Page 2 - Trademarks; CoBox; Documentation Conventions; Type Styles Used in this Manual; Bold text; Prompt; Important Notes
D9412G/D7412G | Program Entry Guide | EN | 2 Bosch Security Systems | 1/04 | 47775E Trademarks CoBox is a registered trademark of Lantronix ® . Windows ® is either a registered trademark of Microsoft Corporation in the United States and/or othercountries. Documentation Conventions Type Styles Used...
Page 3 - Table of Contents
D9412G/D7412G | Program Entry Guide | Table of Contents EN | 3 Bosch Security Systems | 1/04 | 47775E Table of Contents 1.0 Introduction ....................................................... 5 1.1 How to use this Program Entry Guide ............. 5 1.2 Literature Referenced...........................
Page 4 - Figures; Figure 4
D9412G/D7412G | Program Entry Guide | Table of Contents EN | 4 Bosch Security Systems | 1/04 | 47775E 6.7 Miscellaneous .................................................. 127 6.8 Cross Point Parameters .................................. 128 7.0 RADXAXS ..................................................
Page 5 - Introduction; How to use this Program Entry Guide; Table 2; Literature Referenced; Table 1
D9412G/D7412G | Program Entry Guide | 1.0 Introduction EN | 5 Bosch Security Systems | 1/04 | 47775E 1.0 Introduction 1.1 How to use this Program Entry Guide This guide addresses the programming of theD9412G/D7412G Control Panels only, and should notbe used in conjunction with other control panels. ...
Page 6 - EN; New Features; The items shown; Feature
D9412G/D7412G | Program Entry Guide | 1.0 Introduction EN | 6 Bosch Security Systems | 1/04 | 47775E 1.4 New Features The items shown Table 3 are new features added to the D9412G/D7412G Control Panels since version 6.10. Table 3: New Features Feature Description Ground Fault Detect(Version 6.10) For...
Page 8 - Product Handlers; Programming Options; The Program Item Prompt
D9412G/D7412G | Program Entry Guide | 1.0 Introduction EN | 8 Bosch Security Systems | 1/04 | 47775E 1.5 Product Handlers Programming the 9000 Series requires multiple product handlers. The availability of each handler is indicated in Table 4 . See the control panel specific Release Notes to determi...
Page 9 - FILENAME; prompt or set as factory default at the; NEWRECORD; TROUBLE; Display; INCOMPATIBLE PANEL
D9412G/D7412G | Program Entry Guide | 1.0 Introduction EN | 9 Bosch Security Systems | 1/04 | 47775E 1.7 Programming the Control Panelwith the D5200 Programmer Latch the jumper in the upper right hand corner ofthe control panel labeled as RESET on the PCB andReset Pin on the faceplate.Connect the mo...
Page 11 - Phone; Blank; Blank; Phone 1; Blank; Phone 1; Blank; Phone 1
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 11 Bosch Security Systems | 1/04 | 47775E 2.0 9000MAIN Use this programming module to define theoperating characteristics that affect panel-widefunctions. There are nine programming categories inthis module: Phone, Phone Parameters, Routing,Enh...
Page 12 - Phone Parameters; Modem Format; Modem Format; Table 6
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 12 Bosch Security Systems | 1/04 | 47775E 2.2 Phone Parameters The program items in this category describe panel-wide characteristics for telephone dialing, receiverformat, and supervision. Modem Format Default: Yes Selection: Yes or No Yes Rad...
Page 13 - User ID Number; DTMF Dialing; Yes
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 13 Bosch Security Systems | 1/04 | 47775E Table 6: Modem IIIa 2 Communication Format Data - User ID Numbers Point/User Flag NO Point/User Flag YES 000 000 001 to 005 001 to 005 006 to 013 601 to 608 014 to 021 701 to 708 022 to 029 801 to 808 0...
Page 14 - Phone Supv Time; Yes or No; Yes or No; Two Phone Lines; Yes or No
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 14 Bosch Security Systems | 1/04 | 47775E Phone Supv Time Default: Blank Selection: Blank or 10 to 240 Blank No phone line supervision. 10 to 240 Enter the number of seconds (in 10second increments) you wish tosupervise the phone line. After a ...
Page 15 - BFSK Duress Code; Ground Start; Long; Routing; Called Party Disconnect
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 15 Bosch Security Systems | 1/04 | 47775E BFSK Duress Code Default: 0 Selection: 0 to 9 If Duress Enable in Area Parameters is Yes and Modem Format in Phone Parameters is No, you must program a number to identify Duress Reportsat the central st...
