Honeywell Series 90 - Manual
Honeywell Series 90 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – ORDERING INFORMATION
- Page 4 – SPRING RETURN MODEL SHOWN
- Page 5 – INSTALLATION; Location; CAUTION; Mounting; CAUTION
- Page 6 – Adapter Bracket; Damper Linkages; Valve Linkages
- Page 7 – SPRING RETURN
- Page 8 – SETTINGS AND ADJUSTMENTS; Before Setting Stroke; Setting Stroke
- Page 9 – Auxiliary Switches
- Page 10 – Auxiliary Switch Adjustment; OPERATION
- Page 12 – CHECKOUT; Damper Application
PRODUCT DATA
63- 2190-3
® U.S. Registered Trademark
Copyright © 2002 Honeywell • All Rights Reserved
®
Series 90
Modutrol IV™ Motors
APPLICATION
The Series 90 Modutrol IV™ Motors are spring return and
non-spring return modulating proportional control motors. Use
these motors with controllers that provide a Series 90 output
to operate dampers or valves.
FEATURES
• Directly replaces M934A,D, M941, M944A,C,D,
M945A,D,F, M954, M965, and M975 motors.
• Oil-immersed motor and gear train for reliable
performance and long life.
• Integral junction box provides NEMA 3 weather
protection.
• Motor and circuitry operate from 24 Vac. Models
available with factory installed transformer, or a
field-added internal transformer.
• Quick-connect terminals standard—screw terminal
adapter available.
• Adapter bracket for matching shaft height of older
motors standard with TRADELINE motors.
• Field adjustable stroke (90° to 160°) models available.
• Nominal timing of 30 seconds for 90° stroke and 60
seconds for 160° stroke standard. Other timings
available.
• Die-cast aluminum housing.
• Integral auxiliary switches available factory mounted,
or can be field added to TRADELINE
®
models.
• Integral spring returns motor shaft to normal position
(fully open or fully closed, depending on model) upon
power interruption.
• Field addable interface modules can be mounted in the
junction box to upgrade the motor to Series 70
(electronic) control.
• TRADELINE spring return motors can operate valve
linkages from power end or auxiliary end shafts for
normally closed or normally open valve applications.
Contents
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Settings and Adjustments .................................................
Operation .......................................................................... 10
Replacement .................................................................... 12
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
SERIES 90 MODUTROL IV™ MOTORS 63-2190—3 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further informati...
SERIES 90 MODUTROL IV™ MOTORS 63-2190—3 4 Fig. 1. Modutrol IV Motor mounting dimensions in inches (mm). Table 3. Series 90 Modutrol Motor Power Consumption Ratings. Table 4. Auxiliary Switch Ratings (in Amps). a 40 VA pilot duty, 120/240 Vac on opposite contact. Internal Transformer Power Consumptio...
SERIES 90 MODUTROL IV™ MOTORS 5 63-2190—3 Table 5. Series 90 Modutrol Motor Timing and Torque Ratings. a Timings apply to all TRADELINE models. Some OEM models are available with non-standard timing/torque. b The torque rating for dual-ended shaft motors is the sum of the shaft torques (power-end to...