Honeywell TRADELINE Q7100D- User Manual

Honeywell TRADELINE Q7100D

Honeywell TRADELINE Q7100D– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
Page: / 6

Table of Contents:

  • Page 2 – temperature averaging network for a
  • Page 3 – Subbase Installation; WIRING; CAUTION; IMPORTANT; heat and one-stage cool conventional system.
  • Page 5 – Mounting Thermostat on Subbase
Loading the manual

X-XX UL

INSTALLATION INSTRUCTIONS

®U.S. Registered Trademark
Copyright © 1996 Honeywell Inc. • • All Rights Reserved

Q7100A,C,D

Thermostat Subbases

APPLICATION

The Q7100 Thermostat Subbases provide electronic
control of commercial 24 Vac single or multistage heat
pump or conventional heating and cooling systems.
Select models have terminals for light emitting diodes
LEDs, remote temperature sensors and remote setback
timer. The LED models have up to two field configurable
LEDs and up to two factory assigned LEDs. Refer to
Table 1. All Q7100 Thermostat Subbases require a
common wire to the supply power.

Table 1. Description of Q7100 Subbases.

Use

Stages

a

Q7100 T7100

System

Heat

Cool

Figs.

A

D or F Co nventional

1 or 2

1 or 2

8-9

C

E or F Heat pump

1, 2 or 3 1 or 2

10-14

D

E or F Heat pump

1 or 2

1 or 2

15

a

Depends on the model.

RECYCLING NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do

not

place your old

control in the trash.

Contact your local waste management authority
for instructions regarding recycling and the proper
disposal of the old thermostat.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow

the instructions can damage the product or cause
a hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained, experienced service

technician.

4. After completing installation, use these instructions

to check out the product operation.

CAUTION

Disconnect power supply to prevent electrical
shock or equipment damage.

Location

Subbase without Remote-Mounted Temperature Sensor

Install the subbase about 5 ft (1.5m) above the floor in an
area with good air circulation at average temperature.
See Fig. 1.

Do not install the subbase where it can be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

Subbase with Remote-Mounted Temperature Sensor(s)

Install the subbase in an area that is accessible for
setting and adjusting the temperature and settings.

Install the remote-mounted sensor(s) about 5 ft (1.5m)
above the floor in an area with good air circulation at
average temperature. See Fig. 1.

Do not mount the sensor(s) where it can be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

If more than one remote sensor is required, they must be
arranged in a temperature averaging network consisting
of two, three, four, five or nine sensors. See Fig. 2
through 6.

69-0931-3

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - temperature averaging network for a

69-0931—3 2 Q7100A,C,D THERMOSTAT SUBBASES Fig. 2. Two T7047G Sensors providing a temperature averaging network for a T7100/Q7100 Thermostat/Subbase. Fig. 3. Two T7047C Sensors and one T7047G Sensor providing a temperature averaging network for a T7100/Q7100 Thermostat/Subbase. Fig. 5. Five T7047G S...

Page 3 - Subbase Installation; WIRING; CAUTION; IMPORTANT; heat and one-stage cool conventional system.

69-0931—3 3 Q7100A,C,D THERMOSTAT SUBBASES Fig. 6. Nine T7047C Sensors providing a temperature averaging network for a T7100/Q7100 Thermostat/Subbase. Subbase Installation The subbase can be mounted horizontally on the wall ora 2 in. x 4 in. wiring box. Position the subbase horizon-tally on the wall...

Page 5 - Mounting Thermostat on Subbase

69-0931—3 5 Q7100A,C,D THERMOSTAT SUBBASES Fig. 14. Typical hookup of Q7100C1008 in a two-stage heat and two-stage cool heat pump system. Includes remote temperature sensor and remote setback timer. L1(HOT) L2 M4835A FANRELAY D O E B W2 Y2 COOLCHANGEOVERVALVE SUBBASE 2 X HEATRELAY 1 G EM. HT. RELAY ...

Other Honeywell Models