Page 16 - Primary Device; Enhanced Routing; Dialing Attempts; Device
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 16 Bosch Security Systems | 1/04 | 47775E 2.3.3 Programming a Primary and BackupDestination Each route number has an R# Primary Device and an R# Backup Device . In typical applications where two phone numbers are programmed, the R# Primary Devi...
Page 18 - Fire Reports; * This event is not reported when using BFSK format.; Burglar Reports; Selecting; Report; This event is not reported when using BFSK format.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 18 Bosch Security Systems | 1/04 | 47775E Fire Reports Selecting Yes enables a report to be sent when the event occurs. Table 9: Diagnostic Reports Report Selections Description R# Fire Alarm Yes , No Reports Fire Event. R# Fire Restore(Alarm) ...
Page 19 - User Reports
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 19 Bosch Security Systems | 1/04 | 47775E Restoral Reports are not sent if thecontrol panel is reset after a point isbypassed and then the point isunbypassed. This is true for both Fire andNon-fire points. The 9000 Series Control Panels log aGr...
Page 20 - Expand Test Rpt; Diag Reports; Test Reports; prompt in
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 20 Bosch Security Systems | 1/04 | 47775E Test Reports 010101010101 To send a single Test Report (R# TestReport), enable Sked Function Code #9(Test Report) in the Skeds section of theprogram. To expand this Test Report to include anyoff-normal ...
Page 21 - Relay Reports
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 21 Bosch Security Systems | 1/04 | 47775E Table 13: Diagnostic Reports Report Selections Description R# SDI Dev Fail * Yes , No Reports SDI devicefailure. R# SDI Dev Restl Yes , No Reports restoral of SDIdevice failure. R# WatchdogRset Yes , No...
Page 22 - RAM Reports; Point Reports; * Point text is always transmitted when using
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 22 Bosch Security Systems | 1/04 | 47775E RAM Reports Selecting Yes enables sending a report when the RAM Passcode Event occurs. RAM Access Fail can indicate a wrong RAM passcode whencommunicating with the control panel, or avalid RAM session w...
Page 23 - User Chng Reports; always uses the account number from Area 1.; Access Reports
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 23 Bosch Security Systems | 1/04 | 47775E User Chng Reports Selecting Yes enables a report to be sent when theevent occurs. Table 18: User Change Reports Report Selections Description R# DateChanged Yes , No Reports DateChange Event. R# TimeCha...
Page 25 - Programming the Pager Phone Number
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 25 Bosch Security Systems | 1/04 | 47775E RG# Primary Pager Default: No Selection: Yes or No Determines if this route group sends events to anumeric pager. To send events to a numeric pager, aphone number must also be programmed in theroute gro...
Page 27 - Power Supervision; AC Fail Time
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 27 Bosch Security Systems | 1/04 | 47775E Table 20: continued Event Description EventPriority EventNumber Parameters Changed 008 054 RAM Access OK 008 064 RAM Access Fail 008 065 Remote Reset 008 079 Program Access OK n/a n/a Program Access Fai...
Page 28 - AC Tag Along
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 28 Bosch Security Systems | 1/04 | 47775E • 9 (such as 9, 19, 29, 39, and so on): The AC Fail Time interval is in minutes and an AC FailEvent is transmitted after the loss of AC for thisamount of time.An additional AC Fail Event is transmitted ...
Page 29 - Printer Parameters; Printer Address
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 29 Bosch Security Systems | 1/04 | 47775E AC/Battery Buzz Default: No Selection: Yes or No Yes Initiates panel-wide trouble tone at allcommand centers. No Does not initiate panel-wide troubletone at command centers Initiate a panel-wide trouble...
Page 31 - RAM Parameters; Section 6.4 SDI RAM Parameters
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 31 Bosch Security Systems | 1/04 | 47775E P## Auto Functions Event Default: See Program Record Sheet Selection: Yes or No P## RAM Event Default: See Program Record Sheet Selection: Yes or No P## Relay Event Default: See Program Record Sheet Sel...
Page 32 - RAM Passcode; RAM Call Back; RAM Ph; prompt in this; RAM Line Monitor; Answer Armed; . The control panel must be in the proper
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 32 Bosch Security Systems | 1/04 | 47775E RAM Passcode Default: 999999 Selection: 0 to 9, A to F(six characters required) Enter six characters. Do not use a space in thepasscode. The control panel verifies the Remote AccountManager at the centr...
