Page 2 - Physical; FUNCTIONALITY; HARDWARE; Note: All modules shown with terminal covers removed.
D Physical FUNCTIONALITY HARDWARE The range of IQ5-IO Expansion Modules comprises the following variants: 16UIO 16DI 8DO 8DO-HOA 8UIO -105 Note: All modules shown with terminal covers removed.
Page 3 - Function; with a maximum load of 12 A; Input/Output Channels; Cable Screening; or fan speed
3 Enclosure Each IQ5-IO Module is housed in a polycarbonate enclosure compatible with the DIN43880 and DIN 19 size 2 standard and with a complimentary styling to the IQ5 controller. Integral clips on the back of the case enable the unit to be clipped on to (and quickly released from) a standard TS35...
Page 4 - Data Sheet; Note: The 24VDC OUT terminal can source up to
Data Sheet 4 Example wiring Digital input: Used for a volt free contact, logic circuit (e.g. TTL, CMOS), open collector (transistor) or open drain (FET). Example wiring free collector circuit The volt free contact has a nominal wetting current of 3.5 mA . The input is ON when the contact is closed. ...
Page 5 - Note: The relay on channel 5 on the 8DO and 8DO/HOA has a; T1L IO Bus
Data Sheet IQ5- I/O MODULE 5 Ensure that external circuits are suitably protected against fault currents that would exceed the ratings for the switching circuits provided in this product. The relay contacts close (i.e. NO makes with IN) when the output channel is ON. Note: The relay on channel 5 on ...
Page 6 - wiring; Maximum I/O Bus Length; Note: One or more additional power supplies may be required on; Maximum Number of Modules; This bus supply is derived from the controller’s
Data Sheet 6 Modules can be slotted together, adjacent to the controller (or other I/O modules) with inter-module connections being made via integral spring connectors. Note: The IQ5-IO-ADPT wiring adapter includes a self-resetting fuse and transient voltage suppression that protects the I/O bus fro...
Page 7 - The 0 V connection must be made when an; I/O Module Addressing; Green indicates normal; Service Button; Note: The language used for display text can changed.; Labelling; XXXXXXXXXXXXXXXXXXXXXX; FIRMWARE; from controller
Data Sheet IQ5- I/O MODULE 7 Important: The 24 Vdc connection from the previous module must not be made. The 0 V connection must be made when an external supply is used and the 0 V line must be continuous for the entire length of the I/O bus. Earthing/Grounding Arrangements It is important that corr...
Page 8 - New versions of firmware may be made available from time to
Data Sheet 8 New versions of firmware may be made available from time to time to change or add functionality or to provide support for new products. New firmware will be installed as part of an upgrade to the IQ5 controller. Once the controller has been upgraded it will automatically update the firm...
Page 10 - ACCESSORIES; RADIO FREQUENCY STATEMENTS AND REQUIREMENTS
IQ5-IO Data Sheet 10 A full description of installing the IQ5-IO modules is given in the IQ5-IO Modules Installation Instructions - Mounting (TG201484) and IQ5- IO Expansion Modules Installation Instructions - Configuring (TG201485). ORDER CODES IQ5-IO-16UIO IQ5 I/O Module with 16 universal input/ou...
Page 11 - Le present appareil est conforme aux CNR d’Industrie Canada; SPECIFICATION; ELECTRICAL; Minimum 60 dB series mode rejection
Data Sheet IQ5-IO 11 ▪ Important: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment. ▪ Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pu...
Page 12 - Maximum Total Load; CONTROLS; MECHANICAL; Flame Retardant Polycarbonate.; Connectors; ENVIRONMENTAL; This device is suitable for indoor use only.; Approvals and Certifications
IQ5-IO Data Sheet 12 Maximum Total Load 12 A (across all channels) Maximum Inrush 7. 5 A (channels 1-4, 6-9); 15 A (channel 5). Minimum Load 10 mA (all channels). Minimum Cable Size 1.5mm 2 (16 AWG). Note: To meet safety requirements, the relays in block 1 (ch.14) and block 2 (ch.5-8) must all be sw...
Page 13 - Trend Control Systems Limited
Data Sheet IQ5-IO 13 Protection IP20 if mounted in an enclosure rated at IP20 or equivalent. Please send any comments about this or any other Trend technical publication to [email protected] © 2022 Honeywell Products and Solutions SARL, Connected Building Division. All rights reserved. Manufactured ...