  • Page 2 – PRECAUTIONS; WARNING
  • Page 3 – INSTALLATION; MAIN PIPING CONNECTIONS; PILOT GAS CONNECTION; Loosen the pilot fitting until it is finger-tight.; NOTE
  • Page 4 – PRESSURE REGULATOR ADJUSTMENT; ADJUSTMENT; SYSTEM WIRING
  • Page 5 – PILOT FLAME ADJUSTMENT
  • Page 6 – LIGHTING INSTRUCTIONS; FOR YOUR SAFETY
  • Page 7 – PARA APAGAR EL GAS QUE LLEGA AL ARTEFACTO; PARA SU SEGURIDAD LEA ANTES DE USAR; INSTRUCCIONES DE USO; INSTRUCCIONES DE ENCENDIDO; P ARA
  • Page 8 – AJUSTE; AJUSTE DE PRESIÓN DE SALIDA; AJUSTE DE LA LLAMA; Para REDUCIR la presión del piloto; NOTA
  • Page 11 – ANTES DE INICIAR LA INST; PRECAUCIONES; ¡ADVER
  • Page 12 – DESCRIPCIÓN; Válvula de gas combinada; INSTRUCCIONES P ARA; T emperatura ambiente:; T amaños de tuberías disponibles
Loading the manual

PART NO. 37-6632B

Replaces 37-6632A

0927

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE IN-

STALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY

AND/OR PROPERTY DAMAGE.

The 36H series combination gas valve is designed with redundant and main solenoid valves that control gas flow to the main
burners, a pressure regulator to maintain a constant outlet pressure, and a two position on/off switch for electrical shutoff.
Model numbers below include features as described:

DESCRIPTION

SPECIFICATIONS

36H SERIES

Combination Gas Valve

INSTALLATION INSTRUCTIONS

CONTENTS

Description ................................................................. 1
Specifications ............................................................. 1
Precautions ................................................................ 2
Installation .................................................................. 3

System Wiring

Adjustment ................................................................. 4

Pressure Regulator Adjustment

Lighting Instructions .................................................... 6

Type of Gas:

Natural Gas

Ambient Temperature:

-40° to 175°F

Pressure Rating:

14” W.C. (

1

2

PSI) max.

Voltage:

24 VAC

Frequency:

50/60 Hz

Current:

Single Stage - .410A

Two-Stage - .540A

MOUNTING POSITIONS:

Upright, or 0

°

to 90

°

from upright

UPRIGHT

LEFT or RIGHT

INLET BOSS

VERTICAL

Figure 1. Gas valve mounting positions

360˚

Model

No.

# of

Stages

Open

Characteristics

Proven

Pilot

36H22

1

Fast

NO

36H23

1

Slow

NO

36H32

1

Fast

YES

36H33

1

Slow

YES

36H54

2

Fast

NO

36H55

2

Slow

NO

36H64

2

Fast

YES

36H65

2

Slow

YES

Pressure Regulator Setting: (“ W.C.)

Single

Stage

Two Stage

Low

High

Min Diff.

Low to High

Natural Gas 2.5 - 5.0 1.0 - 3.5

2.5 - 5.0

1.5

LP Gas

7.0 - 12.0 4.0 - 9.5 8.0 - 12.0

2.5

PIPE SIZES/CAPACITIES

Pipe Sizes

Available (inches)

Capacity (BTU/hr) at 1”

pressure drop across valve

AGA Std. Nat. Gas

(1,000 btu/cu. ft.)

LP. Gas

(2,500 btu/cu. ft.)

3/4” x 3/4” NPT

300,000

486,000

1/2” x 3/4” NPT

260,000

421,000

1/2” x 1/2” NPT

170,000

275,400

www.white-rodgers.com

www.emerson.com

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - PRECAUTIONS; WARNING

PRECAUTIONS 1. Failure to turn off electric or main gas supply to heating system could cause personal injury and/or property damage by shock, gas suffocation, fire, and/or explosion. 2. Do not use this control on circuits exceeding speci- fied voltage. Higher voltage will damage the control and may ...

Page 3 - INSTALLATION; MAIN PIPING CONNECTIONS; PILOT GAS CONNECTION; Loosen the pilot fitting until it is finger-tight.; NOTE

INSTALLATION MAIN PIPING CONNECTIONS R e fe r t o w a r n i n g s a n d c a u t i o n s o n p a g e 2 b e fo r e attempting installation. All piping must comply with local codes, ordinances, and/or national fuel gas codes. 1. Turn off electrical power to the system at the fuse box or circuit breaker...

Page 4 - PRESSURE REGULATOR ADJUSTMENT; ADJUSTMENT; SYSTEM WIRING

4 PRESSURE REGULATOR ADJUSTMENT These controls are shipped from the factory with the regulator set as specified on the control label. Consult the appliance rat-ing plate to ensure burner manifold pressure is as specified. If another outlet pressure is required, follow these steps. INSTALLATION Natur...

Other White Rodgers Models

All White Rodgers Other