Page 33 - Program Record Sheet; See; Program Record Sheet; Ram Ph
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 33 Bosch Security Systems | 1/04 | 47775E 010101010101 Program this item No if it causes falseseizures of the phone line or if you are notusing RAM (this indicates a device usingthe same frequency tone is also using thephone line to which the c...
Page 34 - Miscellaneous; Duress Type; Area Parameters; Area; Enter the area number you are programming.
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 34 Bosch Security Systems | 1/04 | 47775E 2.8 Miscellaneous Duress Type Default: 1 Selection: 1 or 2 1 Add 1 to the last digit to generate an alarm. Forexample, if the passcode is 6123, 6124 triggers aduress alarm. If the last digit of the pass...
Page 36 - Retrnable; in
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 36 Bosch Security Systems | 1/04 | 47775E Figure 2: Account Number Entry 2 2 3 3 4 4 5 5 1 1 2 3 4 5 6 7 1 1 - RPS account number entry 2 - Corresponding D5200 account number digits 3 - Digits 1 and 2 4 - Digits 3 and 4 5 - Digits 5 and 6 6 - D...
Page 37 - Point Index; Verify Time is set for 20 seconds. The
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 37 Bosch Security Systems | 1/04 | 47775E A# Auto Watch Default: No Selection: Yes or No Yes When the area is disarmed, WatchMode turns on automatically. No When the area is disarmed, WatchMode must be turned on or offmanually. 010101010101 Con...
Page 38 - Section 2.8 Miscellaneous
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 38 Bosch Security Systems | 1/04 | 47775E A# Duress Enable Default: No Selection: Yes or No Yes Enable Duress alarm for this area. No Disable Duress alarm for this area. This entry determines if this area allows duressalarms to be generated. Se...
Page 39 - CC# Scope affects master arming
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 39 Bosch Security Systems | 1/04 | 47775E A# Area Type Default: Regular Selection: Regular, Master, Associate, or Shared Regular Arms or disarms as an independent area. Master Does not allow arming for this area unless all associate areas with ...
Page 40 - Area Relays
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 40 Bosch Security Systems | 1/04 | 47775E 2.9.3 Shared-Area Characteristics Arming a Shared Area Requires all associate areas to be armed. As soon asthe last associate area is armed, the shared areabegins its arming sequence automatically. Pass...
Page 46 - Command Center; Cmd Center; DIP Switch Setting
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 46 Bosch Security Systems | 1/04 | 47775E A# Perimeter O/C Default: No Selection: Yes or No Yes This area can send Perimeter Opening andClosing Reports. No This area cannot send Perimeter Opening andClosing Reports. This item determines if this...
Page 47 - Account
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 47 Bosch Security Systems | 1/04 | 47775E CC# Supervised Default: See Program Record Sheet Selection: Yes or No Yes Only one command center can be installed forthis CC SDI address. No More than one command center can beinstalled using this CC S...
Page 48 - CC Assign Door; ACCESS GRANTED
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 48 Bosch Security Systems | 1/04 | 47775E CC# A1[through A8] in Scope Default: See preceding important note Selection: Yes or No Yes Include this area in the scope of thiscommand center. No Do not include this area in the scope ofthis command c...
Page 51 - Sixteen alphanumeric characters; On; Assignment; Custom Function; for
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 51 Bosch Security Systems | 1/04 | 47775E Area # Acct Is On Default: See Program Record Sheet Selection: Sixteen alphanumeric characters Enter the text that displays when all areas sharingthe same account number are master armed. The ACCT IS ON...
Page 52 - Selection; Command; This
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 52 Bosch Security Systems | 1/04 | 47775E CF### Key Strokes Default: See Program Record Sheet Selection: Up to 32 characters: 0 to 9, A, B, C,D, and E Selection Key Faceplate Label 0 to 9 0 to 9 A [COMMAND] B [PREV] (previous) ↑ C [ESC] (escape...
Page 53 - User Interface; Commands; NO AUTHORITY
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 53 Bosch Security Systems | 1/04 | 47775E • Custom Functions can perform several tasks atonce. For example: - To toggle relays 7, 8, and 9 in one CustomFunction enter:[A] [5] [4] [7] [E] [E] [8] [E] [E] [9] [E] [E] [C] - To add a temporary pass...
