Page 2 - Listing Label Information/Location; This owner’s manual; Homeowner Reference Information; Read this manual before installing or operating this appliance.; NATURA L GAS; XXXXXXXX; Serial Number
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 2 Listing Label Information/Location Model Name: ___________________________________________ Date purchased/installed: __________________ Serial Number: __________________________________________ Location on fi replace: _____________________ Dealers...
Page 3 - Safety Alert Key:; Used to address practices not related to personal injury.; Table of Contents
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 3 Safety Alert Key: • DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury. • WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury. • CAUTION! Indicate...
Page 5 - B. Limited Lifetime Warranty
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 5 B. Limited Lifetime Warranty Î
Page 7 - TYPE: Vented Gas Fireplace Heaters; Materials that are reported as passing; NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.; When installing above 2000 feet elevation:; Listing and Code Approvals; IPI
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 7 C. BTU Specifi cations MODELS: QFP38-NG, QFP38-LP LABORATORY: Underwriters Laboratories, Inc. (UL) TYPE: Vented Gas Fireplace Heaters STANDARD: ANSI Z21.88b-2008 • CSA 2.33b-2008 E. Non-Combustible Materials Specifi cation Material which will not ...
Page 8 - Gas Equipment Venting System NOT Provided; The following requirements reference various
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 8 H. Requirements for the Commonwealth of Massachusetts For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operate...
Page 9 - A. Gas Fireplace Safety; Operating Instructions; User Guide; Hot glass will cause burns.; WARNING
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 9 Decorative Doors (not shown) Section 2.D. Fixed Glass Assembly Section 2.E. Mantel Hearth (not required) Climate Control Switch Section 2.B. Clear SpaceSection 2.C. Figure 2.1 General Operating Parts B. Your Fireplace WARNING! DO NOT operate fi re...
Page 10 - E. Fixed Glass Assembly; Install ONLY doors or fronts; F. Before Lighting Fireplace; Before operating this fi replace for the fi rst time,; have a; • Verify all shipping materials have been removed from
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 10 Clear Space 3 ft (0.91 m) in front ofappliance C. Clear Space WARNING! DO NOT place combustible objects in front of the fi replace or block louvers. High temperatures may start a fi re. See Figure 2.3. Avoid placing candles and other heat-sensiti...
Page 11 - H. System Description; Transmitter; I. Fan Control Module; • Fan Control Module (FCM) controls the following items remotely:
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 11 H. System Description The Remote Control System consists of three elements:• Transmitter • Receiver • Fan Control Module (FCM) I. Fan Control Module • Fan Control Module (FCM) controls the following items remotely: - Fan (six speeds)- 120V Out - ...
Page 12 - K. Initializing the System for the First Time
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 12 J. Receiver • The receiver is powered by four AA batteries.• The receiver accepts commands via radio frequency from the transmitter to operate the appliance in accordance with the system confi guration. • The receiver three position slider switch...
Page 13 - Room
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 13 L. Transmitter (Remote Control with LCD Display) • The transmitter is powered by three AAA batteries.• A MODE key is provided to index between the features.• A THERMOSTAT key is used to turn on/off or index through thermostat functions (Figures 2...
Page 16 - Remote Flame Control; A single “beep” will confi rm reception of the command.
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 16 Remote Flame Control The fl ame control has six fl ame levels. With the system on, and the fl ame level at the maximum in the appliance, press-ing the DOWN ARROW key once will reduce the fl ame height by one step until the fl ame is turned off. T...
Page 18 - Fan Speed Control; Remote Actuated 120V Auxiliary Outlet (accent lighting); The auxiliary function controls the accent lighting.
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 18 Fan Speed Control Your appliance is equipped with a hot air circulating fan and the speed of the fan can be controlled by the system. The fan speed can be adjusted through six speeds. To activate this function use the MODE key to index to the Fan...
