Page 2 - SPECIFICATIONS; NOTE: In most cases the fuel/air valve inlet pressure needs
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 2 SPECIFICATIONS Valve Inlet / Outlet Port Sizes: 1, 1-1/2, 2 inches DN25, DN40, DN50 Flange Sizes: Valve size: 1 inch (DN25): ½, ¾, 1 and 1 ¼ in. NPT or BSPP DN15, 20, 25, 32 Valve size: 1 ½ and 2 in. (DN40 and DN50): 1, 1 ¼, 1...
Page 3 - NOTE: The Pressure Module and Fuel/Air Module are not; SECURE MODBUS® COMMUNICATION; INTELLIGENT FEATURES
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 3 32-00018—09 EN 12067-2:2004 Gas/air ratio controls for gas burners and gas burning appliances. Electronic types. EN 126:2012 Multifunctional controls for gas burning appliances EN 298:2012 Automatic burner control systems for burners and ...
Page 4 - VALVE CAPACITY RATINGS; VALVE CAPACITY CURVES; Natural gas
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 4 VALVE CAPACITY RATINGS The SV2 Series valve ratings shown below are for both 4 in. w.c. and 1 in w.c.. Valve Capacity Designation / Internal Port Size @ 4 in. w.c. pressure drop 1,2 (10 mbar) @ 1 in. w.c. pressure drop 1,2 (2....
Page 11 - VALVE ACCESSORIES AND REPLACEMENT PARTS; Category
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 11 32-00018—09 VALVE ACCESSORIES AND REPLACEMENT PARTS The SV2 Series valve has required and optional accessories for installation, pressure switch operation, set-up and fuel/air applications. Flanges are required for each valve and must be...
Page 13 - DIMENSIONAL INFORMATION
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 13 32-00018—09 NOTE: The purchaser of any SV2 Series valves should keep the original packaging for a period of time, should any returns be required. The original packaging will provide the appropriate cushioning and protection for the valve...
Page 16 - VALVE INSTALLATION QUICK START GUIDE; What’s in the box; A. Orientation planning; G. Mount Pressure Module or C6097
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 16 VALVE INSTALLATION QUICK START GUIDE The SV2 Series valve installation steps are illustrated below with elaboration of each step in the following pages after the Quick Start Guide. Please review this Quick Start Guide before ...
Page 17 - Wiring; B. Remove valve front electrical enclosure cover; Checkout and Operation - Leak Check; A. Valve connection and accessory leak test.
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 17 32-00018—09 3 Wiring A. Wiring and conduit recommendations. • Use only flexible conduit on NEMA 4 / IP66 enclosures.• Wiring must comply with all applicable electrical codes, ordinances and regulations.• All line voltage wiring must be N...
Page 18 - B. Power SV2 Series valve and HMI or PC Tool.; Wiring Checkout; A. Replace the electrical enclosure cover.
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 18 5 Programming & Setup Any intelligent features requiring setup must be completed before the valve will be operational. The HMI or PC Tools are used for this purpose. This includes: A. Connect Modbus wiring per HMI Tool or...
Page 19 - Remove from the box; Installation and Mounting; When Installing This Product...; WARNING; Explosion Hazard and Electrical Shock Hazard.
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 19 32-00018—09 1 Remove from the box There will be a second box packaged with the valve which contains accessory items and documentation. The box will contain: • A bag of electrical connectors. Note that connectors are typically not provide...
Page 20 - If valve has been dropped, do not use it.; CAUTION; The SV2 Series valve should be used with clean gas; A. Orientation Planning; NOTICE; B. Flange Mounting to Main Gas Connection
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 20 WARNING Explosion Hazard and Electrical Shock Hazard. Can cause explosion, serious injury or death.• Do not take valve apart.• Do not use tools to operate valve.• Do not use valve if it has been flooded.• Call serviceman if v...
Page 21 - the valve piping may be over stressed.; valve body slots
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 21 32-00018—09 NOTE: Ensure the gap left between the flanges when installed on the pipes does not exceed the valve body width otherwise the valve piping may be over stressed. 4. Screw the flanges onto the pipes. Refer to Fig. 14. NOTES: – T...
Page 22 - D. Vent Valve Connection
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 22 D. Vent Valve Connection 1. Take care that dirt does not enter the gas valve during handling. 2. Remove the vent plug from the side of the valve body. Refer to Fig. 14. NOTE: If you need to replace the NOVV plug on the valve,...
Page 23 - Planning; Premix Mixing Unit Extension Piping; Premix Pulse Lines
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 23 32-00018—09 E. Premix Mixing Unit, Pulse Lines, Air Pre-Filter, Outdoor Air Installations and Start-Up Planning Premix Mixing Unit Extension Piping NOTE: For optimal fuel/air ratio performance, it is recommended to assemble an extension ...
Page 24 - intake shall be part of the annual maintenance of the appliance.; Premix Air Pre-Filter
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 24 The pulse line tubing can be plastic or metal, depending on the connection point and approval body requirement. The Honeywell preferred pulse line connection for the reference pressure is aluminum or stainless steel. Honeywel...