Page 54 - Response; not; Watch Mode; Perim Partial
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 54 Bosch Security Systems | 1/04 | 47775E Master Arm Delay Default: P Selection: Blank, E, or P P Passcode: Required for all users with Master Arm Delay enabled for theirauthority level. E Enable: A user does not need a passcode to use [COMMAND...
Page 55 - is enabled in
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 55 Bosch Security Systems | 1/04 | 47775E View Area Stat Default: P Selection: Blank, E, or P #8 View Area Status (MENU FUNCTION only) Use this function to view the armed status of allareas within the scope of the command centerassigned to this...
Page 57 - Bypass Returnable; Section 4.1 Point Index
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 57 Bosch Security Systems | 1/04 | 47775E Print Log Default: P Selection: Blank, E, or P #22 Print Event Log (MENU FUNCTION only) Use this function to print all the events stored in thecontrol panel starting at the start date and endingwith the...
Page 58 - Move to Area; Change Skeds; Custom Functions
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 58 Bosch Security Systems | 1/04 | 47775E Move to Area Default: P Selection: Blank, E, or P #30 Move to Area [COMMAND][5][0] Use this function to temporarily switch thecommand center’s assignment to a different area.This can be used to perform ...
Page 59 - Authority Level; Area Type
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 59 Bosch Security Systems | 1/04 | 47775E 2.11.3 Authority Level Selections Use Section 2.11.3 Authority Level Selections to determine which Authority Level can accesscommand center functions that are PasscodeProtected. You do not need to selec...
Page 61 - for Fire points; Access Control Functions; in the
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 61 Bosch Security Systems | 1/04 | 47775E To Walk Test a Door point connected to aD9210B Access Interface Module, thedoor must be opened without activatingthe door sequence or allowing it to timeout past the extended shunt time. L## Fire Test D...
Page 62 - Definitions
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 62 Bosch Security Systems | 1/04 | 47775E L## Unlock Door Default: See Program Record Sheet Selection: Blank or E Unlock Door (MENU FUNCTION only) Press the command center number keys [1] through[8] that correspond to the door number tounlock/r...
Page 66 - Blank or E
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 66 Bosch Security Systems | 1/04 | 47775E L## Passcode Disarm Default: See Program Record Sheet Selection: Blank or E Disarm an area by entering a passcode and pressing[ENTER]. Access Control Levels L## Security Level Default: See Program Recor...
Page 67 - Function List; WATCH MODE; Menu Item; A failure to program Menu Item 1 causes; Relay Parameters; RlyResp Type
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 67 Bosch Security Systems | 1/04 | 47775E 2.12 Function List The Function List is accessed when the user presses[MENU] (or the key corresponding to menu) on theD1260) while the command center is displaying theidle text. Up to 32 functions M### ...
Page 71 - AC Failure; Battery Trouble; Phone Fail
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 71 Bosch Security Systems | 1/04 | 47775E 010101010101 Programming Tip #4: Fire Trouble Resound was added to firmware versions 6.20 and later. Thisfeature, when enabled, resounds the FireTrouble condition at 12:00 PM or 12:00AM if the Fire Trou...
Page 73 - Passcode/Token Worksheet; User; COMMAND DISABLED; Auth; NOT AUTHORIZED; Figure 3
D9412G/D7412G | Program Entry Guide | 3.0 RADXUSR1/RADXUSR2 EN | 73 Bosch Security Systems | 1/04 | 47775E 3.0 RADXUSR1/RADXUSR2 3.1 Passcode/Token Worksheet These programming items assign user groups 001 to249 a passcode, area assignment by authority level,and a User Group Window. 010101010101 Two ...
Page 75 - User Group; Code; Manua
D9412G/D7412G | Program Entry Guide | 3.0 RADXUSR1/RADXUSR2 EN | 75 Bosch Security Systems | 1/04 | 47775E A silence bell authority is built into allauthority levels, even if they are the defaultand none of the available programmablefunctions are enabled. A user passcodecan silence a Fire/Burg bell ...
Page 77 - RADXPNTS; Record Sheet; Description
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 77 Bosch Security Systems | 1/04 | 47775E 4.0 RADXPNTS 4.1 Point Index Use this programming module to constructpersonality types for points used in the system. TheIndex numbers are used in Point Assignments. Eachunique point index number determ...
