White Rodgers 50A55-743 - Manual
White Rodgers 50A55-743 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – MOUNTING AND WIRING; WARNING; CAUTION
- Page 3 – TYPICAL SYSTEM WIRING DIAGRAM; WIRING
- Page 4 – TYPICAL SYSTEM WIRING TABLE
- Page 5 – HEAT MODE; SYSTEM; COOL MODE
- Page 6 – not reset the; DIAGNOSTIC FEATURES; If the; MANUAL FAN ON MODE; TWIN, the control is equipped with a single; SYSTEM LOCKOUT AND; SYSTEM LOCKOUT FEATURES; (System lockout will never; OPERATION
- Page 7 – NOTES
Goodman
White-Rodgers
0130F00005
PCBBF110
PCBBF123
50A55-743
0130F00005S PCBBF110S PCBBF123S
50A55-289
B1809926
PCBBF112
50T55-289
B1809926S
PCBBF112S
50A55-743
Integrated Furnace Control
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
INSTALLATION INSTRUCTIONS
The 50A55-743 is an automatic gas interrupted ignition
control that employs a microprocessor to continually
monitor, analyze, and control the proper operation of the
gas burner, inducer, and fan.
Signals interpreted during continual surveillance of the
thermostat and flame sensing element initiate automatic
ignition of the burner, sensing of the flame, and system
shut-off during normal operation.
These controls incorporate system fault analysis for quick
gas flow shut-off, coupled with automatic ignition retry upon
sensing a fault correction. It is designed as a replacement
for the following controls:
PRECAUTIONS
Installation should be done by a qualified heating and air
conditioning contractor or licensed electrician.
If in doubt about whether your wiring is millivolt, line, or
low voltage, have it inspected by a qualified heating and
air conditioning contractor or licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
Following installation or replacement, follow manufacturer’s
recommended installation/service instructions to ensure
proper operation.
WARNING
!
Failure to comply with the following warnings could
result in personal injury or property damage.
FIRE HAZARD
• Do not exceed the specified voltage.
• Replace existing control with exact model and
dash number.
• Protect the control from direct contact with water
(dripping, spraying, rain, etc.).
• If the control has been in direct contact with
water, replace the control.
• Label all wires before disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation.
• Route and secure wiring away from flame.
SHOCK HAZARD
• Disconnect electric power before servicing.
• Ensure proper earth grounding of appliance.
• Ensure proper connection of line neutral and
line hot wires.
EXPLOSION HAZARD
• Shut off main gas to appliance until installation
is complete.
www.white-rodgers.com
www.emersonclimate.com
PART NO. 37-7348A
1226
CAUTION
!
Do not short out terminals on gas valve or primary
control. Short or incorrect wiring may damage
the thermostat.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2 SPECIFICATIONS INSTALLATION ELECTRICAL RATINGS [@ 77°F (25°C)]: Input Voltage: 25 VAC 50/60 Hz Max. Input Current @ 25 VAC: 0.45 amp Relay Load Ratings: Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pf Ignitor Relay: 6.0 amp @ 120 VAC 50/60 Hz (resistive) Inducer Relay: 2.2 FLA–3.5 LRA @ 120 VAC Circ...
3 TH TR MV MV GND FP HLO HLI PSO PS C R G W Y EAC N HUM N XFMR N LINE N CIR N IGN IGN-N IND IND-N HUM EAC XFMR LINE PARK PARK HEAT COOL IGNITOR Y W G R THERMOSTAT GAS VALVE HIGH LIMIT (N. C.) ROLLOUT (N. C.) AUX. HIGH LIMIT (N. C.) PRESSURE SWITCH (N. O.) FLAME SENSOR PROBE COMPRESSOR CONTACTOR ELEC...
4 50A55 TERMINAL TERMINAL TYPE SYSTEM COMPONENT CONNECTION TYPICAL SYSTEM WIRING TABLE WGRY CTWIN*MV (2 terminals)TRTHRO1RO2FPPSPSOHLIHLOGND INDIGN COOLHEATPARK (2 terminals)LINEXFMREAC (optional)HUM (optional)CIR NLINE NXFMR NEAC N (optional)HUM N (optional)IND-NIGN-N Terminal block with captive sc...