Honeywell T8195B- User Manual

Honeywell T8195B

Honeywell T8195B– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
Page: / 8

Table of Contents:

  • Page 2 – Installation; CAUTION; Fig. 2—Mounting wallplate or subbase to wall.
  • Page 3 – WIRE WALLPLATE OR SUBBASE; Fig. 4—Mounting wallplate or subbase on horizontal outlet box.
  • Page 4 – Subbase; Control transformer power.; MOUNT THE THERMOSTAT; not reverse the knob.; ATTACH THERMOSTAT COVER
  • Page 5 – SET TEMPERATURE CONTROL LEVERS; Checkout; If thermostat fails any test, refer to the Troubleshooting
  • Page 6 – HEATING/COOLING SYSTEM; Typical Wiring Diagrams
Loading the manual

1

69-0564—3

D.F. • Rev. 11-94 • • ©Honeywell Inc. 1994 • Form Number 69-0564—3

T8195B/Q682B,C, Y8224A

Heating or Cooling and Heating/Cooling

New Construction Thermostat,

Wallplate and Subbase

Installation Instructions for the Trained Service Technician.

Preparation

Check thermostat and subbase (if used) suitability for the

heating, cooling, or heating/cooling system. Refer to Table 1.

Assemble tools required: flat bladed screwdriver, hand or

power drill with 3/16-in. drill bit, wire cutter/stripper or
sharp knife, bubble level or plumb bob and line.

Assure power is off to the heating, cooling, or heating/

cooling system at the main fuse panel. Most buildings have
a separate switch box or circuit breaker for disconnecting
power to the heating and cooling (if applicable) equipment.

This thermostat is compatible with most heating, cooling,

or heating/cooling systems. Refer to Table 1 for thermostat
and system compatibility information.

a

If thermostat is not compatible with the system being controlled, the system will not operate. No hazard exists. The thermo-
stat will not be damaged unless it is used to directly control a line voltage system. For proper system operation, a Honeywell
R841 or R8239D1015 Isolating Relay must be added to the thermostat control circuit.

b

Consult manufacturer for installation requirements.

M3375

Recycling Notice

This control contains mercury in a sealed tube. Do not

place control in the trash at the end of its useful life.

If this control is replacing a control that contains mercury

in a sealed tube, do not place your old control in the trash.

Contact your local waste management authority for in-

structions regarding recycling and the proper disposal of this
control, or of an old control containing mercury in a sealed
tube.

If you have questions, call Honeywell Inc. at 1-800-

468-1502.

TABLE 1—THERMOSTAT AND SYSTEM COMPATIBILITY.

Type of Heating System

to be Controlled

Conditions/Compatibility

Electric (Line Voltage)—typical
baseboard and radiant

• The R8239D1015 Isolating Relay or R841 Silent Switching Center must be

installed in the thermostat control circuit.

a

Fan Coil Unit

• Compatible. Assure correct subbase identity is selected for fan control.

Gas—Direct Spark Ignition
(DSI), Intermittent Pilot (IP), and
Standing Pilot (SP)

• Compatible. Assure that 24V control transformer common is accessible for

connection to thermostat cable conductor and power to the transformer is not
regularly interrupted by high temperature or limit operation.

Heat Pump

• Compatible. Assure correct subbase identity is selected for fan control and

changeover control (O terminal for cool and B terminal for heat). Jumper Y
to W for heat pump compressor control.

Hot Water Zone

• Honeywell 2-wire valves are compatible.
• Some non-Honeywell 2-wire valves require an R8239D1015 Isolating Relay

in the thermostat control circuit.

a

• Some 3-wire valves require an R8239A1052 Isolating Relay in the

thermostat control circuit.

a, b

Oil

• Assure that the 24V control transformer common is accessible for connection

to thermostat cable conductor and power to the transformer is not regularly
interrupted by high temperature, purge cycle, or limit operation.

Vent Damper

• Honeywell damper motors are compatible.
• Some non-Honeywell damper motors require an R8239D1015 Isolating

Relay in the thermostat control circuit.

a

Check control amperage

requirement.

Warm Air Zone

• Most are compatible.

M3375

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Honeywell T8195B

Summary

Page 2 - Installation; CAUTION; Fig. 2—Mounting wallplate or subbase to wall.

69-0564—3 2 Installation WHEN INSTALLING THIS PRODUCT… 1. Read these instructions carefully. Failure to follow them could cause a hazardous condition. 2. Installer must be a trained experienced service technician.3. After installation is complete, check out product op- eration as provided in these i...

Page 3 - WIRE WALLPLATE OR SUBBASE; Fig. 4—Mounting wallplate or subbase on horizontal outlet box.

3 69-0564—3 Fig. 3—Leveling methods for wallplate orsubbase. AUTO OFF COOL HEAT ON FAN B O W Y R G M1555 SPIRIT LEVEL PLUMBLINE PLUMBBOB ORWEIGHT Outlet Box Mounting (Fig. 4) Use a horizontally mounted outlet box if possible. If a vertical outlet box is used, mount the wallplate or subbase ona 20268...

Page 4 - Subbase; Control transformer power.; MOUNT THE THERMOSTAT; not reverse the knob.; ATTACH THERMOSTAT COVER

69-0564—3 4 Fig. 5—Methods of connecting terminals. BARRIER FOR WRAPAROUNDCONNECTION—STRIP 7/16 in. [11 mm] FOR STRAIGHTCONNECTION—STRIP 5/16 in. [8 mm] M1556B TABLE 2—TERMINAL DESIGNATIONS. Subbase Terminal Control Function R Control transformer power. W Heating control circuit. Y Cooling control c...

Other Honeywell Models