Page 79 - These special point types do not respond
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 79 Bosch Security Systems | 1/04 | 47775E P ##Type Description Keyswitch Maintained: Program Point Response as 1. Do not connect initiating devices to a Keyswitch point. Normal: The area is disarmed. Short: When this point changes from normal t...
Page 80 - Local Armed; When this point changes from open to normal, the area arms.; Point Response; as 1. If the system is
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 80 Bosch Security Systems | 1/04 | 47775E P ##TypeSelection Description D279 (O/C Non-Priority): The D279 provides point arming and disarming independent of the area arm state. A non-priority D279 point arm state does not affect the area arm st...
Page 82 - Example of Controlled point:
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 82 Bosch Security Systems | 1/04 | 47775E P## Pt Response Default: See Program Record Sheet Selection: 0 to F Controlled (Non-24-Hour Points) Point Response 0 1 2 3 4 5 6 7 8 9 A B C D E F Armed Open I I I I D D I I D I I I I I T Armed Short I ...
Page 83 - DISARM NOW
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 83 Bosch Security Systems | 1/04 | 47775E P## Entry Delay Default: See Program Record Sheet Selection: 5 seconds to 600 seconds Use this option to enter the amount of entry delaytime that a user has after faulting a Controlled point( P## Type 1...
Page 86 - Do
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 86 Bosch Security Systems | 1/04 | 47775E P## RlyResp Type Default: See Program Record Sheet Selection: Blank, 1 to 2 Blank Point state does not affect the operationof the corresponding relay. 1 Relay Follow Point: The relay corresponding with ...
Page 87 - * Restoral Reports are still transmitted if the alarm,
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 87 Bosch Security Systems | 1/04 | 47775E * Restoral Reports are still transmitted if the alarm,trouble, or bypass (by Sked, RAM, or Swinger bypass)condition occurred when the area disarmed, and thepoint restored. Allows a controlled point (P##...
Page 88 - Close; BYPASS
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 88 Bosch Security Systems | 1/04 | 47775E P## Bypassable Default: No Selection: Yes or No Yes This point can be bypassed and forcearmed. No This point cannot be bypassed or forcearmed from the command center orRAM. However, it can be force arme...
Page 91 - Time; Point Assignments; Point Number
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 91 Bosch Security Systems | 1/04 | 47775E P## Alarm Verify Default: See Program Record Sheet Selection: Yes or No Yes Enable alarm verification on this point. Alarm verification points must beprogrammed as resettable. No Disable alarm verificat...
Page 92 - This entry selects one of the 31
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 92 Bosch Security Systems | 1/04 | 47775E P### Point Index Default: See Program Record Sheet Selection: Blank (00) to 31 This entry selects one of the 31 P## Index codes that define the point’s characteristics and determineshow the control pane...
Page 93 - Trips Relay; for this point is programmed.; format (if it is a reporting
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 93 Bosch Security Systems | 1/04 | 47775E P### BFSK/Relay Default: See Program Record Sheet Selection: 0 to 9 Use this option to:2. Determine the point number reported in BFSKwhen this point is tripped. 3. Activate a relay when the point goes i...
Page 94 - COMMAND 7 and COMMAND 9; CMD7 Point Index; CMD7 Point Text; Section 4.2 Point Assignments; CMD9 Point Text
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 94 Bosch Security Systems | 1/04 | 47775E 4.3 COMMAND 7 and COMMAND 9 These entries assign point indexes, BFSK reportcode, BFSK relay that trips, and the text for theCOMMAND 7 and COMMAND 9 commandcenter functions. CMD7 Point Index Default: 31 ...
Page 95 - RADXSKED; Windows; Opening and Closing; Window; Xept Holiday
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 95 Bosch Security Systems | 1/04 | 47775E 5.0 RADXSKED 5.1 Windows Use this programming module to define thewindows for Opening and Closing and User Access. 5.1.1 Opening and Closing Use these windows to set a schedule for disarmingand arming. ...
Page 96 - Early Begin; prompt in this section for report
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 96 Bosch Security Systems | 1/04 | 47775E W# Monday Default: No Selection: Yes or No W# Tuesday Default: No Selection: Yes or No W# Wednesday Default: No Selection: Yes or No W# Thursday Default: No Selection: Yes or No W# Friday Default: No Se...
Page 97 - prompt
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 97 Bosch Security Systems | 1/04 | 47775E W# Open Window Stop Default: 00: 00 Selection: HH:MM (hours and minutes) Enter the time you want the control panel to end theOpening Window. The window stops at the end ofthe minute. 00:00 is midnight, ...
