Page 2 - Notice
D9112 Operation & Installation Manual Page 2 74-06144-000-C 2/96 © 1993-1996 Radionics Notice The material and instructions covered in this manual have been carefully checked foraccuracy and are presumed to be reliable. However, Radionics, Inc. assumes noresponsibility for inaccuracies and reser...
Page 4 - Table of Contents
D9112 Operation & Installation Manual Page 4 74-06144-000-C 2/96 © 1993-1996 Radionics Table of Contents Power Outputs .................................................. 23 Circuit Protection .......................................... 23Available Power ..............................................
Page 5 - Installation Guide for UL and Fire Applications 61
D9112 Operation & Installation Manual Page 5 © 1993 Radionics 74-06144-000-C 2/96 D8128A OctoPOPIT Module ......................... 42 Listing ....................................................... 42Installing the OctoPOPIT .......................... 42Wiring OctoPOPITs to the D9112 .............
Page 6 - Figures and Tables; Figure 10: D128 Dual Phone Line Switcher
D9112 Operation & Installation Manual Page 6 74-06144-000-C 2/96 © 1993-1996 Radionics Figures and Tables Figure 1: D9112 System Configuration .................................................... 7 Figure 2: Enclosure Mounting ................................................................ 13 F...
Page 7 - Introduction; Figure 1: D9112 System Configuration; Points
D9112 Operation & Installation Manual Page 7 © 1993 Radionics 74-06144-000-C 2/96 Introduction D9112 D8128 COctoPOPIT combines8 POPIT Points in one module. D8125 Interface forD8127POPITSPoints 9-71 Use D1255 Command Centers and/orkeyswitches to arm the D9112 by area. Eachpanel can have up to 8 a...
Page 8 - Areas and Accounts; SDI FAILURE; Keyswitch
D9112 Operation & Installation Manual Page 8 74-06144-000-C 2/96 © 1993-1996 Radionics Areas and Accounts The D9112 supports up to eight separate areas. You can assign all points to a singlearea or spread them out over up to eight areas. You arm and disarm the D9112 panel by area. You can arm an...
Page 9 - Event Memory; NCI
D9112 Operation & Installation Manual Page 9 © 1993 Radionics 74-06144-000-C 2/96 Event Memory The D9112 uses event memory to store events for each area. You can view the eventsfor an area at a D1255 Command Center assigned to the area. The D9112 panel clearsthe events for an area from event mem...
Page 10 - Other Features
D9112 Operation & Installation Manual Page 10 74-06144-000-C 2/96 © 1993-1996 Radionics Other Features The D9112 has many programmable features. A short list of some of the features follows.Complete details on all the D9112’s features can be found in the D9112 Program EntryGuide (74-06145-000). ...
Page 11 - D9112 Control/Communicator Assembly; Literature Pack; Faceplate shield; Ordered Separately; (order two cords if you are using the D128 Dual Phone Switcher)
D9112 Operation & Installation Manual Page 11 © 1993 Radionics 74-06144-000-C 2/96 D9112 Control/Communicator Assembly The Radionics D9112 Control/Communicator is shipped pre-assembled from the factory.You should receive the following parts with your D9112 panel. Literature Pack • D9112 Installa...
Page 12 - Listings and Approvals; Fire; CSFM; Approved by the California State Fire Marshal.; Burglary
D9112 Operation & Installation Manual Page 12 74-06144-000-C 2/96 © 1993-1996 Radionics Listings and Approvals Fire ULUnderwriters Laboratories lists the D9112 Control/Communicator as a Signal System ControlUnit for: Central Station, Local, Auxiliary, Remote Station, and Household Fire Warning. ...
Page 13 - Installation; Before You Begin; Mounting the Enclosure; Figure 2: Enclosure Mounting
D9112 Operation & Installation Manual Page 13 © 1993 Radionics 74-06144-000-C 2/96 Installation Before You Begin This Installation section contains a general installation procedure. It refers you to other sections of the manual for detailed instructions. Radionics recommends you review this manu...
