Page 2 - WIRING; CAUTION; Disconnect power before wiring.
T8611G CHRONOTHERM ® DELUXE ZONING HEAT PUMP THERMOSTAT 69-1414—2 2 Fig. 1. Typical location of thermostat. Fig. 2. Mounting the wallplate. 3. Remove the wallplate from the wall and drill two 3/16 inch (76 mm holes) in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7...
Page 3 - DELUXE ZONING HEAT PUMP THERMOSTAT; Mounting Thermostat; Press lower edge of case to close and latch.
T8611G CHRONOTHERM ® DELUXE ZONING HEAT PUMP THERMOSTAT 3 69-1414—2 Fig. 4. Typical wiring diagram for T8611G on TotalZone® Control Panel. Fig. 5. Correct wiring technique. Mounting Thermostat 1. Engage tabs at the top of the thermostat and wall-plate. See Fig. 6. Be sure to align subbase pins to av...
Page 4 - Using Thermostat Keys; NOTE: Always press the keys with your fingertip or sim-; SETTINGS; System and Fan Settings; System settings control thermostat operation:; Temperature Settings
T8611G CHRONOTHERM ® DELUXE ZONING HEAT PUMP THERMOSTAT 69-1414—2 4 Fig. 7. T8611G key locations and descriptions. Using Thermostat Keys The thermostat keys are used to:• set current day and time,• program times and setpoints for heating and cooling,• temporarily override program temperatures, • dis...
Page 5 - INSTALLER SETUP; IMPORTANT; S e t D a y / T i m e; Hold for; E m H t
T8611G CHRONOTHERM ® DELUXE ZONING HEAT PUMP THERMOSTAT 5 69-1414—2 INSTALLER SETUP The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature display, changeover, and outdoor temperature display. Installer Setup numbers are listed in Table 4...
Page 8 - Setting Current Day and Time
T8611G CHRONOTHERM ® DELUXE ZONING HEAT PUMP THERMOSTAT 69-1414—2 8 Setting Current Day and Time 1. Press Set Current Day/Time. NOTE: On initial powerup or after an extended power loss, 1:00 pm flashes on the display until a key is pressed. 2. Press Day until the current day is displayed. NOTE: Sun=...
Page 9 - A u x H t
T8611G CHRONOTHERM ® DELUXE ZONING HEAT PUMP THERMOSTAT 9 69-1414—2 INSTALLER SELF-TEST Use the Installer Self-Test to check the thermostat operation. Refer to Table 5 for a list of the available self-tests. Table 5. Tests Available In Installer Self-Test. CAUTION Equipment Damage Hazard. Minimum co...
Page 10 - THERMOSTAT INFORMATION; Outdoor Temperature Sensor; Keys to
T8611G CHRONOTHERM ® DELUXE ZONING HEAT PUMP THERMOSTAT 69-1414—2 10 NOTE: Press any key and the displayed numbers will change. Press Time ∇ to go to the previous test and Time ∆ to go to the next test. The Run Program key does not exit this test. Press Time ∆ or Time ∇ and then the Run Program key ...
Page 11 - Symptom
T8611G CHRONOTHERM ® DELUXE ZONING HEAT PUMP THERMOSTAT 11 69-1414—2 TROUBLESHOOTING GUIDE (TABLE 7) Table 7. Troubleshooting Guide. Symptom Possible Cause Action Display does not come on. Thermostat is not being powered. • Check for 24 Vac between R and C terminals. — If missing 24 Vac: — verify th...