Contents InRow RP Technical Data Manual i Overview .......................................................................... 1 Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Room Air Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 5 - Overview
1 InRow RP Technical Data Manual Overview The modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a variety of spaces. Critical environmental requirements now reach far beyond the confines of the traditional data center or computer room to encomp...
Page 6 - InRow Advantages
InRow RP Technical Data Manual 2 Scalable Solution for Critical Environments InRow Advantages The row-based solution improves energy efficiency and cooling ability in a number of ways. First, the InRow RP draws air directly from the hot aisle, allowing the InRow RP to take advantage of higher heat t...
Page 7 - Hot Aisle Containment System
3 InRow RP Technical Data Manual Hot Aisle Containment System Modular ceiling tiles and doors can be used to enclose the hot aisle. This increases the densities that can be handled in a single rack enclosure by eliminating mixing of hot and cold air streams. This method, called load neutralization, ...
Page 8 - Standard Features
InRow RP Technical Data Manual 4 Standard Features Insulated Cabinet The frame is constructed of 1.5 mm (16 gauge) formed steel for maximum strength. Cabinet is serviceable from the front and rear. All exterior panels and corner posts on the frame are powder coated for durability and an attractive f...
Page 10 - Optional Features
InRow RP Technical Data Manual 6 Optional Features Cable Water Detector A leak detection cable is placed on the floor or subfloor around all possible leak sources. If water or other conductive liquids contact the cable anywhere along its length, the microprocessor controller announces the leak visua...
Page 11 - Microprocessor Controller
7 InRow RP Technical Data Manual Microprocessor Controller Microprocessor Controller The microprocessor controller is standard on each system. The controller provides precision control for the demanding requirements of: • Computer rooms• Telecommunication facilities• Clean rooms• Power equipment• Me...
Page 12 - Alarms
InRow RP Technical Data Manual 8 Alarms The microprocessor controller shall activate a visible and audible alarm in the following occurrences: • Cool Fail• Rack inlet temperature violation• Rack inlet temperature sensor fault• Air filter clogged• Air filter run hours exceeded• Filter DP sensor failu...
Page 13 - InRow RP Models
9 InRow RP Technical Data Manual InRow RP Models Hinged rear doors Casters (all swiveling) Side panel lock Door handle and lock Removable side panel Display interface Adjustable leveling foot Hinged front door na 182 4a
Page 14 - Chilled Water Interior Components (front of unit)
InRow RP Technical Data Manual 10 Chilled Water Interior Components (front of unit) Electric heater (for reheat) Electrical panel Fan Supply temperature sensors Fan guard Main feed breakers Humidifier Ladder diagrams Condensate drain pan User interface connectors Condensate pum...
Page 15 - Chilled Water Interior Components (back of unit)
11 InRow RP Technical Data Manual Chilled Water Interior Components (back of unit) Chilled water coil Rear doors Chilled water control actuator Air filters Chilled water three-way valve body Return humidity sensor Flow meter Return temperature sensor Pipe chase na2 10 5a
Page 18 - Chilled Water and Air-cooled User Interface Connections
InRow RP Technical Data Manual 14 Chilled Water and Air-cooled User Interface Connections Rack inlet temperature sensors 1, 2, 3 A-Link IN A-Link OUT Network port Console port Alarm output, NC (Normally Closed) Alarm output, COM (Common) Alarm output, NO (Normally Open) Supply GND ...
Page 19 - Chilled Water Electrical Panel
15 InRow RP Technical Data Manual Chilled Water Electrical Panel Note: ACRP501 shown. Transformers User interface connectors Main controller board Relay board Ground lug Main circuit breaker — power feed A Main circuit breaker — power feed B Automatic transfer switch (ATS) contactors...
Page 20 - Air-cooled Electrical Panel
InRow RP Technical Data Manual 16 Air-cooled Electrical Panel Note: ACRP 101 shown. Transformers User interface connectors Main controller board Relay board Ground lug Main circuit breaker Compressor fuse block (ACRP100, ACRP101) Compressor circuit breaker (ACRP102) Fan circuit bre...
Page 21 - Performance Specifications
17 InRow RP Technical Data Manual Performance Specifications Chilled Water Performance Specifications 5.5°C (42°F) EWT Temperature dry bulb (DB), wet bulb (WB) °C (°F) CW Delta T °C (°F) Total Net Capacity kW (BTU/hr) Sensible Net Capacity kW (BTU/hr) Sensible Heat Ratio SHR CW Flow Rate l/s (GPM) T...