Page 14 - Premises Wiring; Connecting Earth Ground
D9112 Operation & Installation Manual Page 14 74-06144-000-C 2/96 © 1993-1996 Radionics Premises Wiring Run the necessary wiring throughout the premises and pull the wires into the enclosure. EMI (Electro Magnetic Interference) may cause problems: EMI may occur if youinstall the D9112 system or ...
Page 15 - Locking the Reset Pin; Answer Disarmed; Lock the Reset Pin Now
D9112 Operation & Installation Manual Page 15 © 1993 Radionics 74-06144-000-C 2/96 Locking the Reset Pin Locking the Reset Pin disables the panel. See Figure 3. The D9112 ignores the commandcenters and points while disabled. CALL FOR SERVICE appears in command centerdisplays while the pin is loc...
Page 16 - Finishing the Installation; Charge the Battery as You Finish
D9112 Operation & Installation Manual Page 16 74-06144-000-C 2/96 © 1993-1996 Radionics Finishing the Installation Earth ground and reset pin first: Make the earth ground connection to terminal 10 andlock the reset pin in the closed position if you haven’t already done so. Charge the Battery as ...
Page 17 - Make the Telephone Connections; Leave the reset pin locked down for now.; Programming the Panel
D9112 Operation & Installation Manual Page 17 © 1993 Radionics 74-06144-000-C 2/96 Make the Telephone Connections See Telephone Connections. If you are connecting the D9112 to a ground start phonesystem, you need to install D136 relay, see Install Modules and Relays on the previouspage. Connect ...
Page 18 - Testing the System
D9112 Operation & Installation Manual Page 18 74-06144-000-C 2/96 © 1993-1996 Radionics Testing the System After finishing the installation and programming of the panel, make a complete functionaltest of the D9112 system. Test the panel and all devices for proper operation. Test afteryou first p...
Page 19 - Power Supply; Primary Power; Installing the Transformer
D9112 Operation & Installation Manual Page 19 © 1993 Radionics 74-06144-000-C 2/96 Power Supply Primary Power Terminals 1 2 Primary (AC) Power Circuit A 16.5 VAC, 40 VA internally fused transformer (Radionics model D1640) is the primarypower source for the D9112. The AC power circuit provides 1....
Page 20 - Secondary Power; Installing the Battery; BATTERY LOW
D9112 Operation & Installation Manual Page 20 74-06144-000-C 2/96 © 1993-1996 Radionics Secondary Power Terminals 4 5 Secondary (DC) Power A 12V, 7 Ah sealed lead-acid rechargeable battery (Radionics D126) supplies secondarypower for auxiliary and alarm outputs, and powers the system during inte...
Page 21 - BATTERY RESTORAL; Battery Charging Circuit
D9112 Operation & Installation Manual Page 21 © 1993 Radionics 74-06144-000-C 2/96 Battery Supervision (Continued) When battery voltage returns to 13.7 VDC the Low Battery LED goes out. If the panel isprogrammed for power supervision, it transmits a BATTERY RESTORAL report in the Modem II transm...
Page 22 - Charging Status and Low Battery LEDs; Figure 4: Charging and Battery LEDs
D9112 Operation & Installation Manual Page 22 74-06144-000-C 2/96 © 1993-1996 Radionics Charging Status and Low Battery LEDs Charging Status LED (Yellow) The yellow LED shows the charging statusof the battery. Figure 4 shows its location. • Yellow LED off The yellow LED is off when the battery i...
Page 23 - Power Outputs; Circuit Protection; Available Power; Programmable
D9112 Operation & Installation Manual Page 23 © 1993 Radionics 74-06144-000-C 2/96 Power Outputs Circuit Protection Three self-resetting thermal circuit breakers protect the panel from short circuits on boththe continuous and programmable power outputs. The circuit breakers are thermal ratedand ...
Page 24 - Continuous Current Draw; Programmable Power Outputs.
D9112 Operation & Installation Manual Page 24 74-06144-000-C 2/96 © 1993-1996 Radionics Available Power (Continued) Accessory Connector (J2)The D128 Dual Phone Line Switcher connects to J2. Expansion Port (J4)The Expansion Port is reserved for future use. Continuous Power Outputs Terminals 3 24 ...
