- Page 2 – COMPATIBILITY
- Page 3 – WIRING GUIDELINES; Overview
- Page 4 – Cable Type
- Page 5 – NETWORK CONFIGURATION; Maximum Number of Devices
- Page 6 – Maximum Cable Length
- Page 8 – NETWORK ADAPTER; Network Adapter Status LED; Condition of the Status LED
- Page 9 – INTEGRATION; Global Commands
- Page 10 – TB7200 Integration – Graphical User Interface (GUI) objects
- Page 11 – TB7300 Integration – Graphical User Interface (GUI) Objects
- Page 12 – Configuration Objects; Integrating Honeywell Devices on an MS/TP Network
- Page 13 – Graphical interfaces; Free programmed object or loops; Retries and Timeouts
- Page 14 – TROUBLESHOOTING
- Page 15 – APPENDIX; Supported BACnet Services
- Page 16 – BACNET OBJECTS SUPPORTED; Device Objects
- Page 17 – Objects Table
- Page 20 – Standard Object Types Supported; List of Proprietary Properties
- Page 21 – Property Value Range Restrictions
- Page 22 – Property Enumeration Sets for BV & BI Objects
- Page 23 – Enumeration Sets for MV Objects
INTEGRATION MANUAL
Put Bar Code Here
63-4524-01
BACnet Integration Manual for
TB7200 & TB7300 Series
Thermostats
TB7200 Series
Thermostat
TB7300 Series
Thermostat with
Occupancy Sensor
Contents
Product Overview ............................................................. 1
Compatibility ..................................................................... 2
Tips and Things You Need To Know ................................. 2
Wiring Guidelines ............................................................. 3
Network Configuration ...................................................... 5
Network Adapter ............................................................... 8
Integration ........................................................................ 9
Troubleshooting ................................................................ 14
Appendix .......................................................................... 15
BACnet Objects Supported .............................................. 16
PRODUCT OVERVIEW
The TB7200 Series PI thermostats are designed for zoning
applications, and the TB7300 Series PI thermostats are
designed for fan coil control. Both Series are communicating
thermostats with models available in BACnet
®
MS/TP and
ZigBee
®
wireless mesh protocols and can be easily
integrated into a WEBs-AX building automation system based
on the NiagaraAX
®
platform.
TB7200 and TB7300 Series thermostats are compatible with
the Honeywell Occupancy Sensor Cover. Thermostats
equipped with an occupancy sensor cover provide advanced
active occupancy logic, which will automatically switch
occupancy levels from Occupied to Stand-By and Unoccupied
as required by local activity being present or not. This
advanced occupancy functionality provides advantageous
energy savings during occupied hours without sacrificing
occupant comfort. All thermostats can be ordered with or
without a factory installed PIR cover.
More information
The additional following documentation is available on
http://customer.honeywell.com.
• TB7200 Series Installation Instructions (form number 62-
2019).
• TB7300 Series Installation Instructions (form number 62-
2018).
• PIR Application Guide for TB7200 and TB7300 Series
Thermostats (form number 63-4526).
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—01 2 COMPATIBILITY Honeywell TB7200 and TB7300 Series thermostat compatiblity information is provided in Table 1. Table 1. TB7200 Series and TB7300 Series Thermostat Compatibility Information * 128 total devices supported. ...
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 3 63-4524—01 • To assign a Room Temperature (AV7) value manually, users must first enable the Override mode in the Room Temp Override (BV8) object. • To assign a Room Humidity (AV10) value manually, users must first enable the Over...
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—01 4 Cable Type Honeywell recommends the use of balanced 22-24 AWG twisted pair with a characteristic impedance of 100-130 ohms, capacitance of 30 pF/ft or lower. A braided shield is also recommended. Impedance A value base...