Page 2 - Safety Information; DANGER; in injury or equipment damage.
2 31005009 00 November 2003 Safety Information NOTICE Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn...
Page 3 - This document contains the following topics:; Front Panel Components; Overview; The illustration below shows the front panel of the I/O base.; Topic
31005009 01 November 2003 3 170AMM11030 Analog/Digital Momentum I/O Base Overview This document contains the following topics: Front Panel Components Overview This section contains an illustration of the front panel of the 170AMM11030 I/O base and a description of the LEDs. Front Panel Illustration ...
Page 4 - LED Illustration; The illustration below shows the LEDs.
4 31005009 01 November 2003 Components of the I/O Module: LED Illustration The illustration below shows the LEDs. LED Descriptions The following table describes the LEDs. Label Description 1 Internal interface (ATI) connector 2 Locking and ground contact for the adapter 3 LED status display 4 Protec...
Page 5 - Specifications
31005009 01 November 2003 5 Specifications Overview This section contains specifications for the 170AMM11030 Momentum I/O base. General Specifications The following table contains general specifications for the I/O base. Each discrete output is protected against short-circuiting and overload. Extern...
Page 6 - Analog Inputs; The following table contains specifications for analog inputs.
6 31005009 01 November 2003 Analog Inputs The following table contains specifications for analog inputs. Number of Channels 2 Input Ranges ± 10 VDC Input Type Single-ended Resolution 14 bit Surge Tolerance Voltage Input ± 30 VDC Over-range Tolerance 5% full scale Protection Polarity inversion Common...
Page 7 - Analog Outputs; The following table contains specifications for analog outputs.; Discrete Inputs
31005009 01 November 2003 7 Analog Outputs The following table contains specifications for analog outputs. Discrete Inputs The following table contains specifications for discrete inputs. Number of Channels 2 Output Ranges ± 10 VDC Resolution 14 Bit Conversion Times 1.60 ms for all channels Output S...
Page 8 - Discrete Outputs; CAUTION
8 31005009 01 November 2003 Discrete Outputs The following table contains specifications for discrete outputs. Description Solid state switch Operating Voltage 16 - 42 VDC Absolute Minimum Voltage 12 VDC Absolute Maximum Voltage 45 VDC Maximum Voltage 50 VDC for 1 ms Number of Points 8 Number of Gro...
Page 9 - The following table outlines physical dimensions for the I/O base.; Internal Pin Connections; AGND and DGND are connected at a single point inside the module.
31005009 01 November 2003 9 Physical Dimensions The following table outlines physical dimensions for the I/O base. Internal Pin Connections Overview This section contains an illustration showing the internal connections between terminals on the I/O base and an optional busbar. Illustration The follo...
Page 10 - Field Wiring Guidelines
10 31005009 01 November 2003 Field Wiring Guidelines Overview This section contains wiring guidelines and precautions for wiring the 170AMM11030 Momentum I/O base. Terminal Connector To connect field devices to the I/O base, you need a field wiring terminal connector. Schneider Electric sells termin...
Page 11 - Wiring Diagrams; discrete input and output
31005009 01 November 2003 11 Wiring Diagrams Overview This section contains diagrams to assist you in wiring the following types of devices. l discrete input and output l analog input and output Discrete I/O Devices The diagram below shows field wiring for discrete input and discrete output devices....
Page 13 - Register for Outputs; ATI communication is lost.; Word
31005009 01 November 2003 13 Register for Outputs Overview 170AMM11030 analog and discrete output channels are configured by entering the appropriate information in output words 1 through 5 as follows. Note: The module will go to fail state values if network or communication adapter ATI communicatio...
Page 14 - Bit Value
14 31005009 01 November 2003 Word 1 System Info RegisterThis word enables the module’s operation, and specifies if user shutdown values are expected. l Valid setting for word one are 0001 ... FFFF l The module’s default value at power-up for this register is zero (module shut down). Word 2 Discrete ...
Page 15 - x Registers; Not Used; the count range maximum value will be used as the shutdown value.; Data Type
31005009 01 November 2003 15 Words 4 ... 5 Analog Fail State Value RegisterThe module always expects two words of user defined data, even if the data is not used. The first word of the user shutdown field is used for channel 1, the second for channel 2. Word 6 Discrete Output RegisterThis word conta...
Page 16 - Range; Output Operating Range; Register for Inputs; The input register is arranged as follows.; Output Voltage
16 31005009 01 November 2003 Range Output Operating Range Register for Inputs Overview The input register is arranged as follows. Output Voltage Data is Left Justified Comment Output Range -10.000 ... +10.000 00382 ... 32382 Nominal output voltage range Output Over Range +10.000 ... +10.238 32384 .....
Page 19 - Analog Map
31005009 01 November 2003 19 Analog Map Overview 170AMM11030 analog values are mapped as follows. Note: The display is standardized, and, in each case, the analog value will appear left justified. Note: The module resolution is 14-bit (0 ... 32766 decimal or 0 ... 7FFE hex). 0 ... 32766 Input Word 2...
Page 20 - Discrete I/O Points and IEC Compliant Data Mapping
20 31005009 01 November 2003 Discrete I/O Points and IEC Compliant Data Mapping Overview The 170AMM11030 base returns 16 discrete input bits to the processor in one 16-bit word (3x). The input points are field wired to row 2 of the base. The processor sends 8 discrete output bits to the base as a si...
Page 21 - Input and Output Ranges
31005009 01 November 2003 21 Input and Output Ranges Ranges and Decimal Values Input Measuring Range ± 10 V The voltage value is calculated with the following formula using the digital measurand: Vn = 1600 Va + 16382 (for the linear range). 10V >10.238V 10.238V 382 <-10.238V -10V 16382 32 764 ...