Page 19 - Key Lock; This function will lock the keys to avoid unsupervised operation.; N. Low Battery Power Detection; O. Manual Bypass of the Remote System
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 19 Key Lock This function will lock the keys to avoid unsupervised operation. To activate this function, press the MODE and UP ARROW keys at the same time. (Figure 2.16.) To de-activate this function, press the MODE and UP ARROW keys at the same tim...
Page 20 - your; LIGHTING INSTRUCTIONS; If you do not follow these instructions exact; FOR YOUR; WARNING RISK OF FIRE; NA
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 20 Q. Lighting Instructions (IPI) • For normal use, activate/deactivate your fi replace with the remote control. • The IPI system may be operated with four AA batteries. • If your fi replace must be deactivated for serviced or an extended period of ...
Page 21 - Initial Break-in Procedure; Open windows for air circulation during fi replace; R. After Fireplace is Lit; ISSUE; Condensation on the glass
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 21 Initial Break-in Procedure • T h e f i r e p l a c e s h o u l d b e r u n t h r e e t o f o u r h o u r s continuously on low. • Turn the fi replace off and allow it to completely cool. • Remove fi xed glass assembly. See Section 15.K. • Clean f...
Page 22 - Glass Cleaning; CAUTION! Handle fi xed glass assembly with care.; Note; : Fixed glass assembly and gasketing may have; Maintenance and Service; The fi replace should be; Tools; Remote Control; Tools; Venting; Tools
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 22 Glass Cleaning Frequency: Seasonally By: Homeowner Tools Needed : Protective gloves, glass cleaner, drop cloth and a stable work surface. CAUTION! Handle fi xed glass assembly with care. Glass is breakable. • Avoid striking, scratching or slammin...
Page 23 - Control Compartment and Firebox Top; Logs; Firebox; Gasket Seal and Glass Assembly Inspection; Burner Ignition and Operation
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 23 Control Compartment and Firebox Top Frequency: Annually By: Qualifi ed Service Technician Tools needed : Protective gloves, vacuum cleaner, dust cloths • Vacuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these areas...
Page 24 - Fan Replacement & Maintenance
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 24 Fan Replacement & Maintenance Frequency: Annually By: Qualifi ed Service Technician Tools needed : Protective gloves, screwdriver. • Remove door front and fi xed glass assembly; refer to Sections 14.K. and 14.L. • Remove logs. • Bend right fr...
Page 25 - Remove; • Reinstall all parts.
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 25 • Remove two wing nuts holding the fan bracket in place and remove bracket. • Remove fan through the valve plate opening. Figure 3.7 Remove Fan Bracket Remove Wing nuts (both sides) • Clean or replace fan.• Check condition of gasket. It should re...
Page 26 - A. Typical Appliance System; drawn to scale. Actual product may vary from pictures in manual; Getting Started; Installer Guide
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 26 Noncombustible roof flashing maintains minimum clearance around pipe(SECTION 10) Ceiling Firestopon floor of attic(SECTION 8) Vent Pipe(SECTIONS 7, 8, 10) Framing/Header (SECTION 5) Gas Line(SECTION 12) Framing Headed offin Ceiling Joists(SECTION...
Page 27 - • Installation and use of any damaged appliance or vent system; Any such action may cause a fi re hazard.; Damaged parts
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 27 B. Design and Installation Considerations Quadra-Fire direct vent gas appliances are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the out-side. No additional outside air sourc...
Page 28 - Framing and Clearances; A. Select Appliance Location; Provide adequate; Wiring for and the installation of the heat zone kit must
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 28 5 5 Framing and Clearances A. Select Appliance Location When selecting a location for the appliance it is important to consider the required clearances to walls (see Figure 5.1). WARNING! Risk of Fire or Burns! Provide adequate clearance around a...
Page 29 - B. Construct the Appliance Chase; Treatment of ceiling fi restops and wall shield; Install appliance on hard metal or wood surfaces; must; include the fi nished surface. If drywall
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 29 ALL SURFACES MUST BE FLUSHWITH THE BOTTOM OF THE UNIT. C B A Drywall 1 in. (25 mm) 1 in. (25 mm) 1 in. (25 mm) 0 in. 0 in. D 30 in. (762 mm) to ceiling 0 in. to level of standoffs 36 in. (914 mm) Combustible Object A Rough Opening (Width) B Rough...
