White Rodgers 36E93-304 - Manual
White Rodgers 36E93-304 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – PRECAUTIONS; WARNING; CAUTION
- Page 5 – MANUAL VALVE KNOB; ADJUSTMENT; PILOT GAS ADJUSTMENT; Restore power to the system.; PRESSURE REGULATOR; Turn off all electrical power to the system.
- Page 6 – LIGHTING INSTRUCTIONS; FOR YOUR SAFETY; FOR YOUR SAFETY READ BEFORE OPERATING; OPERATING INSTRUCTIONS
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398
Printed in U.S.A.
PART NO. 37-5291C
Replaces 37-5291B
9615
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY
AND/OR PROPERTY DAMAGE.
The 36E93-304 combination gas valve is designed for
intermittent ignition system applications. The valve is
equipped with a redundant solenoid valve that controls
gas flow to the pilot and main burners, a main valve that
controls gas flow to the main burner, a pressure regulator
to maintain a constant outlet pressure, and a two-position
gas cock knob for manual gas shut-off.
DESCRIPTION
WHITE-RODGERS
36E93-304
Delay-Opening Combination Gas Valve
INSTALLATION INSTRUCTIONS
SPECIFICATIONS
Type of Gas: Natural gas
LP gas (use conversion kit)
Pressure Regulator Setting:
Nat. Gas – 2.5 to 5.0” W.C.
LP Gas –
7.0 to 12.0” W.C.
Ambient Temperature:
-40
°
to 175
°
F
Pressure Rating: 14” W.C. (
1
⁄
2
PSI) max.
Voltage:
24 VAC
Frequency:
50/60 Hz
PIPE SIZES/CAPACITIES
Pipe Sizes Available
(inches)
Capacity (BTU/hr) at
1” pressure drop across valve
3
⁄
8
” x
3
⁄
8
” NPT any combination
3
⁄
8
” x
3
⁄
4
” NPT straight through
1
⁄
2
” x
3
⁄
8
” NPT any combination
1
⁄
2
” x
1
⁄
2
” NPT any combination
1
⁄
2
” x
3
⁄
4
” NPT straight through
75,000
75,000
100,000
140,000
140,000
AGA Std. Nat. Gas
(1,000 BTU/cu. ft.)
121,500
121,500
162,000
226,800
226,800
LP Gas
(2,500 BTU/cu. ft.)
Figure 1. Gas valve mounting positions
INLET
PRESS
TAP
INLET
PRESS
TAP
PILOT ADJ
360
°
MOUNTING POSITIONS:
Upright, or 0
°
to 90
°
from upright
UPRIGHT
LEFT OR RIGHT
INLET BOSS
UP OR DOWN
Operator: Save these instructions for future use!
CONTENTS
Description ......................................................... 1
Specifications ..................................................... 1
Precautions ........................................................ 2
Installation .......................................................... 3
Pilot Gas Connection
System Wiring
Adjustment ......................................................... 5
Manual Valve Knob
Pilot Gas Adjustment
Pressure Regulator Adjustment
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2 DO NOT BEGIN INSTALLATION UNTIL YOU READTHE FOLLOWING PRECAUTIONS. PRECAUTIONS 1. Failure to turn off electric or main gas supplyto heating system could cause personal in-jury and/or property damage by shock, gassuffocation, fire, and/or explosion. 2. Do not use this control on circuits exceedings...
5 MANUAL VALVE KNOB The manual valve knob is a two-position (ON-OFF) type.To turn manual valve on, rotate knob clockwise or coun-terclockwise to line up the word ON on the knob with theindicator on the cover casting (see fig. 5). To turn manualvalve off, rotate knob clockwise or counterclockwise tol...
LIGHTING INSTRUCTIONS A. This appliance is equipped with an intermittent ignition device which automatically lights the appliance. Do not tryto light the pilot by hand. B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because somegas is heavier than...