Page 24 - Chilled Water Performance Specifications 10°C (50°F) EWT
InRow RP Technical Data Manual 20 Chilled Water Performance Specifications 10°C (50°F) EWT Temperature dry bulb (DB), wet bulb (WB) °C (°F) CW Delta T °C (°F) Total Net Capacity kW (BTU/hr) Sensible Net Capacity kW (BTU/hr) Sensible Heat Ratio SHR CW Flow Rate l/s (GPM) Total CW Pressure Drop kPa (f...
Page 27 - Chilled Water Data - General
23 InRow RP Technical Data Manual Chilled Water Data - General MODEL ACRP 500 Series MODULATING VALVES Size -3 Way Ball Valve - NPT mm (in) 25.4 (1) AIR SYSTEM - FANS (Standard Filter Installed) Air Volume - l/s (SCFM) 3162 (6700) Fan Motor - W (HP) 1100 (1.5) Number of Fans 3 COOLING COIL - COPPER ...
Page 28 - Glycol Correction Factors
InRow RP Technical Data Manual 24 Glycol Correction Factors Altitude Correction Factors for InRow Products Air-cooled Performance Specifications Performance Criteria Glycol Solution Percent Weight of Solution *** 0 10% 20% 30% 40% 50% Capacity* Ethylene 1.00 0.97 0.93 0.88 0.81 0.75 Propylene 1.00 0...
Page 30 - Sound Performance Data
InRow RP Technical Data Manual 26 Sound Performance Data Electrical Data Chilled Water Tested Sound Data Fan Speed% Airflow m 3 /s (SCFM) Sound Power dB at Frequency Hz re: 10 -12 W Lp Sound Pressure dB re: 20 microPa* 125 250 500 1000 2000 4000 8000 dBA dBA 35 1.13 (2500) 69.5 37.5 63.5 60.0 54.0 4...
Page 31 - Dimensional Data; InRow RP Assembled Module
27 InRow RP Technical Data Manual Dimensional Data InRow RP Assembled Module Dimensions are shown in mm (in). na24 65 a
Page 32 - SX to VX Height Adapter
InRow RP Technical Data Manual 28 SX to VX Height Adapter SX to 48U SX Height Adapter Dimensions are shown in mm (in). na2 44 5a na24 46 a
Page 33 - Piping and Mechanical Connections; Chilled Water Piping Diagram
29 InRow RP Technical Data Manual Piping and Mechanical Connections Chilled Water Piping Diagram Flex hose or copper Circuit setter (field-installed) Copper tubing Hose end drain with cap Y-strainer with 20 mesh screen (field installed)* Isolation valve *Blow down may be installed on Y-strainer. na ...
Page 34 - Top Chilled Water Piping Access (top view)
InRow RP Technical Data Manual 30 Top Chilled Water Piping Access (top view) Note: Top or bottom entry can be chosen individually for each type of connection, i.e. power, condensate drain, humidifier water supply, chilled water supply and chilled water return. Top piping configuration will have the ...
Page 36 - Air-cooled Piping Diagram
InRow RP Technical Data Manual 32 Air-cooled Piping Diagram Note: Shutoff valves shown nearest to the condensers are not supplied by APC. Note: Route piping through the top or bottom of the InRow RP. Note: Trap the vertical discharge line every 6 m (20 ft) to ensure proper oil return. Note: The maxi...
Page 39 - Air-Cooled Condensers; Mechanical Data
35 InRow RP Technical Data Manual Air-Cooled Condensers Mechanical Data SKU Ambient Temp Sound Pressure (dbA)* Sound Pressure (dbA) ** Air Quantity Fan Unit Connection Size Weight Capacity l/s (CFM) Qty. kW Hot Gas Liquid Kg (Lbs) MBH/1F TD kW/1C TD ACCD75201 95 (35) 67 62 4955 (10500) 1 2.2 1 3/8 i...
Page 41 - Air-cooled Condenser Features
37 InRow RP Technical Data Manual ACCD75207 ACCD75208 and ACCD75209 Dimensions are shown in mm (in). All condensers shown on this page have 16 mm (0.63 in) mounting holes on each of their lower legs. Air-cooled Condenser Features Available in one to three fan configurations, APC offers air-cooled co...
Page 42 - Guide Specifications
InRow RP Technical Data Manual 38 Guide Specifications PART 1 — GENERAL 1.01 SUMMARY A. The environmental control system shall be designed specifically for precision temperature and humidity control applications. It will automatically monitor and control heating, cooling, humidifying, dehumidifying,...
Page 48 - Guidelines for Installation; Room preparation; Receiving the unit; Condensate Drain
InRow RP Technical Data Manual 44 Guidelines for Installation The InRow RP provides reliable, accurate temperature control of computer rooms, laboratories, and other environments that require close tolerance control. The unit incorporates the latest system design innovations to provide you with opti...
Page 50 - APC Worldwide Customer Support
9/2009 990-2469E-001 APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.– www.apc.com (Corporate Headq...