Page 3 - Table of contents; Introduction
Table of contents 1 Introduction 4 1.1 About documentation 4 1.2 Determine Bosch Security Systems, Inc. Product Manufacturing Dates 4 2 Installation 5 2.1 Installation Preparation 5 2.2 Enclosure Options 5 2.3 Mounting Enclosure 5 2.4 Installing the Control Panel 6 2.5 Connecting Earth Ground 7 2.5....
Page 4 - About documentation
Introduction About documentation CopyrightThis document is the intellectual property of Bosch Security Systems, Inc. and is protected bycopyright. All rights reserved. TrademarksAll hardware and software product names used in this document are likely to be registeredtrademarks and must be treated ac...
Page 5 - Installation; Installation Preparation
Installation Installation Preparation This section contains a general installation procedure and refers to other sections of thedocument for detailed instructions. Review this document and the D9412GV4/D7412GV4Program Entry Guide (P/N: F01U265459) before beginning the installation to determine theha...
Page 6 - Callout - Description; Installing the Control Panel
i Notice!Electromagnetic interference (EMI) can cause problems on long wire runs. Figure 2.1: Enclosure Mounting Callout - Description 1 - Point chart label 2 - Mounting skirt hooks (2) 3 - Module mounting holes (12) 4 - Tamper switch mounting holes (5) 5 - Skirt mounting hole (1) 6 - Enclosure moun...
Page 7 - Connecting Earth Ground; Ground Fault Detect Enable
Connecting Earth Ground Terminal 10 To help prevent damage from electrostatic charges or other transient electrical surges,connect the system to earth ground at Terminal 10 before making other connections.Recommended earth ground references are a grounding rod or a cold water pipe. ! Warning!Do not ...
Page 8 - Ground Fault Impedance Specifications; Impedance; Locking the Reset Pin
Figure 2.2: Ground Fault Detect (S4) Callout - Description 1 - S4 Locked (Closed). Control panels detects ground faults. 2 - S4 Unlocked (Open). Control panel does not detect ground faults. Ground Fault Impedance Specifications The table below provides the impedance specifications for detecting grou...
Page 10 - Diagrams; Faceplates
Diagrams Faceplates Figure 3.1: Faceplates Callout - Description Callout - Description 1 - Charging status LED (yellow) 8 - Ring 2 - Low battery LED (red) 9 - Operation monitor LED (green) 3 - Color-coded battery leads 10 - Accessory connector 4 - Ground fault detect enable 11 - Reset pin 5 - Phone ...
Page 11 - Power Supply Side Wiring Diagrams
Power Supply Side Wiring Diagrams D9412GV4/D7412GV4 Power Supply Side System Wiring Diagram (Power and Phone) Figure 3.2: Side System Wiring Diagram Callout - Description Callout - Description 1 - If required by local AHJ, connect D113Battery Lead Supervision Module. 8 - To Output A or Output B 2 - ...
Page 12 - System Wiring Diagram
i Notice!For UL Certified accounts, additional power can be obtained using only a UL Listed auxiliary12.0 VDC regulated, power-limited power supply. i Notice!All terminals accept for Outputs A, B, and C (Terminals 6, 7 and 8) are supervised. D9412GV4/D7412GV4 Input Points and Peripheral Devices Syst...
Page 14 - SDI Devices Wiring Diagrams; D9412GV4 SDI and Zonex Devices System Wiring Diagram; Callout
SDI Devices Wiring Diagrams D9412GV4 SDI and Zonex Devices System Wiring Diagram Figure 3.4: D9412GV4 System Wiring Diagram, SDI and Zonex Devices Callout ᅳ Description Callout ᅳ Description 1 ᅳ Up to 16 supervised D1265, D1255 (all versions), D1255RB, D1256RB Keypads, or D1257RB Fire Annunciators,o...
Page 15 - D7412GV4 SDI and Zonex Devices System Wiring Diagram
i Notice!Terminals 24 through 36 are power limited, supervised. Fire and Intrusion devices must be onseparate circuits. Refer to ICP-SDI-9114 Installation Instructions (P/N: F01U030068) D7412GV4 SDI and Zonex Devices System Wiring Diagram Figure 3.5: D7412GV4 SDI and Zonex Devices System Wiring Diag...
Page 17 - Module
Module D9412GV4 D7412GV4 4 BB810/B820 SDI2 Inovonics Interface Modules 1 1 B920 Two-line AlphanumericKeypad 5 16 16 B930 ATM Style AlphanumericKeypad (SDI2) 5 16 16 B520 Auxiliary Power SupplyModule 8 8 1 For the D7412GV4, only 5 inputs are available on the Octo-input at address 7. 2 For the D7412GV...
