Field Controls PVO-300 - Manuals

Field Controls PVO-300 – Manual in PDF format online.

Manuals:

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12

Summary

Page 2 - ELECTRICAL RATINGS; determining equivalent length of vent pipe.

Page 2 UNIT SPECIFICATIONS (See Table 1 and Figure 1) Table 1 UNIT DIMENSIONS (INCHES) MODEL “H” “W” “D” I/O* PVO-300 7.50 9.25 7.00 4/4 PVO-600 8.75 9.75 8.50 4/4 * Inlet and outlet diameter. ELECTRICAL RATINGS MODEL VAC Hz RPM WATT AMP TP** PVO-300 120 60 3000 145 2.1 YES PVO-600 120 60 3000 167 1...

Page 3 - MAXIMUM EQUIVALENT HORIZONTAL PIPE LENGTH (FEET); VENTER MODEL NO. AND VENT PIPE DIAMETER; EQUIVALENT LENGTH (FEET) OF VENT PIPE FOR VENT PIPE FITTINGS; Step 1

Page 3 POWER VENTER SIZING In order to choose the correct size power venter for a particular installation, the total input firing rate and total equivalent length of vent pipe to be used must be known. Refer to Table 2 to determine the maximum allowable equivalent feet of pipe for each model used wi...

Page 4 - INSTALLATION SAFETY INSTRUCTIONS; plumbing inside walls.; Diagram A

Page 4 INSTALLATION SAFETY INSTRUCTIONS CAUTION: This device must be installed by a qualified installer in accordance with the manufacturer's installation instructions. Appliances should have a minimum of 75% combustion efficiency or have a maximum measured flue gas temperature of 550°F at the inlet...