Honeywell W7750A- User Manual

Honeywell W7750A

Honeywell W7750A– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18
19 Page 19
20 Page 20
21 Page 21
22 Page 22
23 Page 23
24 Page 24
25 Page 25
26 Page 26
27 Page 27
28 Page 28
29 Page 29
30 Page 30
31 Page 31
32 Page 32
33 Page 33
34 Page 34
35 Page 35
36 Page 36
37 Page 37
38 Page 38
39 Page 39
40 Page 40
41 Page 41
42 Page 42
43 Page 43
44 Page 44
45 Page 45
46 Page 46
47 Page 47
48 Page 48
49 Page 49
50 Page 50
51 Page 51
52 Page 52
53 Page 53
54 Page 54
55 Page 55
56 Page 56
57 Page 57
58 Page 58
59 Page 59
60 Page 60
61 Page 61
62 Page 62
63 Page 63
64 Page 64
65 Page 65
66 Page 66
67 Page 67
68 Page 68
69 Page 69
70 Page 70
71 Page 71
72 Page 72
73 Page 73
74 Page 74
75 Page 75
76 Page 76
77 Page 77
78 Page 78
79 Page 79
80 Page 80
81 Page 81
82 Page 82
83 Page 83
84 Page 84
85 Page 85
86 Page 86
87 Page 87
88 Page 88
89 Page 89
90 Page 90
91 Page 91
92 Page 92
93 Page 93
94 Page 94
95 Page 95
96 Page 96
97 Page 97
98 Page 98
99 Page 99
100 Page 100
101 Page 101
102 Page 102
103 Page 103
104 Page 104
105 Page 105
106 Page 106
107 Page 107
108 Page 108
109 Page 109
110 Page 110
111 Page 111
112 Page 112
113 Page 113
114 Page 114
115 Page 115
116 Page 116
Page: / 116

Table of Contents:

  • Page 2 – EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
  • Page 3 – List of Figures; ® RTU object details (variables not implemented in Excel 10 CVAHU
  • Page 5 – List of Tables
  • Page 6 – INTRODUCTION; Description of Devices; Excel 10 W7750A,B,C Constant Volume AHU Controller
  • Page 7 – Control Application; Bus network access; Control Provided; sensor or a
  • Page 8 – Title
  • Page 9 – Device
  • Page 10 – Abbreviations and Definitions
  • Page 11 – Construction; Controllers
  • Page 13 – PERFORMANCE SPECIFICATIONS
  • Page 16 – Bus communications
  • Page 17 – ® FUNCTIONAL PROFILE
  • Page 18 – ® RTU object details; The W7750A Unit supports the following hardware features:; Discharge Air Temperature:
  • Page 19 – CAUTION; IMPORTANT
  • Page 20 – Wall Modules
  • Page 22 – Configurations; General
  • Page 24 – STAGED HEATING/COOLING CONTROL
  • Page 25 – Fig. 15. Heat pump with two compressors and auxiliary
  • Page 26 – Occupancy Sensor; Window Open/Closed Digital Input
  • Page 27 – Modes of Operation
  • Page 29 – APPLICATION STEPS; Overview; Fig. 18. Connecting the portable operator terminal; Description
  • Page 30 – ® Bus Configuration Rules And Device Node Numbers.; Bus Layout; One L
  • Page 31 – Fig. 19. Wiring layout for one doubly terminated daisy-chain L
  • Page 32 – Fig. 20. Wiring layout for two singly terminated; Power Wiring; POWER BUDGET CALCULATION EXAMPLE
  • Page 33 – LINE LOSS
  • Page 34 – Fig. 22. Power wiring details for one Excel 10 per
  • Page 35 – Step 4. Prepare Wiring Diagrams; General Considerations
  • Page 38 – Fig. 27. Typical W7750A Controller AHU application
  • Page 39 – Fig. 29. W7750A Controller floating economizer damper
  • Page 40 – Fig. 30. Typical W7750B Controller with staged heating
  • Page 41 – enthalpy sensors and digital inputs. (For more
  • Page 42 – solid state humidity sensor. (For more information on
  • Page 43 – Bus Termination Module; Bus segment; RP7517B PNEUMATIC TRANSDUCER
  • Page 44 – ® Bus segment termination module wiring diagram.
  • Page 45 – ® Bus termination wiring options.; Step 5. Order Equipment; O I II
  • Page 48 – Part Number
  • Page 49 – Alarms; Name of alarm or error bit
  • Page 50 – Broadcasting the Service Message; W7750 Controller Status LED
  • Page 51 – pushbutton locations.; APPENDICES; Sensor Calibration
  • Page 52 – — The Proportional Gain (also called Throttling Range)
  • Page 53 – Common Operations
  • Page 55 – If the pushbutton is
  • Page 56 – Bus device, so that no physical; The three sources of manual override status are:
  • Page 57 – Bus to the other W7750 controllers. If the; Bus even if the time clock input is configured.; SETPOINT RAMPING
  • Page 59 – DIRTY FILTER MONITOR; Temperature Control Operations; See Fig. 49 for a diagram of a typical W7750 Unit.
  • Page 60 – STAGED COOLING CONTROL
  • Page 61 – CASCADE CONTROL OF MODULATING COOLING/HEATING; C) hysteresis with the lock-out control to prevent short; ECONOMIZER DAMPER CONTROL
  • Page 63 – User Address Indexes (all in alphabetical order); Page
  • Page 64 – Address; Mappable User Addresses and Table Number
  • Page 65 – Failure Detect User Addresses and Table Number
  • Page 106 – Map
  • Page 107 – re
  • Page 109 – Approximate Memory Size Estimating Procedure.
  • Page 110 – Table 29. Sensor Resistance Versus Temperature.; SENSOR RESISTANCE VERSUS TEMPERATURE; SENSOR RESISTANCE VERSUS TEMPERATURE
  • Page 112 – SENSOR VOLTAGE VERSUS HUMIDITY PERCENTAGE
  • Page 113 – Sensor Current
  • Page 114 – Fig. 61. C7400A Solid State Enthalpy Sensor output
  • Page 115 – SENSOR VOLTAGE VERSUS CO2 CONCENTRATION; SENSOR VOLTAGE VERSUS INPUT VOLTAGE TO A/D
  • Page 116 – SENSOR VOLTAGE VERSUS PRESSURE
Loading the manual