Page 25 - Programmable Power Outputs; Programming; Figure 5: Relays for Terminals 7 and 8
D9112 Operation & Installation Manual Page 25 © 1993 Radionics 74-06144-000-C 2/96 Programmable Power Outputs Terminals 6 7 8 Programming The power outputs at terminals 6, 7, and 8 are programmed as relays A, B, and C. Allrelays are programmed in the Relays module of the program. Relays are assi...
Page 26 - Terminals 6 and 7
D9112 Operation & Installation Manual Page 26 74-06144-000-C 2/96 © 1993-1996 Radionics Terminals 6 and 7 Terminals 6 (relay A) and 7 (relay B), provide positive (+) 10.2 VDC to 13.9 VDC poweroutput when activated. Use the power at terminals 6 and 7 to power bells, siren drivers,piezo fire sound...
Page 27 - Telephone Connections; Registration; The particular line you are going to connect the panel to; Location; Figure 6: RJ31X Wiring; PREMISES
D9112 Operation & Installation Manual Page 27 © 1993 Radionics 74-06144-000-C 2/96 Telephone Connections Registration The Radionics D9112 Control/Communicator panel is registered with the FederalCommunication Commission under part 68, for connection to the public telephone systemusing an RJ31X j...
Page 28 - Phone Cord Connection; You can program the D9112 to use DTMF or pulse dialing. See; Phone Line Monitor; Phone Supervision
D9112 Operation & Installation Manual Page 28 74-06144-000-C 2/96 © 1993-1996 Radionics Phone Cord Connection Connect one end of a D161 (8') or D162 (2') Telephone Cord to the D9112 TELCO Cordconnector, J3, located on the bottom left corner of the D9112. See Figure 7. Connect theother end to the...
Page 29 - Phone Line Test Points; Phone Parameters; Ground Start; Relay Installation; Figure 7: Telephone Connections
D9112 Operation & Installation Manual Page 29 © 1993 Radionics 74-06144-000-C 2/96 Phone Line Test Points You can attach a telephone test set tothe D9112 at the TELTEST pointslocated above the TELCO jack on thelower left corner of the panel. SeeFigure 7. Communication Failure After 10 attempts t...
Page 30 - Ground Start Jumper; Figure 9: Ground Start Jumper; D128 Dual Phone Line Switcher; Description; Phone Line Monitor in this manual for a description of the
D9112 Operation & Installation Manual Page 30 74-06144-000-C 2/96 © 1993-1996 Radionics LINE SNIFFER SELECT 8 9 10 RED GROUNDSTART EARTH GROUND COMMON Ground Start Loop Start TELCO CORDMODEL No. D161 RequiresOptional RelayModel No. D136 M LOOP START POSITION GROUND START POSITION Ground Start Ju...
Page 31 - Primary Phone Lines, Primary Phone Numbers; Phone; Watchdog Feature; Connect the green lead from the D128 to terminal 1 on the D9112.
D9112 Operation & Installation Manual Page 31 © 1993 Radionics 74-06144-000-C 2/96 Primary Phone Lines, Primary Phone Numbers Don’t confuse primary phone lines with primary phone numbers: With the D128Dual Phone Line Switcher installed, the D9112 uses two phone lines, primary andsecondary, to di...
Page 32 - Phone Line Monitor in this section for a description of
D9112 Operation & Installation Manual Page 32 74-06144-000-C 2/96 © 1993-1996 Radionics D128 Status LEDs Four LEDs mounted on the front edge of the D128 module show the status of AC powerfor the D9112, the status of the two phone lines, and communication failure. See Figure10. AC Power LEDThe gr...
Page 33 - Figure 11: On-board Point Sensor Loop Wiring
D9112 Operation & Installation Manual Page 33 © 1993 Radionics 74-06144-000-C 2/96 On-Board Points Description Terminals 11 to 22 The D9112 panel provides eight on-board points. Each point functions independently anddoes not interfere with the operation of the others. The panel monitors the sens...
Page 34 - Point Parameters; Open Loop; Point Response Time; Debounce Count program item in the Point Assignment
D9112 Operation & Installation Manual Page 34 74-06144-000-C 2/96 © 1993-1996 Radionics Point Parameters You can determine the condition of on-board points 1 to 8 by measuring the voltageacross the point input terminal and one of the common terminals. The sensor loops mustbe connected and the 1k...
