Page 3 - Contents; Safety Overview 1
Contents Dry Contact I/O SmartSlot Card i Safety Overview 1 Important Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Product Overview 2 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Product description 2 Hardware and...
Page 4 - Disclaimer 20; APC Worldwide Customer Support 32
Dry Contact I/O SmartSlot Card ii Disclaimer 20 APC Worldwide Customer Support 32
Page 5 - Safety Overview; Important Safety Information; DANGER; WARNING; CAUTION; NOTICE
Dry Contact I/O SmartSlot Card 1 Safety Overview Important Safety Information Follow all applicable electrical codes for your installation area. Read the instructions carefully to become familiar with the equipment before trying to install, operate, service or maintain it. The following special mess...
Page 6 - Product Overview; Introduction; Product description
2 Dry Contact I/O SmartSlot Card Product Overview Introduction The Schneider Electric™ Dry Contact I/O SmartSlot Card (AP9613) is a management product that provides the following features: • UPS status information presented through 6 fully isolated output relays. This is expandable to 8 using univer...
Page 7 - Hardware and software requirements and tools needed
Dry Contact I/O SmartSlot Card 3 Hardware and software requirements and tools needed The Dry Contact I/O SmartSlot Card works with most APC by Schneider Electric UPS devices with an output rated less than or equal to 160kVA and an available SmartSlot. While most devices meet this requirement; verify...
Page 8 - Showing the product detail; Itemizing the features of the Dry Contact I/O SmartSlot Card
4 Dry Contact I/O SmartSlot Card Showing the product detail Itemizing the features of the Dry Contact I/O SmartSlot Card
Page 10 - Itemizing the input contact and output relay terminal blocks
6 Dry Contact I/O SmartSlot Card Itemizing the input contact and output relay terminal blocks Number of positions on each terminal block 9 Tightening torque 0.35 N.m Tightening torque max 0.4 N.m Wire stripping length 5 mm Minimum wire gauge 0.14 mm 2 (26 AWG) Maximum wire gauge 2.5 mm 2 (14 AWG)
Page 11 - Configuring the Dip Switches; Location of dip switches
Dry Contact I/O SmartSlot Card 7 Configuring the Dip Switches The Dry Contact I/O SmartSlot Card requires configuration before testing, final installation, and use. See “Location of dip switches” directly below and “Dip switches: input and outputs” . Location of dip switches The “callout” below poin...
Page 12 - Dip switches: input and outputs
8 Dry Contact I/O SmartSlot Card Dip switches: input and outputs The table below lists the four possible configurations, with their corresponding inputs and outputs. * With this setup (the factory default), the Configuration Utility is used automatically. Configuration 1 Configuration 2 Configuratio...
Page 13 - Installing; Planning your installation; Operating considerations
Dry Contact I/O SmartSlot Card 9 Installing See “Planning your installation” directly below, “Installation steps” on page 12, and “Connecting to the configuration utility” on page 14. Planning your installation Operating considerations Note the following characteristics of the Dry Contact I/O SmartS...
Page 15 - Connection strategies
Dry Contact I/O SmartSlot Card 11 Connection strategies You can connect the alarm outputs of the Dry Contact I/O SmartSlot Card in several ways to meet the requirements of your management systems or switched load. Both normally open (N. O.) and normally closed (N. C.) systems are accommodated in any...
Page 16 - Installation steps
12 Dry Contact I/O SmartSlot Card Installation steps Warning: After installation, it is strongly recommended that you fully test your configuration before putting it into a production environment. 1. Make all connections to the Dry Contact I/O SmartSlot Card to support your configuration before cont...
Page 18 - Connecting to the configuration utility
14 Dry Contact I/O SmartSlot Card Connecting to the configuration utility The Configuration Utility does not need to be installed, it runs off the Card. With the Utility, you can: • review the status of your AP9613 Dry Contact I/O SmartSlot Card and Universal I/O ports • perform actions in response ...
Page 20 - Specifications
16 Dry Contact I/O SmartSlot Card Specifications For all specifications, when there is a difference between the VDE and UL approval standards, use the lower rating. Electrical, physical, environmental, and approval specifications Item Specification Electrical Nominal switching capacity 3A@ 30 VAC or...
Page 21 - Ratings for input contacts and output relays
Dry Contact I/O SmartSlot Card 17 Ratings for input contacts and output relays Relative HumidityOperatingStorage 0 to 95%0 to 95% Approvals Emissions and Immunity Verification: FCC Part 15 Class A, EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 6...
Page 22 - Warranty; Two-Year Factory Warranty; Terms of warranty
18 Dry Contact I/O SmartSlot Card Warranty Two-Year Factory Warranty This warranty applies only to the products you purchase for your use in accordance with this manual. Terms of warranty APC warrants its products to be free from defects in materials and workmanship for a period of two years from th...
Page 23 - Warranty claims; support
Dry Contact I/O SmartSlot Card 19 OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC’S SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BRE...
Page 24 - Disclaimer
20 Dry Contact I/O SmartSlot Card Disclaimer The information presented in this manual is not warranted by Schneider Electric to be authoritative, error free, or complete. Schneider Electric assumes no liability for damages, violations of codes, improper installation, system failures, or any other pr...
Page 32 - APC Worldwide Customer Support
APC Worldwide Customer Support Customer support for this or any other product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. – www.apc.com (Corporate Headquarters) Connect to loca...