Page 25 - Premix Outdoor Air Installations; into the pulse lines should be avoided or prevented
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 25 32-00018—09 IMPORTANT – The filter should be mounted as close to the valve FARMOD as possible. – Replacement of the filter shall be included in the annual appliance maintenance procedures. Fig. 17. Premix installation with valve, mixing ...
Page 26 - Installation Sequence
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 26 – Excessive moisture can partially or fully clog the pulse lines between the mixing unit and the FARMOD and damage the FARMOD. In this case, the system will fail safely by causing a flame out, a valve lockout and/or may rende...
Page 27 - F.–G. Pressure Module or C6097 Planning and Mounting; SV2 Series Pressure Module Placement and Connection
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 27 32-00018—09 F.–G. Pressure Module or C6097 Planning and Mounting SV2 Series Pressure Module Placement and Connection Refer to document 32-00017, which is packed with the Pressure Modules, for installation instructions regarding the place...
Page 28 - C6097 Pressure Switch Placement and
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 28 C6097 Pressure Switch Placement and Connection WARNING Explosion Hazard. Can cause explosion, serious injury or death. • The M4x25 screws (bag assembly 32305434- 001) shipped with the SV2 valve MUST be used to secure the flan...
Page 29 - Preparation; mounted in the valve train.; C6097 Installation on SV2 Series Valve
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 29 32-00018—09 Preparation 1. Take care that dirt does not enter the gas valve during handling. 2. Select the correct pressure access location (A/B/C/D) to mount the C6097 and correct pressure port to open from the selection table. Refer to...
Page 31 - WIRING; A. Wiring and Conduit Recommendations; Use lead wire which can withstand 90 °C (194 °F) ambient temperatures.; B. Remove Electrical Enclosure Cover
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 31 32-00018—09 3 WIRING From the factory, several items will be fully wired internally via connectors inside the electrical enclosure. The factory wiring terminals can be found in Table 7. Customers may purchase the Honeywell SV2 Series val...
Page 33 - Description
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 33 32-00018—09 SOLENOID 1 PROOF OF CLOSURE POC 1 POC 2 SOLENOID 2 MAINS SUPPLY L1 N MAINS CHASSIS GROUND ILK ILK VPS POC MV2 MV1 OUT IN SW CONTROL WIRING RS-485 MODBUS + – C OFF BIAS TERMIN. BIAS ON 123 MODBUS GND IN1 GND IN2 A N A L O G FI...
Page 34 - BEFORE
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 34 Description Terminal Purpose Rating 6 Applicable Model(s) 5 MAINS SUPPLY 1 L1 Valve incoming voltage supply L1 connection 24, 100-240VAC,15W All N Valve incoming voltage supply neutral connection GROUND(PROTECTIVE EARTH PE) M...
Page 35 - before
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 35 32-00018—09 1. For NEMA 4 / IP66 enclosures: NOTES: – Use only flexible conduit with the SV2 Series valve NEMA 4 / IP66 enclosures. – There are 6 low voltage entry points using M16 x 1.5 cord grips and retaining nuts. – There are 6 entry...
Page 38 - F. Valve Modbus Bias Setup; start bit, 8 data bits, 1 stop bit and no parity; OFF
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 38 F. Valve Modbus Bias Setup The SV2 Series valve can communicate via Modbus RTU communication with any compatible device. Only RTU communications with 1 start bit, 8 data bits, 1 stop bit and no parity is supported. When more ...
Page 39 - Burner Control Interface Wiring; Valve Operational Notes
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 39 32-00018—09 Burner Control Interface Wiring IMPORTANT: – If the burner management control does not have a running or lockout interlock input, consult the factory. The valve ILKIN terminal must be powered before MV1 and MV2 valve seats ca...
Page 42 - SOLA Controller
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 42 SOLA Controller LIMIT CONTROL INPUT RECTIFIER V1 RECTIFIER V2 INTERNAL ELECTRONICS N RUN/LOCKOUT INTERLOCKS OPTIONAL ILK WIRING L1 L1 SV2 SERIES VALVE 1 MATCH SV2 SERIES VALVE AND FLAME SAFEGUARD VOLTAGES. ILK (INTERLOCK) WIR...
Page 43 - 800 SERIES and ControLinks
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 43 32-00018—09 7800 SERIES and ControLinks R7999 11 LCI MV 14 LCO RM7800L RM7838B/C EC7840L DEMAND RECTIFIER V1 V2 INTERNAL ELECTRONICS N RUN/LOCKOUTINTERLOCKS L1 L1 ILKOUT MV1 MV2 ILKIN POC VPS L1 N GROUND L1 CTRL LIMITS 13 INTERLOCKS PRE-...
Page 44 - SLATETM
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 44 SLATE™ LCI FUEL 1/LCI FUEL 2 RECTIFIER V1 RECTIFIER V2 INTERNAL ELECTRONICS N RUN/LOCKOUTINTERLOCKS L1 L1 SV2 SERIES VALVE 1 MATCH SV2 SERIES VALVE AND FLAME SAFEGUARD VOLTAGES. ILK (INTERLOCK) WIRING RUN THROUGH THE SV2 SERI...
