Page 2 - Unitary Products Group
036-21528-007-A-1205 2 Unitary Products Group CONDENSATE PAN A non-corrosive, long-lasting, water-tight pan is posi-tioned below the evaporator coil to collect and drain all condensate; less collection of stagnate condensate will build-up. The condensate pan conforms to ASHRAE 62-89 standards (Venti...
Page 3 - 36-21528-007-A-1205; FIELD-INSTALLED ACCESSORIES
036-21528-007-A-1205 Unitary Products Group 3 PROTECTED COMPRESSOR The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compres-sor, if undesirable op...
Page 5 - FIGURE 1 - UNIT CUT AWAY; TABLE 2: PHYSICAL DATA; MODELS
036-21528-007-A-1205 Unitary Products Group 5 SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period. COP = Coefficient of Performance - the total heatin...
Page 15 - TABLE 16: ADDITIONAL STATIC RESISTANCE
036-21528-007-A-1205 Unitary Products Group 15 NOTE: Above data includes allowances for a dry indoor coil and no filters. For additional pressure drops, refer to the “Additional Static Pressure Resistance” table. TABLE 15: SIDE & BOTTOM SUPPLY AIR BLOWER PERFORMANCE (208/230/460 VOLT 1 ) MODEL N...
Page 16 - FIGURE 2 - FIELD WIRING DIAGRAM
036-21528-007-A-1205 16 Unitary Products Group FIGURE 2 - FIELD WIRING DIAGRAM R G W R C Y Y W2 C W1 O O G THERMOSTAT UNIT TERMINAL STRIP * ** ** = Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire. * = Only required on units with supplemental electric heat. PROGRA...
Page 19 - TABLE 19: APPLICATION DATA; FIGURE 4 - UNIT CLEARANCES; CLEARANCES; UNIT CLEARANCES
036-21528-007-A-1205 Unitary Products Group 19 TABLE 19: APPLICATION DATA MODEL BHP 024 030 036 042 048 060 MINIMUM AIR FLOW (CFM) COOLING 800 1000 1050 1300 1500 1500 HEATING 800 1000 1050 1400 1400 1500 MAXIMUM AIR FLOW (CFM) COOLING 900 1125 1200 1400 1600 2050 HEATING 900 1125 1200 1500 1600 205...
Page 20 - FIGURE 5 - UNIT DIMENSIONS
036-21528-007-A-1205 20 Unitary Products Group FIGURE 5 - UNIT DIMENSIONS )5217 )5217 $OO GLPHQVLRQV DUH LQ LQFKHV 7KH\ DUHVXEMHFW WR FKDQJH ZLWKRXW QRWLFH &HUWLILHGGLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW $ 29(5$// %$&. 81,7 6,=( ',0(16,21 ³$´ 24
Page 21 - FIGURE 6 - TYPICAL APPLICATIONS
036-21528-007-A-1205 Unitary Products Group 21 FIGURE 6 - TYPICAL APPLICATIONS
Page 22 - FIGURE 7 - ROOF CURB DIMENSIONS
036-21528-007-A-1205 22 Unitary Products Group FIGURE 7 - ROOF CURB DIMENSIONS
Page 26 - MECHANICAL SPECIFICATIONS; GENERAL DESCRIPTION
036-21528-007-A-1205 26 Unitary Products Group MECHANICAL SPECIFICATIONS GENERAL DESCRIPTION Units shall be factory-assembled, single packaged, Heat Pumps, designed for outdoor mounted installa-tion. Units shall have minimum SEER ratings of 13.0. They shall have built in, equal size, field convertib...
Page 27 - Solid-core filter dryer to eliminate any foreign matter.; ELECTRIC HEATING SECTION
036-21528-007-A-1205 Unitary Products Group 27 B. Shall have internal isolation and sound muffling tominimize vibration and noise, and be externally iso-lated on a dedicated, independent mounting. 2. Coils: A. Evaporator and condenser coils shall have alumi-num plate fins mechanically bonded to seam...