Page 2 - TABLE 1: Ratings and Dimensions
XL-2000 2 XL-20 0.65 91,000 78 68 8 x8x15 6 x 15 83.56 8 11/ 16 4 9/ 16 6¶ 1 1/ 4 25 3/ 8 XL-30H 0.85 119,000 104 90 8 x8x15 6 x 15 86.00 12 3/ 16 6 5/ 16 6 1 1/ 4 28 7/ 8 XL-30 1.00 140,000 121 105 8 x8x15 6 x 15 85.04 12 3/ 16 6 5/ 16 6 1 1/ 4 28 7/ 8 1.15 161,000 138 120 8 x8x15 6 x 15 84.12 12 3...
Page 3 - BOILER LOCATION; MINIMUM CLEARANCE
THE INSTALLATION INSTRUCTIONS IN THIS MANUALARE ABBREVIATED. SEE THE FRONT COVER OF THISMANUAL FOR REFERENCES TO CODES AND STAN-DARDS. BOILER LOCATION Provide a level, solid foundation for the boiler. Location shouldbe near the chimney so that the Flue Pipe Connector orBreeching to the chimney is sh...
Page 4 - TABLE 2: Provisions for Combustion and Ventilation Air Supply.
tion, heavy sooting and health hazards. Any oil-fired boilermust have a steady draft* and an ample supply of combustionair at all times during firing. If air supply or chimney draft* isunreliable, CO 2 and overfire draft* will change unpredictably. DO NOT vent this boiler to the same chimney flue us...
Page 6 - WATER PIPING FOR HOT WATER HEATING BOILERS; Alternate Air Eliminating System
XL-2000 6 The opening size recommendation just given is for guidanceonly. It is the installer’s responsibility to provide air for combus-tion and ventilation to all appliances, under all operating con-ditions, for each installation. See NFPA 31, latest edition formore specific details. INSTALLING CO...
Page 8 - CLEANING AND FILLING A NEW WATER BOILER; VOLUME OF WATER IN STANDARD PIPE OR TUBE; CARE AND MAINTENANCE
smoke and dry soot formation in the fire box. F. If smoke reading is satisfactory, but CO 2 can not be increased to a satisfactory level (12%) or overfire draft of0.02" W.C. can not be obtained, check for proper sealingbetween sections, between the hinged burner mountingdoor and front section, a...
Page 9 - DO NOT USE ETHYLENE GLYCOL BECAUSE IT IS TOXIC.
6. Use the flue brush to clean the pinned flueways between the sections.† A wire brush may be usedto remove any carbon accumulation that may havedeveloped in the combustion chamber. Vacuum theloose soot and debris from the boiler. 7. Inspect the burner combustion head. Clean if nec- essary and make ...
Page 11 - BURNER DATA—CARLIN BURNERS FOR PACKAGED BOILERS ONLY
BURNER DATA—CARLIN BURNERS FOR PACKAGED BOILERS ONLY XL-2000 11 XL-20 99-FRD 0.65 0.65 70° A DELAVAN 100 0 50 Closed 71399-00F-XL-20 0.65 70° W DELAVAN 100 0 50 Closed XL-30 99-FRD 1.00 1.00 70° A DELAVAN 100 2 80 Closed 71399-00F-XL-30 1.15 1.00 70° A DELAVAN 130 3 90 Closed XL-40 99-FRD 1.35 1.35 ...
Page 12 - BURNER DATA—BECKETT BURNERS FOR PACKAGED BOILERS ONLY
XL-2000 12 BURNER DATA—BECKETT BURNERS FOR PACKAGED BOILERS ONLY XL-20 (4) AFG F0 0.65 0.65 80° A DELAVAN 100 7 Blank/Closed 3 3/ 8 SF2201 XL-30H AFG F3 0.85 0.85 70° W DELAVAN 100 6 Blank/Closed 2 3/ 4 SF2204 XL-30 AFG F3 1.00 1.00 80° W DELAVAN 100 8 0 2 3/ 4 SF2202 1.15 1.00 80° W DELAVAN 130 10 ...
Page 13 - Figure 7A. Riello 40 Series
BURNER DATA - RIELLO BURNERS FOR PACKAGED BOILERS ONLY(RIELLO R-40 SERIES W/SHORT TUBE) † Air shutter and head settings shown are approximate ONLY. See START-UP page 7 NOTE: For proper insertion into combustion chamber see figure 8 XL-2000 13 BOILER MODEL RIELLO BURNER MODEL SLANT/FIN BURNER P/N SIN...
Page 14 - TURBULATOR SETTINGS - RIELLO 40 SERIES; Figure 9A; SETTING THE AIR ADJUSTMENT PLATE
XL-2000 14 BURNER DATA - RIELLO (continued) REGULATION OF THE TURBULATOR AND AIR SHUTTERFOR PROPER COMBUSTIONTurbulator Setting 1. Loosen nut, 1, then turn the screw, 2, until the index marker, 3, is aligned with the correct index number. 2. Retighten the retaining nut, 1. TURBULATOR SETTINGS - RIEL...