Page 30 - D. Mantel and Wall Projections; Comply with all minimum clear-; Mantel Leg or; Mantels
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 30 Measured from appliance opening (in inches) 0 - 10 11 12 22 22 1/2 23 30 in. minimum to ceiling D. Mantel and Wall Projections WARNING! Risk of Fire! Comply with all minimum clear- ances to combustibles as specifi ed. Framing or fi nishing materi...
Page 31 - A. Vent Termination Minimum Clearances; Termination Locations; DO NOT; pack air space with insulation or other; Gas, Wood or Fuel Oil
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 31 A. Vent Termination Minimum Clearances Figure 6.1 Minimum Height From Roof To Lowest Discharge Opening Horizontaloverhang 12 X 20 in. (508 mm) Lowest Discharge Opening Termination Cap Roof Pitchis X / 12 Verticalwall H (min.) - Minimum heightfrom...
Page 33 - mix pipe, fi ttings or joining methods from differ-; Vent Information and Diagrams; D. Measuring Standards; • Horizontal terminations are measured to the outside; DVP Pipe
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 33 Horizontal Vertical 8-1/2 in. 8-1/2 in. 12 in. On 45° runs, 1 ft (.3 m) of diagonal is equal to 8-1/2 in. (216 mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A. Approved Pipe This appliance is approved for use with Hearth & Home Tech...
Page 34 - One Elbow
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 34 H 1 V 1 To replace the fi rst starter elbow with two 45° elbows, refer to Figure 7.4. All other 90° elbows can be replaced with two 45° elbows. General Rules: • SUBTRACT 3 ft. from the total H measurement for each 90° elbow installed horizontally...
Page 35 - Installed
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 35 Figure 7.5 Two Elbows 1. Top Vent - Horizontal Termination - (continued) Figure 7.4 Two 45° Elbows replacing One 90° Elbow 4 ft min. (1.22 m) 20 ft max. (6.10 m) 1 ft min. (.30 m) H 1 V 1 V 2 H 2 Installed Vertically V 1 min H 1 max V 2 min H 2 m...
Page 36 - If installing a vertical vent/
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 36 2. Top Vent - Vertical Termination No Elbow Figure 7.6 Figure 7.7 Two Elbows Note: If installing a vertical vent/ termination off the top of the ap-pliance, the fl ue restrictor should be used. See Section 15.J. for damper adjustment. 12 ft (3.66...
Page 37 - A. Pipe Clearances to Combustibles; Maintain air space clearance to; Vent Clearances and Framing; B. Wall Penetration Framing; Combustible Wall Penetration; • The opening must be framed on all four sides using the; Non-Combustible Wall Penetration; Drywall
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 37 Framing should be constructed of 2 X 4 lumber or heavier. The center of theframing hole is1 in. [25 mm] abovethe center of thehorizontal vent pipe. Vent framing hole. 68 in. (1727 mm)* * Center of pipe 10 in. (254 mm) 12 in. (305 mm) A. Pipe Clea...
Page 38 - C. Install the Ceiling Firestop; A ceiling fi restop; MUST; be used between
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 38 3 fasteners per side Ceiling firestop installed below ceiling. Ceiling firestop installed above ceiling. Install attic insula-tion shields before or after installation of vent system. Attic Above 10 in. (254 mm) Hole should measure 10 in. x 10 in...
Page 39 - D. Install Attic Insulation Shield; DO NOT allow loose materials or; Flat Ceiling Installation; Vaulted Ceiling Installation; Cut previously installed batt insulation to make
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 39 Bend all tabs inward 90° to maintain clearance and prevent insulation from falling inside Insert 3 screws Bend 4 tabs inward 90° to maintain clearance D. Install Attic Insulation Shield WARNING! Fire Risk. DO NOT allow loose materials or insulati...
