Page 2 - CONTROL KITS; For operation with oil-fired systems. Has electronic post purge.; INSTALLATION SAFETY INSTRUCTIONS; plumbing inside walls.

Page 2 CONTROL KITS CK-20F/HWK: For operation with 30 or 750 millivolt gas-fired water heaters, gas-fired space heaters and gas-fired pool or spa heaters with an internally mounted thermostat. Includes a fixed post purge. CK-21: For operation with gas-fired instantaneous water heaters with a pressur...

Page 3 - UNIT SIZING CHART; OIL

Page 3 INSTALLATION OF SWG POWER VENTER (See Table 1) Table 1 UNIT SIZING CHART OIL GAS MAXIMUM EQUIVALENT FEET OF VENT PIPE MAX* OIL GPH INPUT MAX** BTU/HR. IMPUT AT MAX BTU/HR INPUT AT 60% OF MAX BTU/HR INPUT VENTING WITH VENT PIPE SIZE MODEL 21 80 3” 50 100 4” N/A 70,000 --- --- --- SWG-3 --- 23 ...

Page 4 - equivalent feet of the vent system.; Table 2; VENT PIPE DIAMETER; Figure 1

Page 4 P ROCEDURE F OR C ALCULATING T OTAL E QUIVALENT P IPE L ENGTH I N F EET 1. Calculate the total equivalent feet for each type of fitting used in the venting system from the chart below. 2. Calculate the total amount of feet for the straight lengths of vent pipe. 3. Add the equivalent feet for ...