Page 2 - Manufacturer’s; : The manufacturer shall specialize in manufacturing of on-line,; Factory Testing; : All materials and parts comprising the UPS shall be new, of; REQUIREMENTS
outline, connection diagram for external cabling, internal wiring diagram, and written instruction for installation. 1.4 FINAL SUBMITTALS Upon delivery of the UPS system the following submittals shall be included: A. A complete set of installation drawings showing all the information stated in secti...
Page 3 - Up to 1000 meters above sea level (up to 2000 meters with; UPS Module; : The UPS shall be covered by a full parts and labor warranty from the; Battery; shall have a minimum period of one year.; SERVICE AND SPARE PARTS; Self-adjustment of replaced subassemblies; APPROVED MANUFACTURERS & PRODUCT DESCRIPTION; : The specified equipment will be manufactured by APC by; Product Description
UPS Module Operating : 0° to 40°C (32°F to 104°F) Non-Operating : -20° to +45°C (-4°F to 113°F) B. Relative humidity (operating and storage): 0 to 95% non-condensing C. Barometric Pressure: Up to 1000 meters above sea level (up to 2000 meters with ambient temperature less than 28°C) / (up to 12,000 ...
Page 4 - DESCRIPTION
static switch, battery plant, graphical status/control panel, dry contact and communications ports, and synchronizing circuitry as described herein. 2.2 SYSTEM DESCRIPTION A. UPS Design Requirements 1. Output Power Continuous Rating : The continuous output power rating of the UPS shall be [ ] kVA at...
Page 6 - Variable Frequency Pulse Width Modulated (PWM)
Incoming AC power shall be converted to a regulated DC output voltage by an IGBT (insulated gate bipolar transistor) power factor correction (PFC) rectifier. The PFC rectifier shall provide high quality DC power to charge the batteries and power the inverter and shall have the following characterist...
Page 7 - SYSTEM CONTROLS AND INDICATORS
1. Uninterrupted Transfer : The static bypass transfer switch shall automatically cause the bypass source to assume the critical load without interruption after the logic senses one of the following conditions: a) Inverter overload exceeds unit's rating b) Battery protection period expired and bypas...
Page 10 - MECHANICAL DESIGN AND VENTILATION
D. Audible Alarm Reset : The UPS shall provide an audible alarm that can be stopped using the user interface. If a new alarm is sensed after the original alarm has been silenced, it will reactivate the audible alarm. E. Remote Emergency Power Off (REPO) : The UPS shall be equipped with provisions fo...
Page 11 - Protection Against Deep Discharge and Self-Discharge; ACCESSORIES; Extended Battery Cabinet
3.2 BATTERY The UPS module shall use a valve regulated sealed lead acid heavy-duty industrial battery, designed for auxiliary power service in a UPS application. The primary battery shall be furnished with impact resistant plastic cases and housed in a matching cabinet(s) next to the UPS module. A. ...
Page 13 - FIELD QUAILTY CONTROL & SERVICE ORGANIZATION
160/320/520kVA depending on model selected. Secondary UPS isolation breakers (2 to 6) are standard – must be determined pre-orderd. Includes: PM800 Meter for SBC System Level Metering. E. 42” Distribution Cabinet: Distribution Cabinets are an available option to the System Bypass Cabinets not indivi...
Page 14 - END OF SECTION
END OF SECTION APC – MGE Galaxy 5000 Specification (60Hz) 14 Effective: June 1, 2008 REV X0 JJG Parallel Module
Page 15 - SPECIFICATION KEY; OUTPUT POWER RATINGS; 80V Core Voltage Only; BATTERY; Configuration Battery; INPUT CURRENTS; OUTPUT CURRENTS; KVA
SPECIFICATION KEY 2.2 A–1 OUTPUT POWER RATINGS 40 kVA/ 36 kW 50 kVA/ 45 kW 60 kVA/ 54 kW 80 kVA/ 72 kW 100 kVA/ 90kW 130 kVA /117kW 2.2 A-3 / A-4 INPUT / OUTPUT VOLTAGES 480V Core Voltage Only 2.2 A-5 BATTERY BACK-UP TIME (minutes) Configuration Battery 40 kVA 50 kVA 60 kVA 80 kVA 100 ...
Page 16 - BATTERY DC CURRENT; ADC; WEIGHTS AND DIMENSIONS; UPS MODULE HEAT REJECTION
2.2 D-2 BATTERY DC CURRENT 40 KVA 50 KVA 60 KVA 80 KVA 100 KVA 130 KVA ADC At Max End Voltage 109 137 164 219 273 355 3.1 C WEIGHTS AND DIMENSIONS Dimensions (Inches)/ WEIGHT (Lbs.) KVA UPS 40 to 80kVA UPS 100 to 130kVA TOP Entry Battery Height 75.0 75.0 75.0 75.0 Width 28.0 28.0 14.0 28/36/48 Depth...