Page 2 - Johnson Controls Unitary Products; Physical and Electrical Data
556454-YTG-A-0210 2 Johnson Controls Unitary Products All dimensions are in inches. They are subject to change without notice.Certified dimensions will be provided upon request. . Physical and Electrical Data MODEL TCHD18 S41S3 TCHD24 S41S3 TCHD30 S41S3 TCHD36 S41S3 TCHD48 S41S3 TCHD60 S41S3 Unit Su...
Page 3 - System Charge for Various Matched Systems; Outdoor Unit
556454-YTG-A-0210 Johnson Controls Unitary Products 3 System Charge for Various Matched Systems Outdoor Unit TCHD18S41S3 TCHD24S41S3 TCHD30S41S3 TCHD36S41S3 TCHD48S41S3 TCHD60S41S3 Required Orifice or TXV 1 1TVM4F1 1TVM4F1 1TVM4G1 1TVM4G1 1TVM4J1 1TVM4K1 Factory Charge, lbs-oz 2 - 14 3 - 5 4 - 0 4 -...
Page 4 - System Charge for Various Matched Systems (Continued)
556454-YTG-A-0210 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting line tubing. 2. Verify the TXV and additional charge required for specific evaporator c...
Page 5 - COOLING CAPACITY - With Air Handler Coils
556454-YTG-A-0210 Johnson Controls Unitary Products 5 COOLING CAPACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RATED CFM NET MBH SEER EER TOTAL SENS. 13 SEER AC WITH MV - VARIABLE SPEED TCHD18S41S3 MV12B 17 FC/MC18B 600 18.0 12.3 14.05 11.85 MV12B 17 FC/MC24B 600...
Page 7 - COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils
556454-YTG-A-0210 Johnson Controls Unitary Products 7 COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RATED CFM NET MBH SEER 1 EER TOTAL SENS. TCHD18S41S3 450 - 750 14,17 FC/MC/PC24 600 18.0 12.6 13.00 11.00 450 ...
Page 8 - COOLING CAPACITY - With High Efficiency Motor Furnaces
556454-YTG-A-0210 8 Johnson Controls Unitary Products COOLING CAPACITY - With High Efficiency Motor Furnaces UNIT MODEL FURNACE MODEL COIL MODEL 1 W COOLING RATED CFM Net MBH SEER EER TOTAL SENS. 13 SEER AC WITH VARIABLE SPEED FURNACES 2 TCHD18S41S3 T*(8,L)X*A12 FC/MC/PC18A 14 540 17.7 12.4 14.00 11...
Page 9 - COOLING CAPACITY - With High Efficiency Motor Furnaces (Continued)
556454-YTG-A-0210 Johnson Controls Unitary Products 9 TCHD18S41S3 Y*9C*B12 HD36 17 635 18.5 12.9 14.75 12.35 Y*9C*C16 HD36 21 595 18.6 12.9 15.00 12.50 Y*(8,L)C*A12 UC18A 14 620 18.2 13.1 14.55 12.10 Y*(8,L)C*B12 UC18B 17 580 18.0 12.7 14.50 12.15 Y*9C*B12 UC18B 17 610 18.2 13.1 14.70 12.25 Y*(8,L)C...
Page 17 - ACCESSORIES; Refer to Price Manual for specific model numbers.; Hard Start Kit; provides increased starting torque for areas with low voltage.; Off Cycle Timer Delay; vent rapid recycling of the compressor.; Thermostats; - Compatible thermostat controls are available; TYPICAL INSTALLATION; Model
556454-YTG-A-0210 Johnson Controls Unitary Products 17 ACCESSORIES Refer to Price Manual for specific model numbers. Hard Start Kit - Required when using TXV indoor coil. Also, provides increased starting torque for areas with low voltage. Off Cycle Timer Delay - Provides a 5-minute off cycle to pre...
Page 18 - COOLING PERFORMANCE DATA
556454-YTG-A-0210 18 Johnson Controls Unitary Products Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature ...