Page 2 - SPECIFICATIONS; Processer
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 66-2069—02 2 1. All models include Electronic self-check. 2. Flicker Frequency filter settings available for IR sensor models. 3. Gain Selection available through Signal Processor. The viewing heads, the viewing head connector, and the cable ...
Page 3 - APPROVALS; Signal Processor Mounting; WARNING; Signal Processor Power
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 3 66-2069—02 APPROVALS S70X/S80X Viewing Heads (Connector series and Pipe fit series [PF]) CSA for CLASS I, DIV 2, GROUPS A, B, C, D & T4A FM 7610/NEMA 4X and CLASS 1, DIV 2, GROUPS A, B, C, D & T4A* SIL 3 “Fit for Use” IECEx CSA 10.0...
Page 6 - Viewing Head Connector and Wiring
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 66-2069—02 6 Viewing Head Connector and Wiring Viewing heads are wired to the appropriate terminals located on bottom of the 700ACSP, 700DCSP, P531 or P532 signal processors. The terminals are listed functionally in Table 2. Connectors and ca...
Page 7 - Cable Preparation
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 7 66-2069—02 Fig. 4. Model 700/800 Viewing Head Cable Connections. Cable Preparation NOTE: This section will typically be used for reference only. The S70X/S80X connector parts are very small and delicate and difficult to assemble. It is advi...
Page 8 - Protecting the Viewing Head Cable; Viewing Head Mounting Block
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 66-2069—02 8 Fig. 6. ASSY786 Viewing Head Plug Assembly with C330S. Protecting the Viewing Head Cable (Connector Series) Note that when the wiring needs to meet Class I, Division 2 requirements for use in hazardous locations and when conduit ...
Page 9 - Vibration; ACCESSORIES; Cable and Connectors - S70X/S80X Viewing Heads
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 9 66-2069—02 position has been decided. A continuous flow of air must be maintained in order to reduce the conducted heat and to keep the sight pipe and viewing head lens free of dirt and debris. Air required is about 5 SCFM (0.13 Nm3 /min) d...
Page 10 - Fiber Optic System Compatibility -; OPERATION; IR Detector; Filter Selection for IR Viewing Head; UV Detector
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 66-2069—02 10 Vortex coolers (M3204, M3208, M3210, M4025) - Used with air cooling canister. Contact your distributor or the factory for selection assistance. Cable restraints (800CR, 700CRLT) - Liquid tight S80X and S70X cable restraint versi...
Page 11 - Adjustment of VH Sighting and Gain; NOTE: Adjustment to the viewing head parameters; Orificing; Front Panel LED Indicators and Display; • Two digit display; Push Button Functions; • RELAY ON SETPOINT button:
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 11 66-2069—02 Self-Checking The self-check circuitry guards against internal component failure. There are several tasks that require intelligent interaction between the viewing heads and the signal processor. If all of these interactions do n...
Page 12 - • LOAD FACTORY DEFAULTS button:; Manual Setup of Setpoints; Relay On Setpoint
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 66-2069—02 12 INCREASE, DECREASE and STORE buttons (range of 00 to 29). • LOAD FACTORY DEFAULTS button: — Used to restore all settings to the factory default values • ↑ INCREASE button: — Used to increase parameter value when in programming m...
Page 13 - Setting FFRT (Flame Failure Response; Automatic Setup of Setpoints
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 13 66-2069—02 is live. Adjustments will cause the Flame Relay to de-energize immediately, ignoring FFRT settings. To access this setpoint, press and hold the ACCEPT RATIO/ SET GAIN button for 2 seconds until the current value is displayed. Wh...
Page 14 - Panel Lock; MODBUS COMMUNICATION; Communication Setting
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 66-2069—02 14 the computed ratio, for example, “AC” and “75.” Press either the ACCEPT RATIO or RESET keys. If ACCEPT RATIO is pressed, the display responds with “- -”, the ratio is stored, and the AUTO SET LED is turned on. If RESET is presse...
Page 15 - Modbus RTU Function Supported; Register
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 15 66-2069—02 using key sequence below at the front panel of the 700 as follows: 1. Press and hold BNR-OFF SEQ START/END button for 2 seconds. 2. Press up arrow to change setting from P0 to P1. 3. Press STORE. The factory default Modbus addre...
Page 16 - Fig. 7. Typical Communication Wiring and Recommended Addressing.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 66-2069—02 16 Fig. 7. Typical Communication Wiring and Recommended Addressing. NOTE: Refer to Fig. 8 for converter to RJ11 wiring details. Fig. 8. COMMOD Communication Converter Wiring. BNR 1 11 BOILER 1 ADDRESS M34457 NOTES: A CONVERTER MAY ...
Page 17 - TROUBLESHOOTING; Lockout or Faulty VH Indication; MAINTENANCE
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 17 66-2069—02 TROUBLESHOOTING Lockout or Faulty VH Indication If the viewing head produces any pulses during the last one third of the self-check time, the relay will immediately de- energize, the display will show “LO” (lockout), and the FAU...
Page 21 - Mounting Examples
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 21 66-2069—02 Fig. 13. Viewing Head Mounting Example. Fig. 14. Viewing Head Mounting Example. Mounting Examples Purge air should be provided via the purge air connection to reduce conducted heat and to keep the sight pipe and viewing head len...
Page 23 - Fig. 17. Opposed Fired Viewing Head Sighting
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 23 66-2069—02 Fig. 17. Opposed Fired Viewing Head Sighting VIEWING HEAD BURNER NOZZLE NO. 1 NO. 1 FLAME ENVELOPE NO. 2 FLAME ENVELOPE VIEWING HEAD BURNER NOZZLE NO. 2 HIGH FREQUENCY IR ZONE LOW FREQUENCY ZONE (LESS THAN 36Hz) HIGH FREQUENCY I...
Page 33 - SAFETY MANUAL: 700 SIGNAL PROCESSOR; Safety Function of the 700
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 33 66-2069—02 SAFETY MANUAL: 700 SIGNAL PROCESSOR 700ACSP, 700DCSP Product Declaration FIT FOR USE IN A LOW DEMAND SAFETY APPLICATION. Models: 700ACSP & 700DCSP Safety Function of the 700 The safety function of the 700 signal processor co...
Page 34 - Proof Test Interval; on the proof test interval for 700AC.; on the proof test interval for 700DC.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 66-2069—02 34 As an added safety feature, the coil of the Flame Relay is wired in series with a second pole of contacts on a Self Check Relay. The Self Check Relay is designed to be closed during normal operation of the signal processor and o...
Page 35 - 00AC or 700DC Signal Processor Proof Test Procedure; Equipment; Product Decommissioning
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 35 66-2069—02 700AC or 700DC Signal Processor Proof Test Procedure Equipment • Powered 700AC or 700DC correctly connected to a compatible viewing head. • Multimeter able to take voltage and resistance measurements. • For 700AC signal processo...
Page 36 - Product Declaration
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 66-2069—02 36 SAFETY MANUAL: S70X & 80X VIEWING HEAD S702, S706, S802, AND S806 Product Declaration FIT FOR USE IN A LOW DEMAND SAFETY APPLICATION. Models: S702, S702-PF, S702-HF, S702-HF-PF, S706, S706-PF, S802, S802-HF, S806 Models SIL ...
Page 37 - S70X and S80X Viewing Head Proof; S70X and S80X Viewing Head Proof Test Procedure
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 37 66-2069—02 Safety Function of the S702, S706, S802, and S806 The S702, S706, S802, and S806 viewing heads do not have a safety function. They are used to provide flame intensity information via cables to Signal Processor Models 531AC, 531D...
Page 40 - Automation and Control Solutions
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD Automation and Control Solutions Honeywell International Inc.1985 Douglas Drive NorthGolden Valley, MN 55422customer.honeywell.com ® U.S. Registered Trademark© 2014 Honeywell International Inc.66-2069—02 M.S. Rev. 03-14 Printed in United Stat...