Page 3 - Introduction; NSTALLATION; Read the Safety Guide before installing the UPS.; Unpacking; to 95% relative humidity
. 1 Introduction The APC by Schneider Electric Smart-UPS RT is a high-performance, uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electroni...
Page 4 - Wiring and Connecting the UPS; VA
2 Wiring and Connecting the UPS 5000/6000 VA XLI MODELS O NLY : H ARDWIRING I NSTRUCTIONS • Wiring must be performed by a qualified electrician. • Install a high magnetic 30/32 A utility circuit breaker. • Adhere to all national and local electrical codes. • Use #10 AWG gauge (5 mm 2 ) wire. 1. Swit...
Page 6 - serial com; for the information on the external
4 B ASIC C ONNECTORS serial com Power management software and interface kits can be used with the UPS. Use only interface kits supplied or approved by APC. Any other serial interface cable will be incompatible with the UPS connector. normal bypass Manual bypass enables the user to manually put conne...
Page 7 - UPS; Avoid using extension cords.; Do not
. 5 C ONNECTING E QUIPMENT AND P OWER TO THE UPS 1. Connect equipment to the UPS (cables not included for XLJ/XLT/XLTW models). 2. Avoid using extension cords. • 3000 VA XLJ/XLT/XLTW/XLI and 5000/6000 VA XLJ/XLT/XLTW models : Using a power cord, plug the UPS into a two-pole, three-wire, grounded rec...
Page 8 - PERATION; RT; Indicator Description; Troubleshooting; Feature Function
6 O PERATION Load S MART -UPS RT F RONT D ISPLAY Battery Charge Indicator Description Online The Online LED illuminates when the UPS is drawing utility power and performing double conversion to supply power to connected equipment. On Battery The UPS is supplying battery power to the connected equipm...
Page 9 - Battery Charge; On Battery Operation
. 7 Feature Function Cold Start When there is no utility power and the UPS is off, press and hold the button to power up the UPS and connected equipment. The UPS will emit two beeps. During the second beep, release the button. Self-Test Automatic: The UPS performs a self-test automatically when turn...
Page 11 - EPO; Adhere to National and local electrical codes when wiring the EPO.
. 9 N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OW ER C HUTE SOFTW ARE OPTIONAL S MART S LOT ACCESSORY CARDS OR T ERMINAL M ODE . F UNCTION F ACTORY D EFAULT U SER S ELECTABLE C HOICES D ESCRIPTION Low Bypass Point -30% of output voltage setting -15%, -20%, -25%, -30% Minimum voltage that the UPS ...
Page 12 - Business Edition
10 Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV. If circuit standard cannot be confirmed, use a contact closure switch. Use one of the following cable ty...
Page 14 - Replacing the Battery Module; for information on
12 M AINTENANCE AND T RANSPORT Replacing the Battery Module This UPS has an easy to replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the procedure. See your dealer or contact APC at the W...
Page 15 - Disconnecting the Battery for Transport; Shut down and disconnect any equipment attached to the UPS.
. 13 R EPLACING B ATTERY MODULES X Y Z [ \ ] ^ _ Disconnecting the Battery for Transport Always DISCONNECT THE BATTERY(s) before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The battery(s) may remain in the UPS. 1. Shut down and disconnect any equipment...
Page 16 - for assistance with complex UPS problems.
14 T ROUBLESHOOTING , S ERVICE , AND W ARRANTY I NFORMATION Use the table below to solve minor installation and operation problems. Refer to the APC Web site, www.apc.com for assistance with complex UPS problems. P ROBLEM AND P OSSIBLE C AUSE S OLUTION UPS WILL NOT TURN ON Battery not connected prop...
Page 18 - Service; Limited Warranty
16 Service If the UPS requires service do not return it to the dealer. Follow these steps: 1. Review the problems discussed in the Troubleshooting section of this manual to eliminate common problems. 2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com . • N...
Page 19 - EGULATORY; Radio Frequency Warnings; APC Worldwide Customer Support; Global support searching APC Knowledge Base and using e-support.
. 17 R EGULATORY Radio Frequency Warnings This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a...