- Page 2 – Unitary Products Group; FACTORY-INSTALLED OPTIONS; ECONOMIZERS; Interlocked outdoor and return air dampers are con-
- Page 3 – FIELD-INSTALLED ACCESSORIES; Power exhaust is not available as
- Page 4 – COIL GUARD KIT; GAS HEAT RATINGS
- Page 5 – COOL ING CA PACI TIES
- Page 6 – BLOWER PER FORM ANCE; BLOWER PERFORMANCE; - BOT TOM DUCT CON NEC TIONS
- Page 7 – OP ER AT ING WEIGHTS; Units With Elec tric Heat
- Page 8 – BLOWER MO TOR AND DRIVE DATA; Cool ing Only Units and Units With Gas Heat; STATIC RE SIS TANCES*
- Page 9 – C O N T R O L W I R I N G
- Page 10 – UTILITIES ENTRY DATA; Front; CLEARANCES
- Page 15 – MECHANICAL SPECIFICATIONS; GENERAL DESCRIPTION; isolated
- Page 16 – UNIT OPERATING CHARACTERISTICS
- Page 17 – ROOF CURB
- Page 18 – OTHER FACTORY INSTALLED OPTIONS
®
SINGLE PACKAGE
GAS / ELECTRIC UNITS AND
SINGLE PACKAGE AIR CONDITIONERS
D2CE / D2CG 300 CONSTANT VOLUME
25 NOMINAL TONS
8.5 EER
SUNLINE 2000 ™
036-21359-001-B-0302
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DESCRIPTION
Sunline™ 2000 series convertible package rooftop mod-
els have two independent refrigerant circuits for efficient
part load operation. Although the units are primarily
designed for curb mounting on a roof, they can also be
slab-mounted at ground level or set on steel beams above
a finished roof.
Cooling only, cooling with gas heat and cooling with electric
heat models are available with a wide variety of factory-
mounted options and field-installed accessories to make
them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead
rigging.
Every unit is completely piped, wired, charged and tested
at the factory to simplify field installation and to provide
years of dependable operation. Powder paint cabinets pro-
vide an exceptionally durable finish with the 750 hour salt
spray process per ASTM-B117 test standard.
All models (including those with an economizer) are suit-
able for either bottom or horizontal duct connections. Mod-
els with power exhaust are suitable for bottom duct
connections only. For bottom duct, you remove the sheet
metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you
replace the supply and return air panels on the rear of the
unit with a side duct flange accessory.
All models are available with five different outdoor air
damper options:
• Single enthalpy economizer
• Differential (dual) enthalpy economizer
• Single enthalpy economizer with power exhaust
• Differential (dual) enthalpy economizer with
power exhaust
• Motorized outdoor air damper
A fixed outdoor air intake assembly is shipped in the return
air compartment of all units ordered without an economizer
or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10,
15 or 25% outdoor air. With bottom duct connections, the
intake damper assembly should be mounted over the
opening in the return air panel. With horizontal ductwork, it
should be mounted on the return air duct.
Technical Guide
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
036-21359-001-B-0302 2 Unitary Products Group All supply air blowers are equipped with a belt drivethat can be adjusted to meet the exact requirements ofthe job. A high speed drive accessory is available forapplications with a higher CFM and/or static pressurerequirement. All compressors include int...
036-21359-001-B-0302 Unitary Products Group 3 FIELD-INSTALLED ACCESSORIES SINGLE INPUT ELECTRONIC ENTHALPYECONOMIZERS Includes a slide-in/plug-in damper assembly with fullymodulating spring-return monitor actuator capable ofintroducing up to 100% outdoor air with nominal 1%leakage type dampers. The ...
036-21359-001-B-0302 4 Unitary Products Group also includes a 1-phase motor to replace the unit'sstandard 3-phase condenser fan motor. Standard unitscan operate down to 45°F. COIL GUARD KIT Provides coil guard and fastners. Note: All gas units are two-stage heating. First stage is 50% of total. All ...