Page 3 - General Information; Package Contents; The installer must inform the central station of this; Operation; ULC Compliance
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 1 – General Information The IPGSM-4GC Commercial Fire Communicator (henceforth referred to as IPGSM-4GC) includes everything you need to upgrade a commercial fire system that previously reported by POTS to a system that uses the...
Page 4 - STEP 1 – Setup the Customer Account; Have the following information ready:; STEP 2 – Register the Communicator with AlarmNet; IMPORTANT - Do Not mount this device outdoors.; RF Exposure; For this procedure you will need a fully charged 12V battery.
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 2 – STEP 1 – Setup the Customer Account The communicator requires a subscriber account (customer account) to be setup with AlarmNet Direct. This is accomplished by registering the communicator with AlarmNet. Registering, enables...
Page 5 - STEP 4 – Mount and Wire; For ULC compliant installations, refer to the topic on; manual for wiring and component identification.; LED Display Information; ” topic if a wire is detached from its connector.); At this time DO NOT apply power.; Ensure all ground connections are tight.
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 3 – 3. Temporarily wire the battery's negative [–] terminal to TB1–4 on the communicator, then wire the battery's plus [+] terminal to TB1–2 on the communicator. Wait about one minute for the communicator to initialize. 4. Posit...
Page 6 - PowerBoost1; Ensure the following:
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 4 – 11. Verify the PowerBoost1 DIP switches are configured as shown below. iPGSM-COM-008-V0 PowerBoost1 1 5 ON 2 3 4 1 5 ON 2 3 4 (Switch handle = white) 12. Ensure the following: LED Display board is fully seated. All wirin...
Page 7 - BATTERY; TRANSFORMER; Tin wire ends
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 5 – IPGSM-4GC-001-V0 TB 1 678 5 1011 9 234 1 BATTERY ANTENNAMOUNTINGADAPTER CONDUIT CABINET DOOR TO FacilityGround ANTENNA NUT,WASHER 1 5 ON 2 3 4 FUSE + (not supplied) BATTERY 7AH Dialer Capture Module Telco 1 Te lco 2 ECP Tip ...
Page 8 - Wiring the 659EN Line Fault Monitor (Required for ULC); Refer to the installation guide for the 659EN.; Example wiring for an addressable fire control panel:
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 6 – Wiring the 659EN Line Fault Monitor (Required for ULC) The IPGSM-4GC is compatible with Fire Panels when the model 659EN Line Fault Monitor, (also known as the HFS-659EN), is installed. Note, the wire colors may vary. 1. Ref...
Page 9 - STEP 5 – Program the Communicator; You must use the 7720P Programming tool to program the IPGSM-4GC.
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 7 – STEP 5 – Program the Communicator You must use the 7720P Programming tool to program the IPGSM-4GC. When using the 7720P Programming tool, the values given below are for most installations. Press the [#] key to accept the di...
Page 10 - will reset to ensure that the programming features are enabled.; Display; Communicator is not yet initialized.; Setting Factory Defaults; STEP 6 – Configure the Fire Panel
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 8 – To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displa...
Page 11 - Dialer Capture Module Information; LED Indicator; Status LED; zzer; RADIO TROUBLE
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 9 – Dialer Capture Module Information LED Indicator STATUS RED – Steady ON Messages exist in buffer. RED – Flashing No messages to be sent. Waiting for messages. GREEN – Steady ON Normal Indication. GREEN – Blinks every 2 sec. P...
Page 12 - PowerBoost1 Information; Missing or low battery.
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 10 – PowerBoost1 Information LED Indicator STATUS AC (green) AC power available. ACTIVE (green) Cyclical flashing – normal communications. Repetition of 3 flashes – loss of communications. LOW BATT (yellow) Missing or low batter...
Page 13 - Communicator Information; GRN
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 11 – Communicator Information TB 1 67 8 5 1011 9 234 1 IPGSM-4GC-012- V 0 RSSI / Modeandstatus LEDs O N – Message transmission pending. QUICK PERIODIC BLI N K – N ormal. FAST BLI N K – Message w aiting for net w ork ACK. SLOW BL...
Page 14 - RF Specifications; Central Station Messages
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 12 – RF Specifications Frequency Bands 2G GSM/GPRS/EDGE Quad Band, 850/900/1800/1900 MHz 3G/4G UMTS/HSPA+ Band V, Band II Output Power 2G GPRS +33dBm, GMSK modulation EDGE +27dBm, 8-PSK modulation 3G UMTS +24dBm, QPSK modulation...
Page 16 - NOTES
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide – 14 – NOTES
Page 23 - Wiring Diagram
Wiring Diagram The wiring diagram below is depicted for point-to-point electrical connection checks used for troubleshooting or component replacement. It is not intended to show the physical routing of wires. When replacing a wire or component, ensure the wire is routed in the same manner as the ori...
Page 24 - INDUSTRY CANADA CLASS B STATEMENT; For the latest warranty information, please go to:; Woodbridge, Ontario L4L 7Z4 Canada; Copyright
FEDERAL COMMUNICATIONS COMMISSION STATEMENTS The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. CLASS B DIGITAL DEVI...