PRODUCT DATA
60-2309-13
V4055A,B,D,E
On-Off Fluid Power Gas
Valve Actuator
APPLICATION
The V4055 Gas Valve Actuator, in combination with a
VE5000
a
, V5055 or V5097 Gas Valve, controls the gas supply
to commercial and industrial burners.
When replacing a V4034 with a V4055, the V5034 gas valve
must also be replaced with a V5055 or V5097 gas valve.
FEATURES
• The V4055 Actuator, when used with the VE5000
a
,
V5097 or V5055 Valve, is rated for final safety shutoff
service.
• The V4055 Actuator can be used with the characterized
guide model of the V5055 or V5097 Gas Valve to
enhance lightoff smoothness.
• The standard model has an opening time of 26
seconds at 60 Hz or 32 seconds at 50 Hz. A fast-
opening model is available with timings of 13 seconds
at 60 Hz or 16 seconds at 50 Hz.
• Maximum closing time is one second, which meets
code, standard and insurer requirements.
• Models available with damper shaft, with or without
spring return; shaft extends out both sides and rides in
Teflon-like Delrin bushings; used with standard
7616BR Damper Crank Arm.
• Red OPEN indicator attached to actuator stem shows
when valve is even slightly open; yellow SHUT
indicator on valve stem shows only when gas valve is
fully closed.
• Models available with adjustable max flow limit switch.
• Ambient temperature rating is -40°F to +150°F (-40°C to
+66°C) for 60 Hz models and -10°F to +158°F (-23°C to
+70°C) for 50 Hz and 50/60 Hz models.
• Valve and actuator combinations can be mounted in
any position, with the exception of the 220 to 240 Vac,
50/60 Hz models, which are mounted vertically.
• Models available with factory-installed single pole
double throw (spdt) field-adjustable Auxiliary Switch.
Field-addable Auxiliary Switch kits are also available.
• Standard enclosure meets NEMA 1 (IP30)
requirements; models available with NEMA 4 (IP54)
weatherproof enclosure.
• V4055D and high pressure V4055E with Proof-of-
Closure Switch and V5055/V5097C or E with valve seal
overtravel interlock (double seal) to meet specific
code, standard and insurer requirements.
a
VE5000 is a European manufactured and approved valve for
European use only.
Contents
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Wiring ...............................................................................
Checkout and Service ......................................................
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Honeywell V4055
Summary
V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR 60-2309—1 3 4 Accessories: 133568 Auxiliary Switch Bag Assembly (not for models with maximum flow limit switch). 133569 Valve-Closed Indication Switch Bag Assembly. NOTE: Check local codes for acceptance of adding the switch and using the valve seal...
V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR 5 60-2309—1 3 IMPORTANT 1. All wiring must comply with all applicable electrical codes, ordinances, and regulations. All wiring must be NEC Class 1. 2. Voltage and frequency of the power supply connected to this control must agree with those marked ...
V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR 60-2309—1 3 6 Fig. 3. 7616BR Damper Crank Arm can be attached to actuator shaft to drive a damper when valve is open. WIRING WARNING Electrical Shock Hazard. Can cause serious injury or death. Disconnect power supply before making wiring connections...