Page 45 - European Burner Controls; Option 1; Burner Control
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 45 32-00018—09 European Burner Controls European Standards (CE, EN, etc.) Certain European burner controls do not have separate interlock circuits. The SV2 Series valves require that the ILKIN terminal be tied to the burner management contr...
Page 46 - Option 2
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 46 Option 2 Alternately, a transformer may be used. The transformer must be a double- or reinforced-isolated separation transformer, so that a short between the primary and secondary is excluded. EN298:2012 Annex E requires the ...
Page 47 - Pressure Module
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 47 32-00018—09 External VPS (Valve Proving Sequence) Used; Electronics configuration BASIC (5) with external pressure switch or STANDARD with Pressure Module The SV2 Series valve Pressure Module is used with this scenario with the VPS switc...
Page 49 - SLATE
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 49 32-00018—09 SLATE ™ LCI FUEL 1/LCI FUEL 2 RECTIFIER V1 RECTIFIER V2 INTERNAL ELECTRONICS N RUN/LOCKOUTINTERLOCKS L1 L1 SV2 SERIES VALVE 1 MATCH SV2 SERIES VALVE AND FLAME SAFEGUARD VOLTAGES. ILK (INTERLOCK) WIRING RUN THROUGH THE SV2 SER...
Page 51 - VALVE CHECKOUT AND OPERATION; A. Valve Connection and Accessory Leak Test; leaks on complete system when operational.
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 51 32-00018—09 4 VALVE CHECKOUT AND OPERATION WARNING Explosion Hazard and Electrical Shock Hazard. Can cause explosion, serious injury or death. • Do not allow fuel to accumulate in the combustion chamber for longer than a few seconds with...
Page 52 - Electrical Shock Hazard and Explosion Hazard.
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 52 B. Valve Seat Leak Test (Refer to Fig. 35) IMPORTANT This is a test for checking the closure tightness of the gas shut-off valve. It should be performed only by trained, experienced combustion service technicians during the i...
Page 53 - After the Test; PROGRAMMING AND SETUP
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 53 32-00018—09 12. Close the manual test petcock (F) . 13. Remove the leak test tap from the valve body. 14. Using a small amount of pipe sealant on the 1/8 in (3mm) NPT or BSP plug, re-install the plug in pressure tap point (M) . Maximum t...
Page 54 - B. Power Valve and Programming Tool
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 54 • VPS (valve proving system) • Fuel/air firing curve (Premix/V2V valves) IMPORTANT – You DO NOT have to enable and utilize the intelligent valve features. – Any intelligent features used do require completion of setup and ver...
Page 55 - Final Wiring Check and Static Checkout; and control system function properly.; Troubleshooting; Service Information; Scheduled Inspection and Maintenance
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 55 32-00018—09 6 Final Wiring Check and Static Checkout A. Test CAUTION • Cycle the valve several times with the manual fuel shut-off valve closed. Verify that the valve, accessory modules and control system function properly. • Test each l...
Page 56 - FINISH; A. Replace Enclosure Cover; B. Replace Solenoid Cover; VALVE INTERFACE
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 56 7 FINISH A. Replace Enclosure Cover 1. Replace the valve electrical enclosure cover. 2. Tightening torque for each fastener should be between 1.26 and 1.54 Nm (11 to 13.63 in-lbf). B. Replace Solenoid Cover 1. Replace the sol...
Page 57 - LED; Open; Fault; HGP; NOTE: The Fault LED will also be lit while this fault is active.; PASSWORD RESET FEATURE
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 57 32-00018—09 LED Purpose Applicable Models Open If a POC (proof of closure switch) is present on the valve, this LED indicates that the valve seat is open. This gives visual position indication per FM (Factory Mutual) 7400 and ANSI Z21.21...
Page 58 - Installer Reset; effectively be locked out of editing the valve.; OEM Reset; locked out of editing the valve at the OEM level.
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 32-00018—09 58 Installer Reset An Installer level 12-character random code is generated at the factory, which is only applicable to a particular valve serial number. That code is placed on a card which is shipped with the valve in the acces...
Page 59 - PATENTS; Country
SV2 SERIES SAFETY SHUT-OFF VALVES INSTALLATION INSTRUCTIONS 59 32-00018—09 PATENTS The following is a list of granted patents for the SV2 Series valve platform as of May 2017: NOTE: Every effort is made to keep this information up to date, however, there may be patent grants in process that are not ...
Page 60 - Disposal and Recycling
® U.S. Registered Trademark. © 2018 Honeywell International Inc. 32-00018—09 M.S. Rev. 10-18 Printed in U.S.A. For More Information The Honeywell Thermal Solutions family of products includes Honeywell Combustion Safety, Eclipse, Exothermics, Hauck, Kromschröder and Maxon. To learn more about our pr...