PRODUCT DATA

Honeywell

y

Subject to change

EN0H-2119GE25 R1106

V2652

Optimal-plus

MANUAL RADIATOR VALVE

1/2

1/2

Angle

Straight

Design

The manual radiatior valves consists of:

• Valve housing PN10, DN10, 15 or 20 with

• internal thread connection to DIN2999 (ISO7) for threaded,

copper or precision steel pipe on inlet (compression ring
fittings see ‘Accessories’)

• external thread connection to DIN/ISO228 with union-nut

and radiator tailpiece on outlet

• Valve insert

• Handwheel

Materials

• Valve housing made of nickel-plated red bronze

• Valve insert made of brass with EPDM O-rings

• Handwheel made of white plastic

• Threaded tailpiece and connection nut made of nickel-plated

brass

Application

Optimal-plus manual valves are installed on the supply of radi-
ators and heat exchangers in warm water heating systems.
Control of the room temperature is done by manually opening
or closing the valve.

Features

Convertible to thermostatic control, also when installed
and in operation

Robust valve housing made of corrosion resistant red
bronze with good flow and sound properties

Maintenance-free spindle sealing

Valve housing with dimensions according to EN215,
Appendix A, Series D

Non-rising handwheel

Connection to all types of pipe DN10...DN20

Specifications

Medium

Heating water, water quality to
VDI2035

pH-value

8...9.5

Operating temperature max. 90°C (194°F)

Operating pressure

PN 10

k

vs

(cv)-values

Angle DN10

2.1 (2.46)

Angle DN15

2.3 (2.69)

Angle DN20

2.7 (3.16)

Straight DN10

1.7 (1.99)

Straight DN15

1.8 (2.11)

Straight DN20

2.2 (2.57)

Leakage rate

0.01 % of k

v

-value

Thermostat connection M30 x 1.5

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Function

V2652 - OPTIMAL-PLUS EN0H-2119GE25 R1106 2 Honeywell y Subject to change Function The orifice between valve seat and valve cartridge increases when the valve is opened by turning the handwheel anti-clock-wise. More heating water can flow into the radiator or heat exchanger and the room temperature r...

Page 3 - Accessories; for all sizes

V2652 - OPTIMAL-PLUS Honeywell y Subject to change 3 EN0H-2119GE25 R1106 Accessories Compression ring and nut 3/8" x 10 mm VA620A1010 3/8" x 12 mm VA620A1012 1/2" x 10 mm VA620A1510 1/2" x 12 mm VA620A1512 1/2" x 14 mm VA620A1514 1/2" x 15 mm VA620A1515 1/2" x 16 mm VA620...

Page 4 - Hardhofweg

V2652 - OPTIMAL-PLUS Automation and Control SolutionsHoneywell GmbH Hardhofweg 74821 Mosbach, Germany Phone: +49 (6261) 810 Fax: +49 (6261) 81393 www.honeywell.com Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du ...

Other Honeywell Models