  • Page 2 – ICTORY VSPH Models; NOTE: Height dimensions increase by; Natural; Boiler; RATINGS AND DIMENSIONS; Figure 1. Dimensions data
  • Page 3 – LOCATION AND IDENTIFICATION OF PARTS; Figure 2. Location and identification of parts; Base Assembly
  • Page 4 – In no case may the boiler be installed on carpeting.; Figure 3. Victory “VSPH” boiler min. clearances for; INSTALLATION REQUIREMENTS
  • Page 5 – *AL29-4C is a registered Trademark of Allegheny Ludlum Corp; Manufacturer
  • Page 6 – EXAMPLE: Boiler model VSPH-180 is to be installed at sea; elbow; Equivalent Length of Various 90-Degree Elbows
  • Page 9 – VICTORY VSPH MODELS NON - DIRECT VENT, SIDEWALL VENTING; The height should be used as the SNOW LINE.
  • Page 10 – VICTORY VSPH MODELS- NON- DIRECT VENT, VENTING THROUGH A ROOF
  • Page 11 – VICTORY VSPH MODELS- NON - DIRECT VENT, UTILIZING AN EXISTING
  • Page 12 – VICTORY VSPH MODELS - DIRECT VENT, SIDEWALL VENTING
  • Page 14 – Figure 12. Direct vent, venting and air intake through a roof.; VICTORY VSPH MODELS; DIRECT VENT, VENTING AND AIR INTAKE THROUGH A ROOF
  • Page 15 – Selecting pipe size for natural gas:; ELECTRICAL WIRING
  • Page 16 – Figure 13b. Boiler control
  • Page 17 – ZONE VALVE SYSTEM USING V8043E/F ZONE VALVES; MULTIZONING OF VSPH BOILER; PUMP ZONING SYSTEM USING R845A RELAY; MULTIZONING OF VSPH BOILER; PUMP ZONING SYSTEM USING R882A/B RELAYS
  • Page 18 – Model; Boiler Water Content; Figure 17. Piping arrangement
  • Page 19 – Figure 18. Cooling system to a water boiler and chiller.
  • Page 20 – WHAT TO DO IF YOU SMELL GAS:; To Turn Off Gas to Appliance; GAS; FIG U RE; OPERATING INSTRUCTIONS
  • Page 21 – VSPH BOILER SEQUENCE OF OPERATION; PILOT LIGHTS AND
  • Page 22 – Boiler rated input in
  • Page 23 – SAFETY CHECK; LED’s FLASHING
  • Page 24 – Figure 21. Location and identification of pressure
  • Page 25 – General Troubleshooting Guide For Service Personnel; Turn off all electric power to the boiler before servicing.; CAUSE; Figure 22. Flue passage cleaning illustration
Loading the manual

IMPORTANT

READ ALL OF THE FOLLOWING

WARNINGS AND STATEMENTS

BEFORE READING THE

INSTALLATION INSTRUCTIONS

WARNING

LIQUEFIED PETROLEUM (L.P.)

PROPANE GAS-FIRED BOILERS

Installation location ONLY as permitted in paragraph

entitled "LIQUEFIED PETROLEUM (L.P.) PROPANE

GAS-FIRED BOILER LOCATION" on page 4 of this

instruction book.

The above warning does not apply to NATURAL gas-

fired boilers.

The installation must conform to the requirements of

the authority having jurisdiction or, in the absence of

such requirements, to the National Fuel Gas Code,

ANSI Z223.1-latest edition. The installation must also

conform to the additional requirements in this Slant/Fin

Instruction Book.

In addition where required by the authority having juris-

diction, the installation must conform to American

Society of Mechanical Engineers Safety Code for

Controls and Safety Devices for Automatically Fired

Boilers, No. CSD-1.

WARNING

This boiler, gas piping and accessories must be

installed, connected, serviced and repaired by a

trained, experienced service technician, familiar with all

precautions required for gas-fired equipment and

licensed or otherwise qualified, in compliance with the

authority having jurisdiction.

WARNING

The venting system of this boiler is under positive pres-

sure. Leakage from this system can be hazardous and if

not avoided can result in death or serious injury. In addi-

tion to the recommendations within this manual and the

User’s Information Manual, the venting system, from the

blower to the outdoor discharge, must be carefully

checked annually by a qualified service agency.

This manual must be left
with owner and should be
hung on or adjacent to
the boiler for reference.

V

ICTORY

VSPH

INSTALLATION AND OPERATING INSTRUCTIONS

Printed in U.S.A. 207

Par t No. 455035 Publication No. VSPH-40 Rev. A

Heating Contractor

Address

Phone Number

Boiler Model Number

Boiler Serial Number

Installation Date

DIRECT-VENT SEALED COMBUSTION BOILERS

HOT WATER MODELS VSPH-60 THROUGH VSPH-180

GAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES

TABLE OF CONTENTS

Dimensions, Rating and Orifice Sizes ........................................2
Identification of Par ts ..................................................................3
Installation Requirements ...........................................................4
Venting Application .....................................................................5
Boiler Room Air Supply and Ventilation ......................................5
Flue gas Venting Requirements..................................................5
Vent Material ..............................................................................5
Air Intake Material ......................................................................6
Flue and Air Intake Restrictions .................................................6
Non-Direct Vent Installation ........................................................8
Sidewall Venting, Non-Direct Vent ..............................................8
Vent Termination Location and Clearance ..................................8
Non-Direct Vent Ver tical Venting .................................................8
Direct Vent Installation ................................................................8
Sidewall Venting, Direct Vent ......................................................8
Vent/Air Intake Termination Installation.......................................8
Direct Vent, Venting and Air Intake through a Roof ..................13
Venting and Air Intake Regular Inspection ...............................15
Gas Piping ................................................................................15
Electrical Wiring ........................................................................15
Multi Zoning ..............................................................................18
Water Piping .............................................................................18
Wiring Diagram .........................................................................16
Operating Instructions...............................................................19
Gas Input Rate Adjustment ......................................................20
Boiler Control ............................................................................22
Sequence of Operation .............................................................21
Status of Indicator Lights (LED’s) .............................................22
Safety Check ...........................................................................23
Care and Maintenance .............................................................24
General Troubleshooting Guide ...........................................25-27

®

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - ICTORY VSPH Models; NOTE: Height dimensions increase by; Natural; Boiler; RATINGS AND DIMENSIONS; Figure 1. Dimensions data

V ICTORY VSPH Models 2 NOTE: Height dimensions increase by 1 1 ⁄ 2 " and depth increases to 28 1 ⁄ 2 " when combustible floor kit is used. Natural #49 50 50 50 51 51 51 52 52 52 Propane #57 58 59 59 60 60 61 62 63 63 VSPH-60 60,000 3 11 1 ⁄ 8 " 17 3 ⁄ 8 " VSPH-90 90,000 4 14 1 ⁄ 8 &#...

Page 3 - LOCATION AND IDENTIFICATION OF PARTS; Figure 2. Location and identification of parts; Base Assembly

V ICTORY VSPH Models 3 LOCATION AND IDENTIFICATION OF PARTS Figure 2. Location and identification of parts Base Assembly

Page 4 - In no case may the boiler be installed on carpeting.; Figure 3. Victory “VSPH” boiler min. clearances for; INSTALLATION REQUIREMENTS

V ICTORY VSPH Models 4 The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1- latest edition. This installation must also conform to the additional require- ments in this Slant/Fin In...