Page 35 - Terminals; Placing a short on the data expansion loop generates a
D9112 Operation & Installation Manual Page 35 © 1993 Radionics 74-06144-000-C 2/96 Off-Board Points Point (ZONEX) Buss Terminals 23 to 28 You can use POPIT (Point of Protection Input Transponder) modules to provide up to126 off-board points, bringing the total number of points the D9112 can moni...
Page 36 - Listings; Installation Guide for UL and Fire Applications in this manual to; Installing the D8125 POPEX Module; For use with D9112. Save this set. You will use it later to
D9112 Operation & Installation Manual Page 36 74-06144-000-C 2/96 © 1993-1996 Radionics Listings The D8125 POPEX and D8127 POPIT modules are UL listed for Local or PoliceConnected Burglar Alarm, Central Station Burglar Alarm, Household Burglar Alarm,Central Station Fire (NFPA 71), Local Fire (NF...
Page 37 - See
D9112 Operation & Installation Manual Page 37 © 1993 Radionics 74-06144-000-C 2/96 Wiring the D8125 to the D9112 (Continued) Do not connect more than one D8125 to ZONEX 1, terminals 27 and 28, or ZONEX 2,terminals 25 and 26. See Wiring POPITs to the D8125 for instructions on connecting POPITs to...
Page 38 - Wiring POPITs to the Data Expansion Loop; POPIT Module Point Assignments.; Table 1: Data Expansion Loop Wire Specifications; Maximum Length of All; AWG
D9112 Operation & Installation Manual Page 38 74-06144-000-C 2/96 © 1993-1996 Radionics Wiring POPITs to the Data Expansion Loop You can connect up to 63 POPITs to each D8125 module. Use one 2-wire dataexpansion loop or distribute the POPITs on up to three loops. Setting DIP switches on thePOPIT...
Page 39 - Wiring Data Expansion Loops to POPEX Modules; Premises Wiring in the Installation section.; Figure 13: Typical Expansion Loop/POPIT Configuration
D9112 Operation & Installation Manual Page 39 © 1993 Radionics 74-06144-000-C 2/96 Wiring Data Expansion Loops to POPEX Modules There are two positive (+) and two negative (-) data expansion loop terminals on eachPOPEX module. Follow the procedure below to connect the data expansion loops to the...
Page 40 - Point Assignments; Point Assignment section of the D9112 Program Sheet. See Figure 14.
D9112 Operation & Installation Manual Page 40 74-06144-000-C 2/96 © 1993-1996 Radionics Point Assignments Six switches on each POPIT assign the module to a point number. POPIT switch settingsare found in the Point Assignment section of the D9112 Program Sheet. See Figure 14. D9112 Program Record...
Page 41 - Vertical Grid for POPEX #1 for points 9 to 71 . Use the sheet marked; Vertical Grid for POPEX #1; Figure 15: POPIT Labels
D9112 Operation & Installation Manual Page 41 © 1993 Radionics 74-06144-000-C 2/96 POPIT LabelsOff-board points are numbered 9 to 71 and 73 to 135. The D9112 reserves points 72 and136 for internal use. You must connect POPITs for points 73 to 135 to expansion loopsconnected to POPEX #2. Four she...
Page 42 - Review the; Listing; EMI
D9112 Operation & Installation Manual Page 42 74-06144-000-C 2/96 © 1993-1996 Radionics D8128A OctoPOPIT Module Description The D8128A OctoPOPIT Module combines the functions of the D8125 POPEX moduleand the D8127 POPIT modules to provide eight off-board points in a single module. Youcan use Oct...
Page 43 - Wiring OctoPOPITs to the D9112; Connect terminal 1 on the OctoPOPIT to terminal 23 on the D9112.
D9112 Operation & Installation Manual Page 43 © 1993 Radionics 74-06144-000-C 2/96 Wiring OctoPOPITs to the D9112 Follow the procedure below to wire D8128A OctoPOPIT Modules to the D9112. You canconnect OctoPOPIT and POPEX modules to the same Point Buss terminals. Themodules wire in parallel. Re...
Page 44 - Line Termination; See Figure 16 for the location of the switches on the OctoPOPIT.