Page 98 - Table 33: Programming to Link Two Days over Midnight; This program item is one of
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 98 Bosch Security Systems | 1/04 | 47775E Table 32: Programming for Two Same Day Opening Windows (see Figure 4 ) Open Close W# Day of Week Early Begin Start Stop Early Begin Start Stop eXcept On Holiday Holiday Index Area(s) 1 S M T W T F S 06:...
Page 99 - W# Close Window Start; PLEASE CLOSE NOW; prompt for other report feature explanations.
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 99 Bosch Security Systems | 1/04 | 47775E Disable/Restart the control panel to activatetoday’s window. If you are programming awindow that needs to activate on the same daythat you are programming it, do a disable/restartafter programming. W# C...
Page 100 - Holiday Indexes for O/C Windows
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 100 Bosch Security Systems | 1/04 | 47775E W# Xept Holiday Default: No Selection: Yes or No Yes Do not activate this window onholidays. To use this selection, the window mustbe programmed to activate on at leastone day of the week and a Holiday...
Page 102 - User Windows
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 102 Bosch Security Systems | 1/04 | 47775E Table 38: Delivery Schedule* Open Close W# Day of Week Early Begin Start Stop Early Begin Start Stop eXcept On Holiday Holiday Index Area(s) 3 S M T W T F S 02 : 30 02 : 45 03 : 00 03 : 05 03: 15 03: 3...
Page 104 - Skeds; Sked Number
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 104 Bosch Security Systems | 1/04 | 47775E Holiday Indexes for User Group Windows You can enable up to four Holiday Indexes to usewith User Group Windows. Enable at least oneHoliday Index if UW# Xept Holiday is programmed Yes for this user wind...
Page 105 - Number
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 105 Bosch Security Systems | 1/04 | 47775E S## Function Code Enter the function code you want this sked to execute. Sked Function 12 is reserved and is not a valid entry. The programmer automatically displays the available parameter choices and...
Page 106 - Relay Number
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 106 Bosch Security Systems | 1/04 | 47775E S## Area 1[through 8] Yes Unbypass allpoints in Area #. 5 Unbypass All Points: This function is not available as a command centerfunction. The entry in the S## Area # prompt defines the area(s) where t...
Page 107 - Expand Test Prt; in Phone is; . To send a Test Report every
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 107 Bosch Security Systems | 1/04 | 47775E S## Defer Test Yes Defer the TestReport. Default: No Selection: Yes or No Enable sked to defer the TestReport No Send the TestReport onschedule. S## Hourly Report Yes Send the TestReport every hour. 9 ...
Page 108 - and; Custom Func; Adjust Time Forward One Hour
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 108 Bosch Security Systems | 1/04 | 47775E S## Cmd Center Default: Blank (0) Selections: Blank (0), 1 to 8 Blank (0) No command centeris specified forCustom Functionactivation. Identify the specific keypad(CC #) where the CustomFunction is ente...
Page 109 - Center; The D9412G supports eight doors the D7412G supports two doors.
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 109 Bosch Security Systems | 1/04 | 47775E S## Cmd Center 1[through 8] Default: Blank Yes Watch tone soundsat this commandcenter. 15 Sound Watch Tone atCommand Center : This function sounds the Watch Tone at thecommand center addressprogrammed ...
Page 113 - Holiday Indexes; At the; Date; prompt, enter the month and day
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 113 Bosch Security Systems | 1/04 | 47775E S## Xept Holiday Default: No Selection: Yes or No Yes Prevent this sked from operating onthe holidays identified in the specificHoliday Index(es) used with this sked.Specific Holiday Indexes are select...
Page 114 - Holiday Index 1; ] key to advance to the next Holiday Index.
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 114 Bosch Security Systems | 1/04 | 47775E Holiday Index 1 Default: No Selection: Yes or No Yes Use this date in Holiday Index 1. No Do not use this date in Holiday Index1. Holiday Index 2 Default: No Selection: Yes or No Holiday Index 3 Defaul...
Page 115 - RADXAUX1; Enable SDI Auto; Baud Rate
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 115 Bosch Security Systems | 1/04 | 47775E 6.0 RADXAUX1 6.1 Introduction The RADXAUX1 Handler is primarily used forprogramming Enhanced Communication capabilitiesfor the 9000 Series Control Panels. As new features(that require new programmable ...