Page 40 - A. Secure and Level the Appliance; Prevent contact with:; Appliance Preparation; The bottom of the door frame at time of
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 40 A. Secure and Level the Appliance WARNING! Risk of Fire! Prevent contact with: • Sagging or loose insulation• Insulation backing or plastic• Framing and other combustible materials Block openings into the chase to prevent entry of blown-in insula...
Page 41 - Install Vent Pipe; A. Assemble Vent Sections; Attach Pipe to the Firebox Assembly; Assemble Pipe Sections; Make sure that the seams are not aligned to prevent; INCORRECT
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 41 Lances 10 10 Install Vent Pipe A. Assemble Vent Sections Attach Pipe to the Firebox Assembly Note: The end of the pipe sections with the lanced tabs will face towards the appliance. Attach the fi rst pipe section to the starting collar: • Lanced ...
Page 42 - B. Assemble Slip Sections; Overlap pipe; When installing a vent system with an HRC
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 42 B. Assemble Slip Sections WARNING! Risk of Fire or Asphyxiation! Overlap pipe sections at least 1 1/2 in. (38 mm). Secure slip sections with two screws which must not exceed 1/2 in. (13 mm) in length. Use the pilot holes. Pipe could separate if n...
Page 43 - D. Disassemble Vent Sections; Improper support may allow vent to sag and
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 43 Figure 10.7 Securing Vertical Pipe Sections Figure 10.8 Securing Horizontal Pipe Sections D. Disassemble Vent Sections • Rotate either section (see Figure 10.9) so the seams o n b o t h p i p e s e c t i o n s a r e a l i g n e d a s s h o w n i ...
Page 44 - E. Install Metal Roof Flashing; • See minimum vent heights for various pitched roofs; Failure to properly caulk the roof fl ashing could; Caulk
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 44 E. Install Metal Roof Flashing • See minimum vent heights for various pitched roofs (Figure 10.11) to determine the length of pipe to extend through the roof. • Slide the roof fl ashing over the pipe sections extending through the roof as shown i...
Page 45 - F. Assemble and Install Storm Collar; • Wrap the storm collar around the exposed pipe section
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 45 F. Assemble and Install Storm Collar CAUTION! Risk of Cuts, Abrasions or Flying Debris. Wear protective gloves and safety glasses during installa-tion. Sheet metal edges are sharp. • Connect both halves of the storm collar with two screws (see Fi...
Page 46 - Heat shields may not be fi eld constructed.; To prevent overheating and fi re,; G. Install Vertical Termination Cap; Termination Cap
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 46 Important Notice: Heat shields may not be fi eld constructed. H. Heat Shield Requirements for Horizontal Termination WARNING! Risk of Fire! To prevent overheating and fi re, heat shields must extend through the entire wall thick-ness. • DO NOT re...
Page 47 - When using termination caps with factory-supplied; I. Install Horizontal Termination Cap; The telescoping fl ue section
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 47 INTERIOR Heat Shield or Extended Heat Shield Wall Shield Firestop Heat Shield 1-1/2 in. (38 mm) min. overlap SHEATHING Slip Section can be extended Inner Vent Outer Vent EXTERIOR Figure 10.16 Venting through the wall Note: When using termination ...
Page 48 - Shrouds; Shrouds must be constructed; B. Field Constructed Shrouds
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 48 11 11 Shrouds • Chase top shrouds may be fi eld constructed where permitted by regional building codes. WARNING! Risk of Fire! Shrouds must be constructed as specifi ed. Improper construction may overheat chase top. NOTICE: Some regional codes re...
Page 50 - Gas Information; Gas Pressure; Have the gas supply line installed in accordance with; • If substituting for these components, please consult; C. High Altitude Installations; Gas access is on the left side only.
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 50 A. Gas Pressure • Optimum appliance performance requires proper input pressures. • Gas line sizing requirements will be determined in ANSI Z221.3 National Fuel Gas Code in the USA and CAN/CGA B149 in Canada. • Pressure requirements are: B. Gas Co...