D9112 Operation & Installation Manual Page 44 74-06144-000-C 2/96 © 1993-1996 Radionics Line Termination If there is no D8125 POPEX module connected to ZONEX 1, terminals 27 and 28, setswitch 12 on only one OctoPOPIT connected to those terminals to the on position. If there is a D8125 POPEX modu...
Page 45 - OctoPOPIT Sensor Loops; Point Assignment
D9112 Operation & Installation Manual Page 45 © 1993-1996 Radionics 74-06144-000-C 2/96 OctoPOPIT Sensor Loops The number normally-open and/or normally-closed detection devices each sensor loopcan supervise is limited only by the resistance on the loop. Resistance on each sensorloop must be less...
Page 46 - Switch Settings; to ZONEX 1
D9112 Operation & Installation Manual Page 46 74-06144-000-C 2/96 © 1993-1996 Radionics Table 2: D8128A OctoPOPIT Switch Settings NCI #215 D8128A Switches 9 10 11 D8128A Sensor Loop D9112 Point # Connect D8128A to ZONEX 1 D9112 Point # Connect D8128A to ZONEX 2 On On On P1P2P3 P4P5P6P7P8 9 1011 ...
Page 47 - Testing Off-board Points; Test to be sure that all off-board points operate properly.
D9112 Operation & Installation Manual Page 47 © 1993-1996 Radionics 74-06144-000-C 2/96 Testing Off-board Points Use the Service Walk Test item from the command center Service Menu to test off-boardpoints. See the Service Walk Test in the Troubleshooting section of this manual for instructions. ...
Page 48 - Power Outputs section of this manual to be sure you; Configuring the D8129 OctoRelay
D9112 Operation & Installation Manual Page 48 74-06144-000-C 2/96 © 1993-1996 Radionics Off-board Relays D8129 OctoRelay The D8129 OctoRelay allows you to add relay outputs to your system in groups of eight.Up to 128 OctoRelay outputs (relay numbers 1 to 128) can be added to your systemusing 16 ...
Page 49 - Relay Number
D9112 Operation & Installation Manual Page 49 © 1993-1996 Radionics 74-06144-000-C 2/96 Table 3: D8129 Switch Settings D9112 Relay Number D8129 OctoRelay Switch Setting On D9112, connect D8129 to 1 to 8 Off-On-On-On-On ZONEX 1 Terminal 28 9 to 16 On- Off-On-On-On ZONEX 1 Terminal 28 17 to 24 Off...
Page 50 - Configuring; Wiring Connections
D9112 Operation & Installation Manual Page 50 74-06144-000-C 2/96 © 1993-1996 Radionics Installation Do not use the instructions packaged with the D8129: They do not includeinstructions for connecting the module to the D9112 panel. Follow the instructions below. Set the switches on the OctoRelay...
Page 51 - D811 Arm Status Relay Module; D811 modules connect as shown in Figure 18. Review the; Relay Output
D9112 Operation & Installation Manual Page 51 © 1993-1996 Radionics 74-06144-000-C 2/96 D811 Arm Status Relay Module The 811 Arm Status Relay Module allows you to add a single off-board relay output toyour system. When used with the D9112 you can assign alarm output, auxiliary relay,sensor reset...
Page 53 - Arming Devices; Assigning the D1255 an Address
D9112 Operation & Installation Manual Page 53 © 1993-1996 Radionics 74-06144-000-C 2/96 Arming Devices Description Command centers, maintained or momentary contact keyswitches, or a combination ofthe two are used to arm and disarm areas. The D9112 panel may contain up to 8 areas.See the Introduc...
Page 54 - for all command centers
D9112 Operation & Installation Manual Page 54 74-06144-000-C 2/96 © 1993-1996 Radionics Installation Consult the D1255 Installation Instructions (74-06819-000) for installation and mounting instructions. Command centers connect to the D9112 panel in parallel as shown inTable 5. Table 5: D1255 Co...
Page 55 - You can program any; Figure 19: Power at Command Centers
D9112 Operation & Installation Manual Page 55 © 1993-1996 Radionics 74-06144-000-C 2/96 D268/D269 Independent Zone ControlD279 Independent Zone Control You can program any on-board or OctoPOPIT point so that the D268/D269 or D279 Independent Zone Control operates as independent point control (ar...
