65-0214-08

V4943/V8943B,C,N;

V4944/V8944B,C,L,N

Regulating Diaphragm Gas Valves

APPLICATION

The V4943/V8943B and N (single stage) and V4944/V8944B

and N (two stage) are solenoid-operated diaphragm valves

suitable for natural gas only. The V4943/V8943C and

V4944/V8944C and L are solenoid-operated diaphragm

valves suitable for Liquefied Petroleum (LP) gas only. These

valves are used on boilers, unit heaters, duct furnaces,

makeup air and rooftop heaters.

FEATURES

• Models are available for natural or liquid petroleum

(LP) gases.

• Valve models L, N are rapid opening (less than six

seconds) and fast closing, and are available for LP and

natural gases, respectively.

• Line voltage with two-wire thermostat or controller is

used with V4943; V8943 is used with 24V thermostat or

controller.

• V4944 is used with line voltage dual-stage thermostat

or controller; V8944 is used with 24V dual-stage

thermostat or controller.

• Slow opening B,C valve models are available for

natural and LP gases respectively.

• Valve closes on power failure; recommended for final

shutoff service.

• Valve closing time: 2 seconds maximum at 7 inches wc

inlet pressure.

• Valves rated for 0.5 pound per square inch (psi) (3.4

kPa).

• Leadwires and cover for electrical conduit connections

are provided.

Contents

Application ........................................................................

1

Features ...........................................................................

1

Specifications ...................................................................

2

Ordering Information ........................................................

2

Installation ........................................................................

6

Operation ..........................................................................

9

Checkout and Troubleshooting ......................................... 10

Service Information .......................................................... 12

firealarmresources.com

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Honeywell 1114

Summary

Page 3 - CAUTION; firealarmresources.com

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES 3 65-0214—08 Pressure Reference Port Vent: 5/16–24 UNF internal tapping. Standard Factory Settings: See Table 3. Dimensions: See Fig. 1. Weight: 1 in., 1-1/4 in. valves: 4 lb (1.8 kg). 1-1/2 in., 2 in. valves: 5 lb (2.3 kg). a V494...

Page 4 - Gas Valve Sizing

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES 65-0214—08 4 Fig. 1. V4943/44 and V8943/44 dimensions in in. (mm). Gas Valve Sizing 1. Check the burner nameplate for: a. the type of gas used, and b. the gas flow capacity. The capacity will be listed in British thermal units per ...

Page 6 - To size two identical valves piped in series:; INSTALLATION; WARNING

V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES 65-0214—08 6 Fig. 7. Capacity vs. pressure drop of LP Gas curves for 1-1/4 in. valve. Fig. 8. Capacity vs. pressure drop of LP Gas curves for 1-1/2 in. valve. Fig. 9. Capacity vs. pressure drop of LP Gas curves for 2 in. valve. To ...