Slant/Fin XL-2000 - Manual
Slant/Fin XL-2000 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – TABLE 1: Ratings and Dimensions
- Page 3 – BOILER LOCATION; MINIMUM CLEARANCE
- Page 4 – TABLE 2: Provisions for Combustion and Ventilation Air Supply.
- Page 6 – WATER PIPING FOR HOT WATER HEATING BOILERS; Alternate Air Eliminating System
- Page 8 – CLEANING AND FILLING A NEW WATER BOILER; VOLUME OF WATER IN STANDARD PIPE OR TUBE; CARE AND MAINTENANCE
- Page 9 – DO NOT USE ETHYLENE GLYCOL BECAUSE IT IS TOXIC.
- Page 11 – BURNER DATA—CARLIN BURNERS FOR PACKAGED BOILERS ONLY
- Page 12 – BURNER DATA—BECKETT BURNERS FOR PACKAGED BOILERS ONLY
- Page 13 – Figure 7A. Riello 40 Series
- Page 14 – TURBULATOR SETTINGS - RIELLO 40 SERIES; Figure 9A; SETTING THE AIR ADJUSTMENT PLATE
X
XL
L--2
20
00
00
0
OIL-FIRED WATER BOILERS/NO. 2 OIL
INSTALLATION AND OPERATING INSTRUCTIONS
SAFETY WARNING:
KEEP BOILER AREA CLEAR AND FREE FROM COM-
BUSTIBLE MATERIALS, GASOLINE AND OTHER FLAM-
MABLE VAPORS AND LIQUIDS. FAILURE TO ADHERE TO
ABOVE SAFETY WARNING, MAY RESULT IN PERSONAL
INJURY OR DEATH AND PROPERTY DAMAGE.
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE
Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installation Requirements:
Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . . . . .3
Air Supply and Venting . . . . . . . . . . . . . . . . . . . . . . . . . .3,4
Controls and Accessories . . . . . . . . . . . . . . . . . . . . . . . . .5
Piping for Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Installing Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Oil Supply Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Wiring the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Vent Piping and Draft Regulator . . . . . . . . . . . . . . . . . . . .5
Operating Instructions:
Precautions Before Starting . . . . . . . . . . . . . . . . . . . . . . .7
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Cleaning and Filling New Water Boiler . . . . . . . . . . . . . . .8
Care and Maintenance:
Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Freezing Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Oil Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Burner Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11,12
IIM
MP
PO
OR
RT
TA
AN
NT
T::
The installation of this equipment must con-
form to the requirements of the authority having jurisdiction
or, in the absence of such requirements, to the Installation of
Oil Burning Equipment, ANSI/NFPA 31, latest edition, and to
the National Electrical Code ANSI/NFPA 70, latest edition.
The installation must also conform to the additional require-
ments in this Slant/Fin Instruction Manual. Where there is any
difference, the more stringent requirement shall govern.
In addition, where required by the authority having jurisdiction,
the installation must conform to American Society of Mechanical
Engineers Safety Code for Controls and Safety Devices for
Automatically Fired Boilers, No. CSD-1, latest edition.
THIS MANUAL MUST BE LEFT WITH OWNER AND
SHOULD BE HUNG ON OR ADJACENT TO THE BOILER
FOR REFERENCE.
IMPORTANT: This boiler must be installed, serviced and
repaired by a trained, experienced, service technician,
licensed for the installation and servicing of oil burning hot
water heating system equipment or otherwise qualified by the
authorities having jurisdiction over the installation.
Printed in U.S.A.305
Publication No. XL-40
Part No. 48-0090
Revision C
™
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
XL-2000 2 XL-20 0.65 91,000 78 68 8 x8x15 6 x 15 83.56 8 11/ 16 4 9/ 16 6¶ 1 1/ 4 25 3/ 8 XL-30H 0.85 119,000 104 90 8 x8x15 6 x 15 86.00 12 3/ 16 6 5/ 16 6 1 1/ 4 28 7/ 8 XL-30 1.00 140,000 121 105 8 x8x15 6 x 15 85.04 12 3/ 16 6 5/ 16 6 1 1/ 4 28 7/ 8 1.15 161,000 138 120 8 x8x15 6 x 15 84.12 12 3...
THE INSTALLATION INSTRUCTIONS IN THIS MANUALARE ABBREVIATED. SEE THE FRONT COVER OF THISMANUAL FOR REFERENCES TO CODES AND STAN-DARDS. BOILER LOCATION Provide a level, solid foundation for the boiler. Location shouldbe near the chimney so that the Flue Pipe Connector orBreeching to the chimney is sh...
tion, heavy sooting and health hazards. Any oil-fired boilermust have a steady draft* and an ample supply of combustionair at all times during firing. If air supply or chimney draft* isunreliable, CO 2 and overfire draft* will change unpredictably. DO NOT vent this boiler to the same chimney flue us...