Page 116 - RTS Control; DTR Control; Status Rate; SDI RAM Parameters
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 116 Bosch Security Systems | 1/04 | 47775E 9133 Supervision Default: No Selection: Yes or No Yes Supervise the D9133 Serial InterfaceModule. No Do not supervise the D9133 SerialInterface Module. This item determines whether the D9133 SerialInte...
Page 117 - Enable SDI RAM
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 117 Bosch Security Systems | 1/04 | 47775E • Provide for local programming by a D9133Serial Interface Module. Although not listed in this section, RPS still checksfor the RAM Passcode (see Section 2.7 RAM Parameters ), Datalock Code, and the co...
Page 118 - Call Back Enabled; Figure 6: RAM IP Address Prompts; Set this item to 0 if; RAM IP Address 2; Using an External Modem
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 118 Bosch Security Systems | 1/04 | 47775E When configuring this item to allow forlocal programming, the D9133 needsJumper 8 shorted, power must be cycledafter changing the address, and a standardserial modem cable is required. Call Back Enable...
Page 122 - Enhanced Communications
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 122 Bosch Security Systems | 1/04 | 47775E Enable Ext Modem Default: No Selection: Yes or No Yes Enable SDI Address 88 for use with anexternal modem. No Disable SDI Address 88 for use with anexternal modem. Setting this item to Yes instructs th...
Page 123 - Enhanced Comm; Primary SDI; Figure 9; Path 1 IP Add1
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 123 Bosch Security Systems | 1/04 | 47775E Enhanced Comm Default: No Selection: Yes or No Yes Enable enhanced communications overthe SDI bus. No Do not enable enhancedcommunications over the SDI bus. Determines if the control panel allows enhan...
Page 124 - Count; Example of Heartbeat:
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 124 Bosch Security Systems | 1/04 | 47775E This prompt and the next two prompts determinehow the SDI Path is supervised between the SDIdevice and the central station(s). Do not confuse withthe supervision of the SDI device (the connection ofthe...
Page 126 - Base Port Number; Route Group Attempts
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 126 Bosch Security Systems | 1/04 | 47775E Parity/Stop Default: No/1 Selection: No/1, No/2, Odd/1, Even/1 No/1 No parity, 1 stop bit. No/2 No parity, 2 stop bits. Odd/1 Odd parity, 1 stop bit. Even/1 Even parity, 1 stop bit. This prompt address...
Page 127 - Fire Supv Res Type; Enable Anti Replay; Fire Trouble Resound
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 127 Bosch Security Systems | 1/04 | 47775E RG# 1 Attempt Default: No Selection: Yes or No Yes This route group attempts the primarydestination once and, if unsuccessful,attempts the backup destination. Thecontrol panel still makes a total of te...
Page 128 - Cross Point Parameters; for a complete listing of Cross; Cross Point Time
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 128 Bosch Security Systems | 1/04 | 47775E This item determines if a fire trouble condition,previously acknowledged and silenced at acommand center, automatically (locally) resoundsthe fire trouble tone at 12:00 PM, 12:00 AM, or notat all if th...
Page 130 - Notes
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1 EN | 130 Bosch Security Systems | 1/04 | 47775E Notes
Page 131 - RADXAXS; Door Profile; seconds to 8 seconds; Entry Area
D9412G/D7412G | Program Entry Guide | 7.0 RADXAXS EN | 131 Bosch Security Systems | 1/04 | 47775E 7.0 RADXAXS 7.1 Door Profile This programming category is used to: • Assign an area, that also activates the D9210B • Assign a point to the door • Program the door state to change when the armstate chan...
Page 133 - Strike Profile; Blank, 1 second to 240 seconds
D9412G/D7412G | Program Entry Guide | 7.0 RADXAXS EN | 133 Bosch Security Systems | 1/04 | 47775E D# Card Type Default: 0 Selection: 0 to 3 0 Card format is 26-bit Wiegand. 3 Do not use. This item must be kept to a value of 0 (26 bitWiegand format). 7.2 Strike Profile This programming category is us...
Page 134 - Event Profile; RTE Events require
D9412G/D7412G | Program Entry Guide | 7.0 RADXAXS EN | 134 Bosch Security Systems | 1/04 | 47775E D# Deact On Open? Default: Yes Selection: Yes or No Yes Strike deactivates when the door isopened after a valid Access Grantedrequest. No Strike remains activated for the amountof the programmed strike ...