Page 56 - Relays section of the D9112 Program; See the; FA Bypass Max program; Figure 20: Keyswitch Wiring
D9112 Operation & Installation Manual Page 56 74-06144-000-C 2/96 © 1993-1996 Radionics Keyswitch Description You can connect a maintained or momentary contact arming station (keyswitch) tomaster arm/disarm any of the areas in the D9112. The keyswitch is connected to an on-board or off-board poi...
Page 57 - Programmer and Accessory Connections; using the D5200 programmer.; Advance the D5200 display to a D9112 product handler. See
D9112 Operation & Installation Manual Page 57 © 1993-1996 Radionics 74-06144-000-C 2/96 Programmer and Accessory Connections Programmer Connector (J7) The procedure below shows you how to connect and disconnect the programmer. Referto D5200 Programmer Operation Manual (74-06176-000) for complete...
Page 58 - Programmer Access Reports; PROG ACCESS OK; Figure 22: Programmer and Accessory
D9112 Operation & Installation Manual Page 58 74-06144-000-C 2/96 © 1993-1996 Radionics 5. Disconnect the programmer. 6. Changes to some program parameters require a reset before they become effective. Reset Recommended: Radionics recommends that you reset the panel afterchanging program paramet...
Page 59 - aceplate
D9112 Operation & Installation Manual Page 59 © 1993-1996 Radionics 74-06144-000-C 2/96 3 5 6 7 8 9 10 1 4 2 Low Battery LEDs Off When Normal EARTH GROUND COMMON CLASS 2 TRANSFORMER16.5 VAC 40 VA 60 HZPart No. D1640Internally Fused - Do Not ShortRequires Unswitched OutletDo Not Share With Other ...
Page 60 - Quick Reference Terminal Description; Terminal
D9112 Operation & Installation Manual Page 60 74-06144-000-C 2/96 © 1993-1996 Radionics Quick Reference Terminal Description Terminal Name Description 1, 2 CLA SS 2 TRANSFORMER Connect 16.5 VAC, 40 VA transformer for primary power s upply. 3 +AUX POWER Supplies up to 1.4A at 10.0 VDC to powered ...
Page 61 - Installation Guide for UL and Fire Applications
D9112 Operation & Installation Manual Page 61 © 1993-1996 Radionics 74-06144-000-C 2/96 Installation Guide for UL and Fire Applications Listings and Approvals Fire ULUnderwriters Laboratories lists the D9112 Control/Communicator as a Signal System ControlUnit for: Central Station, Local, Auxilia...
Page 62 - The; Optional Compatible Equipment; Burglary Applications
D9112 Operation & Installation Manual Page 62 74-06144-000-C 2/96 © 1993-1996 Radionics Introduction The D9112 System Chart references components evaluated and listed by Underwriters’ Laboratories for compatibility with the D9112 Control/Communicator. These componentsmeet the basic system requir...
Page 63 - Enclosures; Radionics offers three optional enclosures for the D9112.
D9112 Operation & Installation Manual Page 63 © 1993-1996 Radionics 74-06144-000-C 2/96 Fire Applications (Continued) Enclosures Radionics offers three optional enclosures for the D9112. • The D8103 enclosure is suitable for residential fire and/or burglary installations and commercial burglary ...
Page 64 - System Chart
D9112 Operation & Installation Manual Page 64 74-06144-000-C 2/96 © 1993-1996 Radionics System Chart 2+ = Two or more required for this application. Consult the appropriate standard. 1 • = At least one detector required. You can substitute other 2-wire detectors listed for use with the D125. You...
Page 65 - System Wiring Diagram, Issue A
D9112 Operation & Installation Manual Page 65 © 1993-1996 Radionics 74-06144-000-C 2/96 System Wiring Diagram, Issue A Digital Alarm Communicator T ransmitter P P P P P S D122 DUAL BA TTER Y HARNESS Low Battery LEDs Off When Normal LINE SNIFFER SELECT Loop Start Ground Start TELCO CORD MODEL No....