Page 18 - SDI2 Bus Wiring Recommendations
SDI2 Bus Wiring Recommendations Use the following SDI2 bus wiring recommendations for SDI2 installation. The SDI2 bus isused by the GV4 Control Panel and corresponding modules to communicate with one another.Modules can be connected via home run, daisy chain, or single level T-tapped anywhere on the...
Page 19 - Keyswitch Wiring
Cablecapacitance Overallcablelength Cable capacitance Overallcablelength Cable capacitance Overallcablelength Cable capacitance Overallcablelength pF/ft ft pF/ft ft pF/ft ft pFf/ft ft < 17 7500 22 6363 27 5185 32 4400 18 7500 23 6086 28 5000 33 4242 19 7350 24 5800 29 4828 34 4100 20 7000 25 5600...
Page 20 - Power Supply and Power Outputs; Power Supply - Primary; Modem4 Events; Installing the Transformer
Power Supply and Power Outputs Power Supply - Primary Primary (AC) Power Circuit The primary source is a 16.5 VAC, 40 VA, internally-fused transformer (Bosch SecuritySystems, Inc. Model D1640). The control panel draws 225 mA when idle and 300 mA when inan alarm state. The total available auxiliary c...
Page 21 - Power Terminals - Secondary; Installing the Battery
D8004 Transformer Enclosure Required for Fire SystemsUse the D8004 Transformer Enclosure for the D1640 Transformer in fire and combined fireand burglary applications. i Notice!Check with the Authority Having Jurisdiction (AHJ) about mounting transformers on specificcircuits. Power Terminals - Second...
Page 23 - Power Outputs - Circuit Protection
Figure 4.2: Non-PowerLimited Wiring Callout ᅳ Description 1 ᅳ Conduit required for use with external batteries. 2 ᅳ Battery wires 3 ᅳ 0.25 in (6.4 mm) minimum. To ensure proper spacing, use tie-wraps or similar devices to secure wires. 4 ᅳ Relay output wires 5 ᅳ Input or Zone wires 6 ᅳ Standby batte...
Page 24 - Power Outputs - Total Available Power; Programming
– Terminal 8: Output C (Switched Auxiliary Power) PTC CB5 protects Terminal 24: Zonex Power.PTC CB1 protects Terminal 32: SDI Power +.PTC CB3 protects Terminal 36: SDI2 Power +. Required by UL:– All devices powered from a power output are to be supervised. – Power outputs are not shared between fire...
Page 26 - Terminal 8
Terminal 8 Terminal 8 provides continuous positive (+) 12.0 VDC Nominal power. Output C interrupts thepower at Terminal 8 when activated. Use Terminal 8 to power smoke detectors or otherdevices that are reset by interrupting power. One self-resetting circuit breaker protectsTerminals 6, 7, and 8 aga...
Page 27 - Specifications; Power Outputs; SDI Bus
Specifications Voltage Input(Power Supply) 1 Primary: Terminals 1 and 2 16.5 VAC 40 VA class 2 plug-in transformer (D1640) Secondary: Terminals 4 and 5 Sealed lead-acid rechargeable battery (12.0 VDC, 7 Ah or 12.0 VDC, 17.2 or 18Ah). The control panel supports up to two12.0 VDC, 7 Ah batteries using...
Page 29 - SDI2 Bus
B520 Specifications Voltage Input (PowerSupply) Primary: 18 VAC terminal 18.0 VAC, 50 VA class 2 plug-in transformer -TR1850(18.0 VAC, 50 VA class 2 plug-intransformer – TR1850-CA for Canada) Secondary: Batt 1, Batt 2 terminals The B520 Auxiliary Power SupplyModule supports the connection oftwo inde...
Page 30 - Environmental; Terminal Wiring Requirements; Requirements
Recharge Cycle AC ON – Load shed relay resets, battery charging begins, Battery Trouble and AC Restoral Reportssent. 12.6 VDC – Battery Restoral Report sent, LowBattery LED off. Environmental Temperature: +32 ゚ F to +120 ゚ F (0 ゚ C to +49 ゚ C) RelativeHumidity: Maximum 93% non-condensing CompatibleE...
Page 32 - Compatibilities; Model
TerminalNo TerminalDescription Requirements 36 SDI2 POWER Terminal accommodates 14 to 22 AWG, use appropriate wire size based on peripheraldevice current. *D9412GV4 only. Terminals 25 and 26 are NOT USED on the D7412GV4 Control Panel. Compatibilities i Notice!Where the fire alarm transmitter is shar...
Page 34 - Circuit Classes
Model Title UL 864 UL985 Intrusion cUL Intrusion 3 RFRP-A RADION repeater X X 3 RFPR-12-A RADION PIR X 3 RFPR-C12_A RADION PIR C X 3 RFUN RADION universal transmitter X 1 Where the fire alarm transmitter is sharing on-premise communications equipment, the shared equipment must be UL Listed (ITE or f...