INSTALLATION INSTRUCTIONS
C7089
Outdoor Sensor
(USE WITH TH8000 AND TH7000 THERMOSTATS)
APPLICATION
This C7089 Outdoor Sensor is used with theTH8000 and
TH7000 Thermostat families.
SPECIFICATIONS
Operating Ambient Temperature Range:
-40 to 120°F (-40 to 49°C).
Display Range:
-40 to 127°F (-40 to 53°C).
Sensor Accuracy:
+/-1.5°F at 70°F (+/-.84 at 21°C)
Operating Relative Humidity:
5% to 95% non-condensing.
Dimensions in in. (mm):
2-1/4 (57) x 3/8 (10) with 60 (1524) leadwires.
INSTALLATION
When Installing this Product…
1.
Read
these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2.
C
heck the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3.
In
staller must be a trained, experienced service
technician.
4.
A
fter installation is complete, check out product
operation as provided in these instructions.
CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment
damage.
Disconnect power supply before connecting
wiring.
Location and Mounting (Fig. 1)
Mount the sensor where:
• cannot tamper with settings.
• there is good air circulation.
• it can measure true outdoor ambient temperature.
• surface is flat.
• wire distance between C7089 and thermostat is less
than 200 feet.
Do
not
mount the sensor:
• in direct sunlight.
• where hot or cold air blows on the sensor. Discharge
line from an outdoor compressor unit, vent or fan
causes inaccurate temperature readings.
• where snow, ice or debris can cover it.
Use the following steps to mount the sensor:
1.
R
emove the sensor from the mounting clip.
2.
Mark the area on the location selected for
mounting the sensor mounting clip.
3.
Mount the clip.
Fig. 1. Typical locations for outdoor sensor.
M7514
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Honeywell C7089
Summary
C7089 OUTDOOR SENSOR 69-1709EFS 2 Wiring CAUTION Electrical Interference (Noise) Hazard.Can cause erratic system operation. Keep wiring at least one foot away from large inductive loads such as motors, line starters, lighting ballasts and large power distribution panels. Use shielded cable to reduce...
® Marque de commerce déposée aux É.-U.Copyright © 2004 Honeywell International Inc. • Tous droits réservés • 69-1709EFS NOTICE D'INSTALLATION C7089 Capteur extérieur (À UTILISER AVEC LES THERMOSTATS TH8000 ET TH7000) APPLICATION Le capteur extérieur C7089 est utilisé avec les thermostats des gammes ...
C7089 CAPTEUR EXTÉRIEUR 69-1709EFS 2 Câblage AVERTISSEMENT Risque d’interférences électriques.Peut provoquer le fonctionnement erratique du système. Tenir le fil à au moins 30 cm de distance de charges inductives importantes tels que des moteurs, des démarreurs, des ballasts d’éclairage et de grands...