Page 66 - Current Rating Chart for Standby Battery Calculations; Ratings of other devices in the system which are not shown above:; Total A
D9112 Operation & Installation Manual Page 66 74-06144-000-C 2/96 © 1993-1996 Radionics Current Rating Chart for Standby Battery Calculations AC Power On AC Power Off In Alarm Normal Current Minimum Current Maximum Current Model Number Each Each Each Number Used Unit Total Unit Total Unit Total ...
Page 67 - Standby Battery Requirements; Household Burglary and Commercial Burglary
D9112 Operation & Installation Manual Page 67 © 1993-1996 Radionics 74-06144-000-C 2/96 Standby Battery Requirements Household Burglary and Commercial Burglary Four hours of standby battery capacity required. Central Station or Local Fire Alarm 24 hours of standby plus 5 minutes of alarm operati...
Page 68 - Standby Battery Calculation for; Current Chart First
D9112 Operation & Installation Manual Page 68 74-06144-000-C 2/96 © 1993-1996 Radionics Standby Battery Calculation for NFPA 72 Fire Alarm Applications Current Chart First See the D9112 Standby Battery and Current Rating Chart for totals B and C used in the formulas below. When connecting two ba...
Page 69 - Remote Station or Auxiliary Systems; Household Fire Ampere-Hour Calculation Formula
D9112 Operation & Installation Manual Page 69 © 1993-1996 Radionics 74-06144-000-C 2/96 Remote Station or Auxiliary Systems Remote Station or Auxiliary Systems require 60 hours of standby plus 5 minutes of alarmoperation at the end of the 60 hour period. A D8132 Battery Charger Module with addit...
Page 70 - Troubleshooting Guide; CALL FOR SERVICE; Trouble at Command Center; PANEL BROKEN; Hardware, Software Failed; Return Tag or call Customer Service for a return authorization.; PARAM FAIL; Program Parameters Failed; Operation Monitor LED in the Telephone Connections section for
D9112 Operation & Installation Manual Page 70 74-06144-000-C 2/96 © 1993-1996 Radionics Troubleshooting Guide Introduction Radionics provides this guide to help you troubleshoot problems with the D9112. Toprevent problems from occurring, read the preceding sections of this manual and theprogram ...
Page 71 - AC FAILED
D9112 Operation & Installation Manual Page 71 © 1993-1996 Radionics 74-06144-000-C 2/96 SERVC AC FAIL - AC Power Failed An interruption of AC Power at terminals 1 and 2 causes SERVC AC FAIL to appear incommand center displays. You can program the panel to send an AC FAILED report to the receiver...
Page 72 - Phone Line Trouble; Symptom; in
D9112 Operation & Installation Manual Page 72 74-06144-000-C 2/96 © 1993-1996 Radionics Phone Line Trouble Phone line problems that are not corrected can result in the D9112 going intoCommunications Failure. You can program the D9112 to monitor one or two phone lines.See the D9112 Program Entry ...
Page 73 - Communications Failure; Phone Line Trouble procedure to verify that there is no problem; Relays section of this manual for
D9112 Operation & Installation Manual Page 73 © 1993-1996 Radionics 74-06144-000-C 2/96 Communications Failure The D9112 goes into Communications Failure after ten unsuccessful attempts to reachthe receiver. Follow the Phone Line Trouble procedure to verify that there is no problem with the phon...
Page 74 - experience problems, check for the symptoms below.
D9112 Operation & Installation Manual Page 74 74-06144-000-C 2/96 © 1993-1996 Radionics Communications Failure (Continued) Symptom Diagnosis Remedy The receiver answersthe call and providesan initial “handshake”acknowledgment, butdoes notacknowledge theD9112's reporttransmission with a“kiss-off”...
Page 75 - Problems with Points
D9112 Operation & Installation Manual Page 75 © 1993-1996 Radionics 74-06144-000-C 2/96 Problems with Points If you incorrectly set the switches on a POPIT you may create both a missing and extrapoint. When you find a missing point, perform a Service Walk Test to search for extrapoints. See the ...
Page 76 - Check wiring for shorts.
