York 110 - Manual
York 110 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Fan Coil Unit LOW BODY
- Page 3 – Dimensions
- Page 5 – Compatibility tables for FCU
W
ATER S
YSTEMS
Features
• 6 speed fan
• Cabinet factory fitted
• Valve factory fitted
• Electrical heater factory fitted
• Thermal or modulating valve
• Service valve
Dimensions indicated next page
(1) Cooling capacities based on 7ºC EWT
∆
t 5ºC indoor temperature 27ºC DB / 19ºC WB - (2 pipes - high speed fan)
(2) Heating capacities based on 70ºC EWT
∆
t 10ºC indoor temperature 20ºC - (2 pipes - high speed fan)
(3) In cooling mode 2 rows
For other conditions contact York international
Technical features
YLVR - YLIVR
Model
110
112
114
216
218
Cooling capacity (1) 2 rows
W
832
1054
1493
2041
2356
Cooling capacity (1) 3 rows
W
913
1266
1790
2327
2714
Heating capacity (2) 1 row
W
1167
1691
2319
3029
3552
Pressure drop (3)
kPa
7
1.7
3.8
9
11.7
Power supply
V/Ph/Hz
230 / 1 / 50 + E
Sound power level (3)
dB(A)
49
50
53
53
55
Sound pressure level at 3 m
dB(A)
31
32
35
35
37
Water connections
inch
1/2 “
Thermostats
CSL00 (Built in)
CSR00 (Wall mounted)
Fan speed selector
CML00 (Built in)
CMR00 (Wall mounted)
Thermostat with manual fan speed and S/W
change over
CEL00 (Built in)
CER00 (Wall mounted)
Thermostat with manual fan speed and automatic
change over
CEL20 (Built in)
CER20 (Wall mounted)
Thermostat with auto. fan speed and automatic
change over
CEL30 (Built in)
CER30 (Wall mounted)
Thermostat with auto. fan speed and automatic
change over for modulating valve
Fan Coil Unit
LOW BODY
(2 & 4 pipe system)
A complete range from 0.8 kW up to 2.7 kW
Selection
software
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
E-COM-H0702 Fan Coil Unit LOW BODY 0.8 to 2.7 kW Compatibility table / Codes Model 110 112 114 216 218 With Cabinet YLVR 2 rows l l l l l 3 rows l l l l l 4 rows l l l l l Without Cabinet YLIVR 2 rows l l l l l 3 rows l l l l l 4 rows l l l l l Options (Factory fitted) Coil and heaters 1 row heating...
W ATER S YSTEMS LOW BODY: YLVR Dimensions (All dimensions in mm) DIMENSIONS AND WEIGHTS Dim 110 112 114 216 218 A 648 773 898 1023 1148 B 374 499 624 749 874 C 254 254 254 254 254 D 174 174 174 174 174 E 100 100 100 100 100 G 170 170 170 170 170 H 101 101 101 101 101 J 430 430 430 430 430 N 245 245 ...
W ATER S YSTEMS Compatibility tables for FCU LASER and LOW BODY FEATURES CEL/CER • Dead band for change over 5°C or 2°C (factory set 2°C for 4 pipes and 5ºC for 2 pipes) • Manual fan speeds or automatic (models 20 and 30) • Thermostated fan control or continuous fan running • Option water sensor WS ...