Toshiba LF410/LF600 - Manual

Toshiba LF410/LF600

Toshiba LF410/LF600 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
Page: / 16

Table of Contents:

  • Page 4 – Avoid using the flowmeter in an; Converter LF602 dimensions and weights:
  • Page 5 – ANSI class 150 and class 300 dimensions:; The dimension of L1 is changed when the material of
  • Page 8 – Figure 9. Separate type converter LF602; External Connections; Use the appropriate switch rating as shown below:; flowmeters Wiring Diagram
  • Page 9 – flowmeters wiring Diagram
  • Page 10 – Wiring Precautions; Figure 12. Electrical Conductivity and
  • Page 11 – Combined type; Separate type; Grounding of the Combined type and Separate type
  • Page 12 – Make sure the full-scale flow rate used for the; Figure 13. Flow Rate and Flow Velocity; Calibration Range; Table 1. Standard Flow Range; PED matrix in each flange connection.; Table 2 PED matrix in each flange connection
  • Page 13 – About establishment environment; Ordering Information; Consult Toshiba representative before ordering
  • Page 14 – Table 3. Specification Code (Wafer type detector LF410 Series)
  • Page 15 – Table 4. Specification Code for converters
Loading the manual

No.

EJL-114B

Introduction

The electromagnetic flowmeter uses Faraday’s Law of

electromagnetic induction to measure the process flow.

The device consists of two units: a detector, through

which the fluid to be measured flows and in which

low-level signals proportional to flow rates are

obtained; and a converter, which supplies excitation

current to the detector, and amplifies the signals from

the detector and then processes and converts the

signals into the 4–20mAdc current signal

or

communication signal. Thanks to the unique patented

magnetic field distribution technology, the meter is

highly immune for upstream flow disturbances.

Combined with multi-functional converter LF600

(combined type) or LF602 (separate type) equipped

with its original noise-suppression circuit and

arithmetic operation capability, LF410 has high

tolerance to noise, giving stable output even for slurry

fluid measurement. IR (Infrared) switches enable

parameter setting of the converter without removing

the cover. Flow direction can be set in either way, and

its 128 x 128 dot matrix LCD display allows the LCD

rotated to 90, 180 and 270 degrees with a software.
The AF900 hand-held terminal (HART*

1

communicator) can be used to communicate with the

flowmeter from a remote place. PROFIBUS-PA*

2

interface is available as option.

*1: HART protocol (Highway Addressable Remote

Transducer) is a communication protocol for industrial

sensors recommended by the HCF

(HART

Communication

Foundation).

*2: PROFIBUS is the communication protocol for the

factory automation and process automation that

PROFIBUS Organization recommends. Instead of

analog control with a conventional analog signal

(4-20mA), it is one kind of the fieldbus which digitized

all signals. Flowmeters support PROFIBUS-PA.

Power

supply

Converter

I/O

Detector

Combined type

LF410/LF600
LF414/LF600

Converter

Power

supply

Signal cable

Detector

Separate type
LF410/LF602
LF414/LF602

Terminal box

I/O

Figure1. Configuration

LF410/LF600

LF410

LF602

LF414/LF600 LF414

Figure2. LF410 series Flowmeters

Specifications

Overall Specifications

Measurement range in terms of flow velocity:

0

0.3

m/s to 0

–10

m/s (0

–1.0

ft/s to 0

32.8

ft/s).

0

0.1

m/s to 0

0.3

m/s (0

0.3

ft/s to 0

1.0

ft/s)

range is available optionally.

Accuracy: See the following graph.

Pulse output:

Vs > 0.5 m/s (1.64 ft/s): +/-0.5 % of rate.
Vs < 0.5 m/s (1.64 ft/s): +/-0.3% of rate
+/- 1 mm/s (0.039 inch/s).

Current output: plus +/-8 uA (0.05 % of

span)

Note:

Span = Range in the magmeters.

0.0

1.0

2.0

3.0

4.0

5.0

0

1

2

3

Flow Velosity (m/s)

Error

(% of rate)

Absolute figure

Accuracy

Note:

The accuracy above is measured under standard

operating conditions using the weighing method

at Toshiba's flow calibration facility.

*3: CE mark is under application.

Field Intelligent Device Series

Electromagnetic Flowmeter

LF410 /LF600
LF410 /LF602

15 to 200 mm (1/2" to 8")

0 1 2 10

*3

Certification number

Z01207

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 4 - Avoid using the flowmeter in an; Converter LF602 dimensions and weights:

LF410/LF600 LF410/LF602 4 Cable connection ports: Cable glands — LF600 and LF602 without cFMus Approval: Provided as standard OD of cable φ 11~13mm Material Nylon 66 G (PF) 1/2 male screws. Note: When PROFIBUS option is specified , cable grands size is φ 6~8mm for signal cable, φ 11~13mm for power c...

Page 5 - ANSI class 150 and class 300 dimensions:; The dimension of L1 is changed when the material of

LF410/LF600 LF410/LF602 5 Installation Dimensions Unit : mm L1 Φ D1 (L 2) 64 143 (35) 225 131 BS16, DIN PN16 and JIS 10K dimensions: Meter size (mm) L1 (mm) L2 (mm) D1 (mm) Weight (kg) 15 70 252 49 approx. 5 Note: 1 inch = 25.4mm ANSI class 150 and class 300 dimensions: Meter size (inch) L1 (inch) L...

Page 8 - Figure 9. Separate type converter LF602; External Connections; Use the appropriate switch rating as shown below:; flowmeters Wiring Diagram

LF410/LF600 LF410/LF602 8 矢視A 信号ケーブルグランド 電源ケーブルグランド 封止栓 励磁ケーブルグランド 電流出力ケーブルグランド 接地端子(M4) 取付金具 4-φ11 取付金具 82 (36 ) 15 6 13 15 1 17 8 20 0 151 74±0.3 25 LCD 表示器 赤外線スイッチ Excitation cable ground 15 1 151 74±0.3 4 – Φ 11 Attachment LCD display 17 8 20 0 IR Switch Cable ground 15 6 (36) 25 82 13 I/O cable...

Other Toshiba Models