Honeywell TRADELINE T8090A- User Manual

Honeywell TRADELINE T8090A

Honeywell TRADELINE T8090A– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
Page: / 10

Table of Contents:

  • Page 2 – WHEN INSTALLING THIS PRODUCT...; CAUTION; LOCATION; IMPORTANT: Save package of screws and instructions
  • Page 6 – Checkout
  • Page 7 – Leave Owner’s Manual and assistance information in a; Calibration; THERMOMETER
  • Page 8 – Typical Wiring Diagrams
Loading the manual

1

69-0750—1

T8090A Heating, Cooling,

and Heating-Cooling Thermostat,

Wallplate and Subbase

D.F. • Rev. 10-94 • • ©Honeywell Inc. 1994 • Form Number 69-0750—1

Preparation

Check thermostat and subbase (if used) suitability for

the heating, cooling, or heating/cooling system. Refer to
Table 1.

Assemble tools required: flat bladed screwdriver, hand

or power drill with 3/16 in. drill bit, wire cutter/stripper or
sharp knife, bubble level or plumb bob and line.

Assure power is off to the heating, cooling, or heating/

cooling system at the main fuse panel. Most buildings have
a separate switch box or circuit breaker for disconnecting
power to the heating and cooling (if applicable) equipment.

This thermostat is compatible with all heating, cooling or

heating/cooling systems when thermostat is powered by
batteries. If thermostat is not powered by batteries, refer to
Table 1 for thermostat and system compatibility information.

TABLE 1—SYSTEM COMPATIBILITY FOR NON-BATTERY POWERED THERMOSTATS.

Type of Heating System to be Controlled

Conditions/Compatibility

Electric (Line Voltage)—Typical baseboard and
radiant

• The R8239D1015 Isolating Relay or R841 Silent

Switching Center must be installed in the thermostat
control circuit.

a,b

Fan Coil Unit

• Compatible. Assure correct subbase identity selected for

fan control.

b

Gas—Direct Spark Ignition (DSI), Intermittent
Pilot (IP), and Standing Pilot (SP)

• Compatible. If not using battery backup, assure that the

24V control transformer common is accessible for
connection to thermostat cable conductor and power to
the transformer is not regularly interrupted by high
temperature or limit operation.

b

Heat Pump

• Compatible. Assure correct subbase identity is selected

for fan control and changeover control (O terminal for
cool and B terminal for heat).

c

Hot Water Zone

• Honeywell 2-wire valves are compatible.

b

• Some non-Honeywell 2-wire valves will require an

R8239D1015 Isolating Relay in the thermostat control
circuit.

a,b

• Some 3-wire valves will require an R8239A1052

Isolating Relay in the thermostat control circuit.

a,c,b

Oil

• If not using battery backup, assure that the 24V control

transformer common is accessible for connection to
thermostat cable conductor and power to the transformer
is not regularly interrupted by high temperature, purge
cycle, or limit operation.

b

Vent Damper

• Honeywell damper motors are compatible.

b

• Some non-Honeywell damper motors will require an

R8239D1015 Isolating Relay in the thermostat control
circuit.

a

Check control amperage requirement.

c

Warm Air Zone

• Most are compatible.

b

a

If thermostat is not compatible with the system being controlled, the system will not operate. No hazard exists. The thermostat
will not be damaged unless it is used to directly control a line voltage system. For proper system operation, a Honeywell R841
or R8239D1015 Isolating Relay must be added to the thermostat control circuit.

b

Cut the two black heat anticipator jumper wires before installing the thermostat. See Set Heat Anticipator section.

c

Consult manufacturer for installation requirements.

TRADELINE

®

M3375

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - WHEN INSTALLING THIS PRODUCT...; CAUTION; LOCATION; IMPORTANT: Save package of screws and instructions

69-0750—1 2 M3375 Recycling Notice This control contains mercury in a sealed tube. Do not place control in the trash at the end of its useful life. If this control is replacing a control that contains mer- cury in a sealed tube, do not place your old control in thetrash. Contact your local waste man...

Page 6 - Checkout

69-0750—1 6 Remove the thermostat from the wallplate or subbase. Connect an ac ammeter of appropriate range (about 0A to2A) between the R and W terminals on the wallplate orsubbase except for electric heat and heat pump systems. Let the system operate for one minute.Adjust the heat anticipator lever...

Page 7 - Leave Owner’s Manual and assistance information in a; Calibration; THERMOMETER

7 69-0750—1 THERMOSTAT This thermostat was calibrated at the factory and should not need recalibration in the field. If recalibration seemsnecessary, first be sure wallplate or subbase is accuratelyleveled. Then check thermometer calibration. To check thermostat calibration, allow several hours of o...

Other Honeywell Models