Quick Start Guide - ATV312

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this product.

Information below is designed to use

single drive

connected to

single motor

with a motor cable length less than 50 meters (164 ft).

In any other case, consult the ATV312 installation manual (BBV46391) and programming manual (BBV46385) on

www.schneider-electric.com

.

Check the delivery of the drive

• Remove ATV312 from the packaging and check that it has not been damaged

.

• Check that the drive reference printed on the label matches the delivery note and corresponding purchase order.

Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________

Check the line voltage compatibility

• Check that the

line voltage

is compatible with the supply range of the drive.

Line voltage _______ Volts / Drive voltage range _______ Volts
Drive range: ATV312

M2 = 200/240 V single phase / ATV312

M3=200/240 V three-phase

ATV312

N4 = 380/500 V three-phase / ATV312

S6 = 525/600 V three-phase

Mount the drive vertically

For a surrounding air temperature up to 50 °C (122 °F)

See installation manual (BBV46391) on

www.schneider-electric.com

for other thermal conditions.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Read and understand this quick start guide before performing any procedure with this drive.
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all

equipment.

• Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Before servicing the drive:

- Disconnect all power, including external control power that may be present.
- Place a "DO NOT TURN ON" label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
- Measure the voltage of the DC bus between the PA/+ and PC/- terminals to ensure that the voltage is less than 42 Vdc.
- If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or operate

the drive

• Install and close all covers before applying power or starting and stopping the drive.

Failure to follow these instructions will result in death or serious injury.

WARNING

DAMAGED DRIVE EQUIPMENT

Do not operate or install any drive or drive accessory that appears damaged.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

ENGLISH

S1A1094202

1

8B0917121134

2

3

(a)

(a)

(a)

(a)

(a)

50 mm (2 in.)

(b)

10 mm (0.4 in.)

(b)

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - external; • Wire the speed reference:; internal; Menu; or; OR; ENT

www.schneider-electric.com 2/4 S1A10942 - 02/2012 Apply power to the drive • Ensure that Logic Inputs are not active (see Li1, Li2, Lix ).• Apply power to the drive.• At first power up, the drive displays nSt (3-wire control) or rdY (2 -wire control), after pushed drive displays bFr . • On next star...

Page 3 - DANGER; HAZARD OF ELECTRIC SHOCK OR ARC FLASH; Factory settings of parameters:

www.schneider-electric.com 3/4 S1A10942 - 02/2012 Set motor parameters (continued) • Set tUn parameter to YES . Set basic parameters Set control choice Start the motor Menu Code Description Factory setting Customer setting drC- [MOTOR CONTROL] tUn [Auto Tunning] : Auto-Tunning for UnS , FrS , nCr , ...

Page 4 - LOC; rdY; Menus structure; Parameter selection; ACC

www.schneider-electric.com 4/4 S1A10942 - 02/2012 bFr Fr1 tCC I-O- CtL- FUn- FLt- COM- SUP- SEt- drC- rEF- LOC 35. rdY rEN 3s MODE MODE 3s MODE 2s ESC rdY [SPEED REFERENCE] [SETTINGS] [MOTOR CONTROL] [INPUTS / OUTPUTS CFG] [APPLICATION FUNCT.] [COMMAND] [FAULT MANAGEMENT] [COMMUNICATION] [MONITORING...