Page 2 - ELECTRICAL CONNECTION; ELECTROCUTION HAZARD. FIRST DISCONNECT ALL; INSTALLATION INSTRUCTIONS; Unit Must be Installed by a Qualified Professional; pump, depending upon the installation

2 ELECTRICAL CONNECTION ELECTROCUTION HAZARD. FIRST DISCONNECT ALL ELECTRICAL POWER BEFORE SERVICING. ELECTROCUTION HAZARD. THE DC2 MUST BE ELECTRICALLY GROUNDED. NOTE: The DC2 will operate on 115 VAC & 230 VAC systems. Its ambient air temperature rating is 122°F / 50°C. 1. Disconnect power and ...

Page 3 - NOTE: Steps 5 and 6 are required for outdoor installations only.; LINE; Guardian CPTM; BASIC WIRING

3 4. Loosen the screw on the cover of the controller and remove the plastic cover, exposing the wiring pigtails. (When reassembling cover, do not over-tighten screw.) 5. The wire conduit hub is to be connected to the conduit before the hub is connected to the enclosure. The maximum hub diameter cann...

Page 4 - START UP; “88” will appear, then code; DEVICE ADJUSTMENT (Entering Programming Mode); “LO” appears, release. This will determine the pressure at; OPERATION

4 START UP BEFORE CONTINUING, CHECK FOR OPEN DRAIN VALVES OR OTHER SOURCES OF FLOODING BEFORE STARTING UNIT. 1. Prime pump if necessary and adjust tank precharge to manufacturer’s recommendation for intended pressure range. The factory DC2 setting is 40 psi cut-in and 60 psi cut-out. 2. Turn on powe...