Pneumatic Control Manual 717.1
Temperature Section
Product Bulletin T-3102
Issue Date 0882
© 1982 Johnson Controls, Inc.
1
Code No. LIT-7171130
T-3102 Heating-Cooling
Deadband Thermostat
The T-3102 Heating-Cooling
Deadband Thermostat is
designed for use in terminal air
conditioning units to modulate
heating and cooling controlled
devices in accordance with space
temperature variations. An
adjustable pressure regulator
provides a deadband between
heating and cooling modes which
encourages energy conservation
by eliminating heating and cooling
overlap.
The thermostat movement is
protected by a sturdy snap-on
cover which allows easy access to
the deadband and output
pressure adjustments. The
windows on the external set point
knob display the separate heating
and cooling set points.
Linear expansion or contraction in
the liquid filled bulb element
provides a direct proportional
relationship between temperature
and output pressure.
Mounting
The T-3102 can be mounted
in any position on a relatively
vibration-free surface. The
mounting bracket can be
repositioned to permit a wide
variety of mounting
arrangements (see dimension
drawing). The supply line
must be connected to the
restricted branch of the
1/4 in. barbed tee fitting.
Calibration
The T-3102 is factory tested
and calibrated to the mid spring
ranges of typical heating and
cooling valves (see operational
graph). Refer to
T-3102-A Technical Bulletin for
instructions on recalibrating the
instrument for special
applications.
Application and Drawing
Identification
Specifications
T-3102
Heating-Cooling Deadband Thermostat