Page 2 - COMPATIBILITY
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—01 2 COMPATIBILITY Honeywell TB7200 and TB7300 Series thermostat compatiblity information is provided in Table 1. Table 1. TB7200 Series and TB7300 Series Thermostat Compatibility Information * 128 total devices supported. ...
Page 3 - WIRING GUIDELINES; Overview
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 3 63-4524—01 • To assign a Room Temperature (AV7) value manually, users must first enable the Override mode in the Room Temp Override (BV8) object. • To assign a Room Humidity (AV10) value manually, users must first enable the Over...
Page 4 - Cable Type
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—01 4 Cable Type Honeywell recommends the use of balanced 22-24 AWG twisted pair with a characteristic impedance of 100-130 ohms, capacitance of 30 pF/ft or lower. A braided shield is also recommended. Impedance A value base...
Page 5 - NETWORK CONFIGURATION; Maximum Number of Devices
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 5 63-4524—01 NETWORK CONFIGURATION EIA-485 networks use a daisy chain configuration. A daisy chain means that there is only one main cable and every network device is connected directly along its path. Figure 1 illustrates two impr...
Page 6 - Maximum Cable Length
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—01 6 Maximum Cable Length The maximum length of a chain is related to its transmission speed. The longer the chain, the slower the speed. Using proper cable, the maximum length of an EIA-485 daisy chain is 4000-ft (1200 m)....
Page 8 - NETWORK ADAPTER; Network Adapter Status LED; Condition of the Status LED
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—01 8 NETWORK ADAPTER The polarity of the connection to the cable is important. From one module to the other it is important that the same colored wire be connected to “plus” or “+” and the other colored wire be connected to...
Page 9 - INTEGRATION; Global Commands
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 9 63-4524—01 INTEGRATION Global Commands The following figure shows which objects from the thermostat can be monitored and commanded from the BAS front-end. Fig. 6. Global commands from a BAS front-end to a typical TB7300 Series th...
Page 10 - TB7200 Integration – Graphical User Interface (GUI) objects
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—01 10 TB7200 Integration – Graphical User Interface (GUI) objects The following objects should be typically used in a GUI: • Room Temperature (AV7); • Occupied and Unoccupied Heat Setpoints (AV 39 and AV43); • Occupied and ...
Page 11 - TB7300 Integration – Graphical User Interface (GUI) Objects
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 11 63-4524—01 TB7300 Integration – Graphical User Interface (GUI) Objects The following objects should be typically used in a GUI: • Room Temperature (AV7); • Occupied and Unoccupied Heat Setpoints (AV 39 and AV43); • Occupied and ...
Page 12 - Configuration Objects; Integrating Honeywell Devices on an MS/TP Network
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—01 12 Configuration Objects The following objects and group objects should be typically used for configuration purposes: • General Options 1 Group GRP 45 and its complete list of objects; • General Options 2 Group GRP 55 an...
Page 13 - Graphical interfaces; Free programmed object or loops; Retries and Timeouts
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 13 63-4524—01 Graphical interfaces For example, some graphic interface might poll every data linked to the graphic page on a COV basis. If the 3 rd party device does not support COV, the graphic interface then relies on a pre-confi...
Page 14 - TROUBLESHOOTING
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—01 14 TROUBLESHOOTING Error / Trouble Condition Possible Cause Solution Thermostat does not come online Two or more controllers have the same MAC address. Modify each duplicate address to a unique number. The MS/TP network ...
Page 15 - APPENDIX; Supported BACnet Services
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 15 63-4524—01 APPENDIX TB7200 & TB7300 Series Protocol Implementation Conformance Statement (PICS) Vendor Name: Honeywell Product Name: TB7200 and TB7300 Series Thermostats TB7200 Product Description The TB7200 series BACnet co...
Page 16 - BACNET OBJECTS SUPPORTED; Device Objects
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—01 16 BACNET OBJECTS SUPPORTED Device Objects Table 4. Device Objects. Object Name Type and Instance Object Property Thermostat Parameter TB7200X5x14B TB73xxX5X14B Device Object_Identifier Property 75 (R,W) Unique ID number...
Page 17 - Objects Table
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 17 63-4524—01 Objects Table Table 5. Objects. Object Name Type and Instance Object Property TB 7200 C5x 14B T B 72 00F 5x14 B TB 7300 A5x 14B TB 7305 A5x 14B TB 7300 C5x 14B TB 7305 C5x 14B TB 7350 C5x 14B TB 7355 C5x 14B T B 73 00...
Page 20 - Standard Object Types Supported; List of Proprietary Properties
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—01 20 Standard Object Types Supported Table 6. Standard object types supported. a Present_Value and Out_of_Service properties are writable for every AV objects except : • PI Heating Demand (AV21)• PI Cooling Demand (AV22) b...
Page 21 - Property Value Range Restrictions
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 21 63-4524—01 Property Value Range Restrictions Table 8. Property value range restrictions. Object name Object Type and instance Minimum range value Maximum range value Default value Room Temperature AV 7 -39.9°F (-40°C) 121.9°F (5...
Page 22 - Property Enumeration Sets for BV & BI Objects
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—01 22 Property Enumeration Sets for BV & BI Objects Table 9. Property enumeration sets for BV and BI objects. (**) This object will be linked to the value of the “UI 3 Configuration” object. When the “UI 3 Configuration...
Page 23 - Enumeration Sets for MV Objects
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 23 63-4524—01 Enumeration Sets for MV Objects Table 10. Property enumeration sets for MV objects. NOTES: 1. Enumeration sets for MV16 depends on Sequence of Operation (MV15) value upon device discovery. If required enumeration is n...