Page 51 - A. Wiring Requirements; T h i s a p p l i a n c e m u s t b e e l e c t r i c a l l y w i r e d; C. Intellifi re Ignition System Wiring; Electrical Information; Label all wires prior to
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 51 A. Wiring Requirements N O T I C E : T h i s a p p l i a n c e m u s t b e e l e c t r i c a l l y w i r e d and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code ANSI/NFPA 70-latest edition or...
Page 53 - with ground Romex is the recommended wiring; D. Junction Box Installation; Install the Heat Zone Kit before enclosing the appliance.; Cover Plates
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 53 BLACK WHITE GROUND 14-2 with Ground Romex Figure 13.4 Junction Box Detail 14-2 with ground Romex is the recommended wiring to the appliance junction box. D. Junction Box Installation • Remove junction box from outer shell.• Remove front cover fro...
Page 54 - Non-Combustible Zone; • The QFP38 is shipped with a metal front upper in; Finishing
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 54 0 in. 0 in. 0 in. 15 1/2 in. 43 3/8 in. Wall finishing material may be combustible - Top and Sides High Temperature Sealant (300° F/149° C min.) Non-Combustible Zone Figure 14.2 Non-combustible Facing Diagram A. Facing Material • The QFP38 is shi...
Page 55 - Doors - Outside Surface Fit; Template; B. Facing Template Removal
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 55 Doors - Outside Surface Fit Sheetrock/wall fi nishing material will have been installed and the joints fi lled. • Remove facing templates, retain screws for door installation. • Non-combustible facing material less than one inch thick may be brou...
Page 56 - C. Mantel and Wall Projections
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 56 Measured from appliance opening (in inches) 0 - 10 11 12 22 22 1/2 23 30 in. minimum to ceiling 5 in. (127 mm) Min.to perpendicular wall A 6 in. (152 mm) Min.from fireplace openingto perpendicular wall B Mantel Leg or Perpendicular Wall Top ofApp...
Page 57 - Appliance Setup; As you use the appliance, expansion and contraction
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 57 A. Remove Fixed Glass Assembly See Section 15.K. B. Remove the Shipping Materials Remove shipping materials from inside or underneath the fi rebox. C. Clean the Appliance Clean/vacuum any sawdust that may have accumulated inside the fi rebox or u...
Page 58 - NG
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 58 Figure 15.6 Position Log #4061-170 E. Install Logs, Ember Bed Align notches of ember bed with tabs on rear burner Figure 15.7 Position Ember Bed #4061-171 • Position ember bed over the burner locating the notches of the ember bed inside the tabs ...
Page 59 - Slot over tab
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 59 Lays in groovein front log Figure 15.12 Position Log #4061-176 • Place this log in the white-painted groove of ember bed and front log as shown in Figure 15.13. Figure 15.13 Position Log #4061-177 • The overall placement of the fi rst eight logs ...
Page 60 - Place Rockwool here; G. Complete Log Installation; Follow rockwool placement
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 60 F. Install Andirons, Lava Rock, Rockwool • Remove four screws from the front of the hearth pan as indicated in Figure 15.15. Figure 15.16 Install Andirons Figure 15.15 Remove Screws from Front of Hearth Pan • Align the holes in the andirons with ...
Page 61 - H. Accent Lighting Set Up; Screws; Light Box; Pull light box out of housing
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 61 H. Accent Lighting Set Up • Remove the two screws (one on each side) holding the dashboard in place. • Unplug the two brown wires from the back of the ON/OFF switch. • Set the dashboard and two screws aside for later reinstallation. Screws Figure...
Page 62 - • Repeat with the other light box.; Air Shutter; Replace; I. Adjust the Air Shutter
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 62 • Repeat with the other light box. Figure 15.26 Finished Assembly • Switch the control module to “ON” and/or plug light cord (white) into module. • Plug brown wires into the back of the ON/OFF switch on the dashboard, reattach dashboard with the ...