D9112 Operation & Installation Manual Page 76 74-06144-000-C 2/96 © 1993-1996 Radionics Problems with Points (Continued) NCI #215 Symptom Diagnosis Remedy One or more pointsremain in trouble oralarm with all devices connectedto the sensor loopsnormal. The sensor loop isopen, shorted, orgrounded....
Page 78 - Problems with the D8125 POPEX Data Expansion Loops; If you suspect EMI may be a problem, see; Metering the Loops; Disconnect the loop from the POPEX module.
D9112 Operation & Installation Manual Page 78 74-06144-000-C 2/96 © 1993-1996 Radionics Problems with the D8125 POPEX Data Expansion Loops EMI (Electro-magnetic Interference), excessive resistance, or intermittent grounds,shorts, or opens on the data expansion loop can cause erratic or intermitt...
Page 79 - Checking Shielded Cable
D9112 Operation & Installation Manual Page 79 © 1993-1996 Radionics 74-06144-000-C 2/96 Checking Shielded Cable If improperly installed, shielded cable can create problems rather than solve them. Followthe procedure below to check shielded cable for proper installation. 1. Remove the drain wire ...
Page 80 - Problems with Command Centers
D9112 Operation & Installation Manual Page 80 74-06144-000-C 2/96 © 1993-1996 Radionics Problems with Command Centers Symptom Diagnosis Remedy Command centersshow erratic behavior. For example, the pipthat confirms youpressed a key"echoes" or the backlighting flashes off andon. A supervi...
Page 81 - Battery and Power Reports; problem check the following.; Watchdog Reset Reports
D9112 Operation & Installation Manual Page 81 © 1993-1996 Radionics 74-06144-000-C 2/96 Battery and Power Reports You can program the D9112 to transmit both battery and AC power status reports. Seethe D9112 Program Entry Guide (74-06145-000). If battery or AC power reports are a problem check th...
Page 82 - Overloaded Power Supply
D9112 Operation & Installation Manual Page 82 74-06144-000-C 2/96 © 1993-1996 Radionics Overloaded Power Supply If the load on the D9112's power supply exceeds it's capacity, the panel follows a routineto protect itself and the battery. It sends reports to the receiver at several points duringth...
Page 83 - Service Walk Test; SERVICE WALK? appears in the
D9112 Operation & Installation Manual Page 83 © 1993-1996 Radionics 74-06144-000-C 2/96 Service Walk Test The Service Walk Test differs from the standard Walk Test in that POPITs whoseswitches are set for a point number not programmed in the panel appear in the test. Service Walk Test only avail...
Page 84 - Figure 23: Service Walk Test Flow Chart; Test a device
D9112 Operation & Installation Manual Page 84 74-06144-000-C 2/96 © 1993-1996 Radionics Figure 23: Service Walk Test Flow Chart (Text displays 60 seconds) ENT SERVICE WALK ? IDLE TEXT 134 PTS TO TEST Test a device POINT TEXT 133 PTS TO TEST Test a device ESC POINT TEXT 132 PTS TO TEST Test a dev...
Page 85 - Command 5 7 Toggles Default Idle Text; Command 5 9 Shows Firmware Revision; Ensure the command center is at idle text.
D9112 Operation & Installation Manual Page 85 © 1993-1996 Radionics 74-06144-000-C 2/96 Command 5 7 Toggles Default Idle Text Command 5 7 allows technicians who might not be familiar with the custom idle text toconfirm whether an area is armed or ready to arm. The default idle text displays are:...
Page 86 - Battery Discharge/Recharge Schedule; Specifications; Voltage Input
D9112 Operation & Installation Manual Page 86 74-06144-000-C 2/96 © 1993-1996 Radionics Fire and Fire/Burglary Systems To comply with UL 985 and 864 listingstandards for fire alarm systems (effectiveMarch 1, 1989), the total combinedcontinuous and alarm current draw for thesystem during alarm co...
Page 87 - Connection
D9112 Operation & Installation Manual Page 87 © 1993-1996 Radionics 74-06144-000-C 2/96 SDI Bus SDI Bus A (+): 9 VDC (15,000' max) SDI Bus B (-): 9 VDC (15,000' max) Telephone Connections Connection RJ31X or RJ38X jack can be interfaced withthe D9112. Two TelCo Lines Radionics D128 Dual Phone Li...