SYSTEM ENGINEERING

74- 2958- 1

® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc. • All Rights Reserved

Excel 10

W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Contents

Introduction .................................................................................................................................. 6

Description of Devices ..........................................................................................

6

Control Application ...............................................................................................

7

Control Provided ...................................................................................................

7

Products Covered.................................................................................................

8

Organization of Manual ........................................................................................

8

Applicable Literature .............................................................................................

8

Product Names .....................................................................................................

9

Agency Listings ....................................................................................................

9

Abbreviations and Definitions ............................................................................... 10
Construction ......................................................................................................... 11

Controllers ...................................................................................................... 11

PERFORMANCE SPECIFICATIONS ......................................................... 13
L

ON

M

ARK

® Functional Profile ..................................................................... 17

Inputs/Outputs: ............................................................................................... 18

ANALOG INPUTS:...................................................................................... 18
DIGITAL INPUTS: ....................................................................................... 19
TRIAC OUTPUTS ON THE (W7750B,C MODELS ONLY): ........................ 19
DIGITAL OUTPUTS: ................................................................................... 19

Wall Modules .................................................................................................. 20
Duct Sensor .................................................................................................... 20

Configurations ...................................................................................................... 22

General ........................................................................................................... 22
Allowable Heating and Cooling Equipment Configurations ............................ 24

STAGED HEATING/COOLING CONTROL ................................................ 24
MODULATING HEATING/COOLING CONTROL ....................................... 24
HEAT PUMP CONTROL............................................................................. 24
ECONOMIZER CONTROL ......................................................................... 25
PNEUMATIC ACTUATOR CONTROL ........................................................ 25
MIXED-OUTPUT-TYPE CONTROL ........................................................... 26

Occupancy Sensor ......................................................................................... 26
Window Open/Closed Digital Input ................................................................. 26
Wall Module Options ....................................................................................... 26
Dirty Filter Monitor .......................................................................................... 27
Indoor Air Quality (IAQ) Override ................................................................... 27
Smoke Control ................................................................................................ 27
Freeze Stat ..................................................................................................... 27

Modes of Operation .............................................................................................. 27

Application Steps .................................................................................................................................. 29

Overview .............................................................................................................. 29
Step 1. Plan the System ....................................................................................... 29
Step 2. Determine Other Bus Devices Required .................................................. 29
Step 3. Lay Out Communications and Power Wiring ........................................... 30

L

ON

W

ORKS

® Bus Layout ................................................................................ 30

Power Wiring .................................................................................................. 32

POWER BUDGET CALCULATION EXAMPLE .......................................... 32
LINE LOSS ................................................................................................. 33

Step 4. Prepare Wiring Diagrams ......................................................................... 35

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Honeywell W7750A

Summary

Page 2 - EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER 72-2958—1 2 General Considerations .................................................................................. 35W7750 Controllers .......................................................................................... 36 FACTORY DEFAULT D...

Page 3 - List of Figures; ® RTU object details (variables not implemented in Excel 10 CVAHU

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER 3 74-2958—1 List of Figures Fig. 1. Typical system overview. ................................................................................................................................................ 6 Fig. 2. Typical W7750 control application...

Page 5 - List of Tables

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER 5 74-2958—1 List of Tables Table 1. Agency Listing. ............................................................................................................................................................. 9 Table 2. List of Differences in W7750...

Other Honeywell Models