XT UPS

Installation Planning Guide for 15-80kVA UPS

Standard System: 208v Input, 208/120V Output

Rev. 1.03

Page 1 of 2

4200

FA

-IPG-208v-XT1


General Mechanical Information

Dimensions

(W x D x H)

Approximate Full-Load Heat Loss

UPS kVA/ kW Rating

Inches

Weight

Lbs.

kBTU’s / Hr

15 kVA/12 kW

20 x 36.25 x 59.85

900

5.7

25 kVA/ 20 kW

20 x 36.25 x 59.85

910

7.6

30 kVA/ 24 kW

20 x 36.25 x 59.85

915

9.1

50 kVA/ 40 kW

35.59 x 38.19 x 59.39

2,548

17.7

80 kVA / 64 kW

44 x 31 x 74

2,200

40.0

Primary AC Input (208V 3-Phase / 3-Wire)

Maximum Input Power

Demand

Suggested External

Overcurrent Protection

Suggested Minimum Feeder

Wire Size Per Phase

Suggested Maximum Feeder Length

For Min. Wire Size in Steel Conduit

kVA

PF

Amps

Amps

AWG or kcmil at 75º C Temp. Rating

Feet

15

>0.97

45.7

60 AT

(1) x 8

380

25

>0.97

76.3

90 AT

(1) x 4

380

30

>0.97

92.4

125 AT

(1) x 3

380

50

>0.97

152.6

200 AT

(1) x 1/0

380

80

>0.98

244.3

300 AT

(1) x 300

380

Optional Alternate AC Input (208/120V 3-Phase / 4-Wire)

Maximum Input Power

Demand

Suggested External

Overcurrent Protection

Suggested Minimum Feeder

Wire Size Per Phase / Neutral

Suggested Maximum Feeder Length

For Min. Wire Size in Steel Conduit

kVA

Amps

Amps

AWG at 75º C Temp. Rating

Feet

15

41.6

60 AT

(1) x 8 / (1) x 6

380

25

69.4

90 AT

(1) x 4 / (1) x 2

380

30

83.3

110 AT

(1) x 3 / (1) x 1

380

50

138.8

175 AT

(1) x 1/0 / (1) x 4/0

380

80

222.1

300 AT

(1) x 4/0 / (1) x 400

380

Battery Input (288VDC Nominal)

Battery Capacity Required

for Full Load Output

Maximum Discharge

at Full Load Output

Suggested External

Overcurrent Protection

Suggested Minimum Feeder

Wire Size Per Phase

Suggested Maximum Feeder Length

For Min. Wire Size in Steel Conduit

kVA

kWB

Amps DC

Amps

AWG or kcmil at 75º C Temp. Rating

Feet

15

13.33

61.7

90 AT

(1) x 6

70

25

22.22

102.8

125 AT

(1) x 2

70

30

26.67

123.0

175 AT

(1) x 1

70

50

44.44

205.7

225 AT

(1) x 4/0

70

80

71.11

329.2

400 AT

(2) x 3/0

70

AC Output (208/120V 3-Phase / 4-Wire)

Rated Output Power

Suggested External

Overcurrent Protection

Suggested Minimum Feeder

Wire Size Per Phase / Neutral

Suggested Maximum Feeder Length

For Min. Wire Size in Steel Conduit

kVA

PF

Amps

Amps

AWG or kcmil at 75º C Temp. Rating

Feet

15

0.8

41.6

60 AT

(1) x 8 / (1) x 6

380

25

0.8

69.4

90 AT

(1) x 4 / (1) x 2

380

30

0.8

83.3

110 AT

(1) x 3 / (1) x 1

380

50

0.8

138.8

175 AT

(1) x 1/0 / (1) x 4/0

380

80

0.8

222.1

300 AT

(1) x 4/0 / (1) x 400

380