Page 63 - L. Install Door Fronts; K. Fixed Glass Assembly; Handle fi xed glass; Removing Fixed Glass Assembly; WARNING! Risk of Fire and Electric Shock!; This appliance should be run
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 63 L. Install Door Fronts The doors should be lifted off the frame at the hinges to make installation easier. • Make sure the templates have been removed, retain the screws. • Fit the frame inside the unit opening and use the screws from the facing ...
Page 64 - Troubleshooting; Note on the automatic ignition sequence:
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 64 16 16 Troubleshooting With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do experience a problem, this troubleshooting guide will assist a qualifi ed service technician in th...
Page 66 - Reference Materials; A. Appliance Dimension Diagram
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 66 17 17 Reference Materials 36 3/4 in. 933 mm 15 5/8 in. 397 mm 26° TYP 15 3/8 in. 391 mm 22 1/2 in. 572 mm Gas Line 3 1/8 in. 79 mm 10 in. 254 mm 35 5/8 in. 905 mm 43 3/8 in.1102 mm 31 in. 787 mm 58 7/8 in. 1495 mm 48 5/8 in. 1235 mm 9 5/8 in. 244...
Page 67 - B. Vent Components Diagrams
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 67 B. Vent Components Diagrams Figure 17.2 DVP Vent Components Effective Height/Length DVP Pipe (see chart) Pipe inches mm DVP4 4 102 DVP6 6 152 DVP12 12 305 DVP24 24 610 DVP36 36 914 DVP48 48 1219 DVP6A 3 - 6 76 - 152 DVP12A 3 - 12 76 - 305 Effecti...
Page 70 - Horizontal Termination Cap; The heat shield is designed to be
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 70 B. Vent Components Diagrams (continued) Figure 17.5 DVP Vent Components DVP-HPC1 DVP-HPC2 DVP-TRAPK1 DVP-TRAPK2 DVP-TRAP Horizontal Termination Cap 15-1/8 in. (384 mm) 12 in. (305 mm) 8 in. (203 mm) Max Effective Length Note: Heat shields MUST ov...
Page 71 - Beginning Manufacturing Date: Oct 2008; Service Parts
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 71 C. Service Parts Service Parts Diagram 38 in. Gas Appliance - DV Log Set Assembly Refractory Assembly Part number list on following page. 14 13 10 11 12 1 6 7 5 8 9 3 2 4 16 17 18 19 20 21 22 23 24 26 25 27 15 QFP38-NG, QFP38-LP Beginning Manufac...
Page 72 - ITEM
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 72 IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for your appliance please provide model number and serial number. All parts listed in this manual may be ordered from an authorized dealer. Stocked at Depot ITEM D...
Page 73 - Valve Assembly Diagram; Light Assembly
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 73 C. Service Parts (continued) 38 in. Gas Appliance - DV Valve Assembly Diagram QFP38-NG, QFP38-LP 1 2 3 4 5 6 7 8 Light Assembly Valve Assembly 9 13 12 11 10 14 15 16 18 19 20 21 22 23 24 25 27 26 17 28 29 30 31 R Beginning Manufacturing Date: Oct...
Page 74 - Accent Light Assembly
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 74 IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for your appliance please provide model number and serial number. All parts listed in this manual may be ordered from an authorized dealer. Stocked at Depot ITEM D...
Page 75 - D. Optional Components
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 75 D. Optional Components Tuscan Bar Door - Sienna BZ DF-QFP38TB-SB Tuscan Bar Door - Black DF-QFP38TB-BK Full View Door - Black DF-QFP38FV-BK Full View Door - Hammered Pewter DF-QFP38FV-HP Full View Door - Vintage Copper DF-QFP38FV-VC Iron Gate DF-...
Page 76 - E. Contact Information; For the location of your nearest Quadra-Fire dealer,; DO NOT DISCARD THIS MANUAL; NOTICE; • Leave this manual with
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09 76 E. Contact Information Please contact your Quadra-Fire dealer with any questions or concerns. For the location of your nearest Quadra-Fire dealer, please visit www.Quadra-Fire.com. - NOTES - _______________________________________________________...