (terminal 4, 24 VAC~ output) by a jumper wire provided by the factory. • Remove the jumper if you want t...
Page 21 - NETWORK CONCEPTS; IP Network Topologies
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 21 31-00475-01 NETWORK CONCEPTS The RS-485 Standard According to the RS-485 standard (TIA/EIA 485: “Electrical Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint Systems”), only one driver communicating via an RS...
Page 22 - BACNET IP CONTROLLER; Enabled
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 22 BACNET IP CONTROLLER DHCP IP Configuration A new controller from the factory has DHCP enabled by default. • For the first 15 seconds after powering the controller, a search for a DHCP server will be performed to acquire an IP add...
Page 23 - Remote Antenna Placement
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 23 31-00475-01 5. Tighten the wire terminal nut by turning the nut clockwise. Do not over-tighten. Fig. 25 Installing a Remote Antenna Remote Antenna Placement Place and align the antenna in a way that the BLE signal does not interfere with any...
Page 24 - BACNET MSTP WIRING; Termination Resistors
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 24 BACNET MSTP WIRING The MSTP variants of the Spyder Model 7 VAV controller use the BACnet MSTP communication protocol. The controller’s data is presented to other controllers over a twisted-pair MSTP network, using the TIA/EIA 485...
Page 25 - BACNET MSTP CONTROLLER; Automatic MAC Addressing
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 25 31-00475-01 NOTE: The 120 Ω termination resistor must be inserted directly into the terminals of both end devices. NOTE: The controller is insensitive to bias voltages due to the failsafe chipset inside, and it can share the BACnet bus with ...
Page 26 - Fig. 31 Calculating the MAC Address; Configure the Device Instance
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 26 For example, if only DIP switches 1, 3, 5, and 7 are ON, the MAC address would be 85 (1 + 4 + 16 + 64 = 85). Fig. 31 Calculating the MAC Address Configure the Device Instance Number The Device Instance number must be unique acros...
Page 27 - MODBUS RTU; Modbus Considerations; Cables and Shielding; X X
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 27 31-00475-01 MODBUS RTU The controller features a removable 2-wire with shield, non-isolated, RS-485 interface suitable for Modbus communication (terminal 16, 17, and 18). The terminal block containing it is gray. The controller can function ...
Page 28 - SYLKTM BUS; Supported Sylk bus devices; Fig. 34 SylkTM Wiring Topologies
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 28 SYLK™ BUS Sylk™ Bus compatible wall modules such as TR120 can be connected to the controller's Sylk™ (terminals 14 and 15). • Sylk™ is a two wire, polarity insensitive bus.• The maximum current provided at the Sylk™ bus interface...
Page 29 - BLUETOOTH BALANCING; Overview; Table 23 Mobile Application for Balancing
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 29 31-00475-01 BLUETOOTH BALANCING The antenna facilitates wireless communication via Bluetooth with other devices. Overview The Honeywell Connect Mobile (HCM) is a mobile application used for VAV balancing. The HCM app provides easy access to ...
Page 30 - TROUBLESHOOTING; BACnet and Modbus LED Status
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 30 TROUBLESHOOTING The controller features the following LEDs. Fig. 35 LED Interface BACnet and Modbus LED Status Table 24 BACnet and Modbus LED Status Mode Status Tx and Rx LED Status Visual BACnet Tx1 Fail OFF BACnet Tx1 Success B...
Page 31 - Bluetooth LED Status
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31 31-00475-01 Bluetooth LED Status Controller LED Status Table 25 Bluetooth LED Status Mode LED Status Visual BLE disabled by user OFF BLE normal operation and connected Green, permanently ON. BLE enabled but not connected Green, 2 blinks in 1...
Page 32 - REGULATORY INFORMATION; FCC Regulation; Fig. 36 CE Statement; Professional Installation Warning
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 32 REGULATORY INFORMATION FCC Regulation This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept a...
Page 33 - Standards and Compliance; Article 33 Communication; Table 27 BLE Certification Numbers
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 33 31-00475-01 Standards and Compliance • CE • UL916 Energy Management Equipment • UL60730 • FCC Part 15; Class A verified • EN 55022; Class A • EN 61000-3-2 • 61000 • UL2043 Approvals and Certifications • UL 60730-1, Standard for Automatic Ele...
Page 34 - APPENDIX; Sensor Input Accuracy; Table 29 Sensor Accuracies
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 34 APPENDIX Sensor Input Accuracy The controller's internal sensor inputs support both 10 K NTC Ω and 20 K NTC Ω sensors. The following table lists the typical minimum accuracies of the hardware and software for these temperature se...
