- Page 2 – Manufacturer’s; : The manufacturer shall specialize in manufacturing of on-line,; Factory Testing; : All materials and parts comprising the UPS shall be new, of; REQUIREMENTS
- Page 3 – Up to 1000 meters above sea level (up to 2000 meters with; UPS Module; : The UPS shall be covered by a full parts and labor warranty from the; Battery; shall have a minimum period of one year.; SERVICE AND SPARE PARTS; Self-adjustment of replaced subassemblies; APPROVED MANUFACTURERS & PRODUCT DESCRIPTION; : The specified equipment will be manufactured by APC by; Product Description
- Page 4 – DESCRIPTION
- Page 6 – Variable Frequency Pulse Width Modulated (PWM)
- Page 7 – SYSTEM CONTROLS AND INDICATORS
- Page 10 – MECHANICAL DESIGN AND VENTILATION
- Page 11 – Protection Against Deep Discharge and Self-Discharge; ACCESSORIES; Extended Battery Cabinet
- Page 13 – FIELD QUAILTY CONTROL & SERVICE ORGANIZATION
- Page 14 – END OF SECTION
- Page 15 – SPECIFICATION KEY; OUTPUT POWER RATINGS; 80V Core Voltage Only; BATTERY; Configuration Battery; INPUT CURRENTS; OUTPUT CURRENTS; KVA
- Page 16 – BATTERY DC CURRENT; ADC; WEIGHTS AND DIMENSIONS; UPS MODULE HEAT REJECTION
APC by Schneider Electric
MGE GALAXY 5000
Data Center Grade Three Phase Uninterruptible Power Supply
Parallel Module - Guide Specifications
40-130 kVA UPS
1.0 GENERAL
1.1 SUMMARY
This specification describes a three-phase, on-line, double conversion, solid state Uninterruptible
Power System hereafter referred to as the UPS. The UPS shall operate in conjunction with the
existing building electrical system to provide high quality power conditioning, back-up power
protection and distribution for electronic equipment loads. The system shall consist of a solid state
IGBT rectifier/inverter, power factor corrected rectifier, a 100% rated for continuous duty static
switch, battery plant, graphical status/control panel, and synchronizing circuitry as described herein.
1.2 STANDARDS
The UPS shall meet the requirements of the following standards:
A. UL listed under 1778, standards for uninterruptible power supply equipment
B. UL Canada (cUL)
C. FCC rules and regulations of part 15, subpart J, class A
D. IEC 1004/ANSI C62.41 Standards for Surge Withstand Ability
E. ISO 9001
F. The UPS shall be designed in accordance with the applicable sections of the documents
published by:
National Fire Protection Association (NFPA)/National Electric Code (NEC)
National Electrical Manufacturer’s Association (NEMA) & (NEMA PE 1)
Occupational Safety & Health Administration (OSHA)
1.3 SUBMITTALS
Submittals shall contain the following documentation:
A.
Installation Package:
Complete electrical characteristics and connection requirements.
Provide detailed equipment outlines with cabinet dimensions and spacing requirements;
location of conduit entry/exit paths; location of floor/seismic mounting; available battery
types/sizes; all cabinet weights; heat rejection and air flow requirements; single-line diagram;
control and external wiring.
B.
Product Data
: Provide catalog sheets and technical data sheets to indicate physical data and
electrical performance, electrical characteristics, and connection requirements.
C.
Manufacturer’s Installation Instructions
: Indicate application conditions and limitations of
use stipulated by Product testing agency. Include instructions for storage, handling, protection,
examination, preparation, installation, and starting of Product. Include equipment installation
APC – MGE Galaxy 5000 Specification (60Hz)
1
Effective: June 1, 2008 REV X0 JJG
Parallel Module
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
outline, connection diagram for external cabling, internal wiring diagram, and written instruction for installation. 1.4 FINAL SUBMITTALS Upon delivery of the UPS system the following submittals shall be included: A. A complete set of installation drawings showing all the information stated in secti...
UPS Module Operating : 0° to 40°C (32°F to 104°F) Non-Operating : -20° to +45°C (-4°F to 113°F) B. Relative humidity (operating and storage): 0 to 95% non-condensing C. Barometric Pressure: Up to 1000 meters above sea level (up to 2000 meters with ambient temperature less than 28°C) / (up to 12,000 ...
static switch, battery plant, graphical status/control panel, dry contact and communications ports, and synchronizing circuitry as described herein. 2.2 SYSTEM DESCRIPTION A. UPS Design Requirements 1. Output Power Continuous Rating : The continuous output power rating of the UPS shall be [ ] kVA at...