Page 35 - Recognition of Sensor Failure of Sensor Inputs; Configuration
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 35 31-00475-01 Recognition of Sensor Failure of Sensor Inputs The thresholds at which the sensor fails, that is, sensor breaks (SB) and short-circuits (SC), are recognized, depending upon the given sensor type. In the event of a recognized sens...
Page 36 - Sensor Characteristics; 0 K NTC TYPE II Characteristics
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 36 Sensor Characteristics The characteristics (resistance in relation to temperature) of the sensors and the resultant voltage are listed on the following pages. The stated values do not include failures due to sensor failures, wiri...
Page 38 - 0 K NTC TYPE III Characteristics; Table 32 10 K NTC TYPE III Characteristics
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 38 10 K NTC TYPE III Characteristics Table 32 10 K NTC TYPE III Characteristics Temp. [°F] Temp. [°C] Resistance [ Ω ] Temp. [°F] Temp. [°C] Resistance [ Ω ] -35 -37.2 203.6K 105 40.6 5479 -30 -34.4 173.6K 110 43.3 4947 -25 -31.7 14...
Page 39 - Resistance
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 39 31-00475-01 10 K3A1 Characteristics Table 33 10 K3A1 Characteristics Temp. [°F] Temp. [°C] Resistance [ Ω ] Temp. [°F] Temp. [°C] Resistance [ Ω ] -40 -40 336098 26.6 -3 38110 -38.2 -39 314553 28.4 -2 36184 -36.4 -38 294524 30.2 -1 34366 -34...
Page 40 - Table 33 10 K3A1 Characteristics (Continued)
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 40 93.2 34 6807 159.8 71 1693 95 35 6530 161.6 72 1637 96.8 36 6266 163.4 73 1582 98.6 37 6014 165.2 74 1530 100.4 38 5774 167 75 1480 102.2 39 5544 168.8 76 1432 104 40 5325 170.6 77 1385 105.8 41 5116 172.4 78 1341 107.6 42 4916 1...
Page 42 - 0 K NTC Characteristics; Table 34 20 K NTC Characteristics
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 42 20 K NTC Characteristics Table 34 20 K NTC Characteristics Temp. [°F] Temp. [°C] Resistance [K Ω ] Terminal voltage [V] Temp. [°F] Temp. [°C] Resistance [K Ω ] Terminal Voltage [V] -58 -50 1659 8.78 5 -15 164 7.83 -56.2 -49 1541 ...
Page 43 - Table 34 20 K NTC Characteristics (Continued)
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 43 31-00475-01 68 20 25.3 4.75 134.6 57 5.08 1.66 69.8 21 24.2 4.64 136.4 58 4.88 1.61 71.6 22 23 4.53 138.2 59 4.69 1.56 73.4 23 22 4.43 140 60 4.52 1.51 75.2 24 21 4.32 140 60 4.52 1.51 77 25 20 4.22 141.8 61 4.35 1.46 78.8 26 19.1 4.12 143.6...
Page 45 - Coefficients
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 45 31-00475-01 Nickel Class B DIN 43760 Sensors The characteristic of the nickel temperature sensor is specified as per DIN 43760. The large Temperature Coefficient of Resistance (TCR) of the Ni-RTD, 6178 ppm/K, offers greater sensitivity than ...
Page 46 - Sensor Type
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 31-00475-01 46 NI1000 TK5000 DIN B R-T Characteristics of Ni1000 TK5000 DIN B. Table 36 NI1000 TK5000 Sensor Specification Sensor Type Nominal Resistance Sensitivity Ni1000 TK5000 DIN B R 0 : 1000 Ω TC: 5000 ppm/K Table 37 R-T Characteristics (...
Page 47 - Characteristics
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS 47 31-00475-01 PT100 Characteristics Table 38 PT100 Characteristics Temp. [°F] Temp.[°C] Resistance [ Ω ] -30 -34.44 86 -20 -28.89 89 -10 -23.33 91 0 -17.78 93 10 -12.22 95 20 -6.67 97 30 -1.11 100 32 0.00 100 40 4.44 102 50 10.00 104 60 15.56 ...
Page 55 - ABBREVIATIONS
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS Honeywell Building Technologies 715 Peachtree St NE Atlanta, Georgia 30308 customer.honeywell.com buildings.honeywell.com ® U.S. Registered Trademark ©2022 Honeywell International Inc. 31-00475-01 I Rev. 06-22 The material in this document is f...